ML20050D449

From kanterella
Jump to navigation Jump to search
Proposed Tech Specs Re Surveillance of motor-driven Emergency Feedwater Pump
ML20050D449
Person / Time
Site: Arkansas Nuclear Entergy icon.png
Issue date: 04/05/1982
From:
ARKANSAS POWER & LIGHT CO.
To:
Shared Package
ML20050D447 List:
References
NUDOCS 8204120215
Download: ML20050D449 (1)


Text

,

s PLANT SYSTEMS EMERGENCY FEEDWATER SYSTEM LIMITING CONDITION FOR OPERATION 3.7.1.2 Two emergency feedwater pumps and associated flow paths shall be OPERABLE with:

a. One motor driven pump capable of being powered from an OPERABLE emergency bus, and
b. One turbine driven pump capable of being powered from an OPERABLE steam supply system.

APPLICABILITY: MODES 1, 2 and 3.

ACTION:

With one emergency feedwater pump inoperable, restore the inoperable pump to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in H0T SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.

SURVEILLANCE REQUIREMENTS i 4.7.1.2 Each emergency feedwater pump shall be demonstrated OPERABLE:

l

! a. At least once per 31 days by:

1. Verifying that the turbine driven pump delivers a flow of 1 485 gpm which is capable of being supplied to the steam generators at a discharge pressure of

> 1200 psig when the secondary steam supply pressure is greater than 865 psig. The provisions of specification 4.04 are not applicable.

2. Verifying that the electric driven pump delivers a flow of 1 485 gpm which is capable of being supplied to the steam generators at a discharge pressure of l

2 1200 psig.

3. Verifying that each valve (manual, power operated or automatic), in the flow path that is not locked, sealed, or otherwise secured in position, is in its correct position.

ARKANSAS - UNIT 2 3/4 7-5 l

8204120215 820405 PDR ADOCK 05000368 P PDR

- - -