ML20050T150
| ML20050T150 | |
| Person / Time | |
|---|---|
| Site: | Summer |
| Issue date: | 03/31/1982 |
| From: | Youngblood B Office of Nuclear Reactor Regulation |
| To: | Nichols T SOUTH CAROLINA ELECTRIC & GAS CO. |
| References | |
| NUDOCS 8204140617 | |
| Download: ML20050T150 (2) | |
Text
_
l l
s.
DISTRIBUTION v Docket' Fil e t bec: TERA LB#1 Rdg. ~
PDR l
JYoungblood LPDR MService NSIC MAR 311982 WKane TIC DEisenhut ACRS (16)
Docket No.:
S0-395 SHanauer RMattson HThompson Mr. T. C. Nichols, Jr.
RVollmer 9
Vice President & Group Executive RHartfield, M Nuclear Operations OELD gO g
g 9
South Camlina Electric & Cas Company OIE Post Office Box 764 g?PA69W
~
3 Columbia, South Carolina 29218 C
V o
Dear Mr. Nichols:
cu
Subject:
Alternate Safe Shutdown System - Virgil C. Sunener Nuclea Subsequent to our issuance of Supplement No. 3 to the Safety Evaluation Report (SER), our position has been further clarified regarding the need to provide direct indication of reactivity control in the form of a source range neutron flux monitor for the alternative shutdown system to meet Appendix R concerns for fire in the control complex. Refer to Supplement No. 3 to the SER, Section 9.5.1, Alternative and Dedicated Shutdown-Appendix R in which I
we included our initial evaluation.
It is our current position that you should provide a source range neutron flux monitor either at the control room evacuation panel or another location independent of the control complex as part of the alternate safe shutdown system available in the event of a control complex fire and resulting control room evacuation.
i This matter must be resolved prior to the issuance of a low-power license for the facility.
Sincerely, l
crisinai siiIAeatyt l
li. J. Youns o*4 u
B. J. Youngblood, Chief Licensing Branch No. 1 Division of Licensing cc: See next page i
l "The reporting and/or recordkeeping requirements contained in this letter
"## #t#***#th""t#"#'UP'"d*"t8#
therefore, O'.3 clearance is not required P20414061/ 820331 under P.L.96-511.'
gDRADOCK 05000395 PDR
, t' } /
... LB#1 DL:n W
DL:
omcr>
33.. 9.....
8.JY oo,d 3
om>
7 Nnc ronu ais oo-soi nncu oao OFFICIAL RECORD COPY usam mi-m.eo
Mr. T. C. Nichols, Jr.
Vice President & Group-Executive Nuclear Operations South Carolina Electric & Gas Company Post Office Box 764 Columbia, South Carolina 29218 cc: Mr. Henry.Cyrus Senior Vice President South Carolina Public Service Authority 223 North Live Oak Drive Moncks Corner, South Carolina 29461 J. B. Knotts, Jr., Esq.
Debevoise & Liberman 1200 17th Street, N. W.
Washington, D. C.
20036 Mr. Mark B. Whitaker, Jr.
Group Manager - Nuclear Engineering & Licensing South Carolina Electric & Gas Company Post Office 764 Columbia, South Carolina 29218 Mr. Brett Allen Bursey Route 1, Box 93C Little Mountain, South Carolina 29076 Resident Inspector / Summer NPS c/o U. S. NRC-Route 1, Box 64 Jenkinsv111e, South Carolina 29065 Mr. James P. O'Reilly U. S. NRC, Region II 101 Marietta Street Suite 3100 Atlanta, Georgia 30303
,