McGUIRE NUCLEAR STATION l

Operating Status Report I

1.

Personnel Exposure For the month of December, no individual (s) excedded 10 percent of their i

allowable annua 1' radiation dose limit.

l 2.

The total station liquid release contribution to whole body dose for l

December has been compared with the Technical Specifications annual value of 3 mrem; the total release for December was less than 10 percent.of j

this limit.

1 The total station gaseous release contribution to-any organ dose for December has been compared with the derived Technical Specifications annual value of 15 mrem; the total release for December was'less than 10 percent of this limit.

1 a

4 1

f I

8204050042 820215 PDR ADOCK 05000369 R

PDR

CORRECTED COPY OPERATING DATA REPORT.

DOCKET NO; 50-369 DATE 2-15-82 CO>lPLETED BY J. A. Reavis TELEPilONE 704-171-8532 OPERATING ST.\\TUS

1. Unit Name:

McGuire Unit 1 Notes

2. Reporting Period:

December, 1981

3. Licensed Thermal Power talWti:

3 411 1 220

.l. Nameplate Rating (Grow ilwel:

5. Design Electrical RatingINet alWen:

1 180

6. Stasimum Dependable Capacity (Gross.\\lWe):
7. bla\\imum Dependable Capacity (Net alw l:

820 e

S. If Changes Occur in Capacity Rating titems Number 3 Through ') Since Last Report. Give Reasons:

9. Power Level To Which Restricted. lf Any (Net >!We):
10. Reasons For Restrictions. lf Any:

This 51onth Yr..to Date Cumulative 744.0 744.0 744.0

11. Ilours in Reporting Period
12. Number Of 11 mrs Reactor Was Critical 45.7 45.7 45.7
13. Reactor Resene Shutdown flours
14. Ilours Generator On Line 45.7 45.7 45.7
15. Unit Resene Shutdown !!ours
16. Gross Thermal Energy Generated (>lwill 84 955 84 955 84 955 28 436 28 436 28 436
17. Gross Electrical Energy Generated (.\\lWil)

IS. Net Electrical Energy Generated (SIWil) 19 056 19 056 19 056

19. Unit Service Factor 6.1 6.1 6.1 6.1 6.1 6.1
20. Unit Availability Factor
21. Unit Capacity Factor (Uning.\\lDC Nett 2.2 2.2 2.2
22. Unit Capacity Factor (Using DER Net) 2.2 2.2 2.2
23. Unit Forced Outace Rate 93.9

'93.9 93.9

24. Shutdowns Scheduled Oser Nest 6 ilonths(Type.Date.and Duration of Eacht; Bearing Inspectitn S/G Eddy Current Testing to February is shutdown Online March 7, 1982 25 If Shut Down -\\t End Of Report Permd. Estimated Date of Startup: January 2 1982

- 26. Units In Test Status (Prmr to Conunercul Operationj:

Forecast Achiesed INITI \\ L CRITICAll1 Y INill \\L LLLClRICIf Y CO\\1\\lLRCI \\ L Ol'LR A flON (9/77)

8 CORRECTED COPY 50-369 7-DOCKET NO.

UNITSilUTDOWNS ANDl'OWEli REDUC 110NS UNIINAMg McGuire Unit l'.

DA TE 2-15-82 COMPLETED IlY J. A. Reavis REPORT MONTl! December. 1981 TELEPilONE ' 704-373-8552 "L

c

.] g 4YE Licensee

,E -r,

[*?

Canse A corrective o

No.

Ibte i

5g js&

Event 3,y F-Action to

~gg Report er mL E'

Prevent ' Recurrence y 2,,

d' o

o g

C 1-p 81-12-01 S

3 ZZ ZZZZZZ Holding at 75% power for power escalation testing.

1 81-12-02 F

.33 B

3 ZZ ZZZZZZ During shutdown to eddy current steam generator tubes, t-he unit tripped while performing a loss of offsite power test.

2 81-12-02 F

218.00 B

CB HTEXCH Eddy current of selected tubes in the "A" steam generator.

3 81-12-12 F

480.00 A

HA

'IURBIN Extensica to steam generator outage for replacement of electrical generator hydrogen cooler.

I 2

3 4

17: Forced Reamn:

Method:

Exhibit G. instructions S: Scheduleil A. Equipment Failure (Explain) 1 -Manual for Preparation of Data 11 Maintenance of Test 241anual Scram, Entry Sheets for Licensee C-Refueling 3 Automatic Serain.

Event Report (LElt) File (NURI:C.

D.Itegulatory Restriction 4 Other(Explain) 0161)

E Ope.ator Training & License Examination F Administrative 5

G-Operational E ror (thplain)

Eshibit 1 - Sanie Soinee (9/77)

II-Ot her (lixplain)

.