Advises That Special Simulated Loss of All Ac Test Is Not Satisfactory Substitute for Designated Preoperational Reactor Core Isolation Cooling Tests
ML20049H492
Person / Time
Site: Grand Gulf  
Issue date: 02/19/1982
From: Schwencer A
Office of Nuclear Reactor Regulation
To: Mcgaughy J
MISSISSIPPI POWER & LIGHT CO.
References
NUDOCS 8203030155
Download: ML20049H492 (1)


Text

-

DISTRIBUTION:

  1. O I 3 1902 Docket File bec: TERA LB#2 File NSIC DEis enhut/RPurpl e NRC PDR RTedesco Local PDR Docket Nos. 50-416 9 ASchwencer ACRS (16)

~ and. 41 7. '

DHouston EHylton Wagner, OELD N

D ffr. James P. McGaughy, Jr.

01&E Assistant Vice President Region II Mississippi Power and Light Co.

Resident Inspec RECE;yUU P. O. Box 1640 SHanauer m

Jackson, Mississippi 39205 RMattson

. P; FEB221986 Il0 HThompson

,6 sacun g D

Dear Mr. McGaugby:

RVollmer d

    • * **an RHartfield, MPA b

//

SUBJECT:

RETENTION OF RCIC TESTING W. Long, PTRB g

4 In your letter of December 4,1981, you stated that certain RCIC tests at Grand Gulf, which you were committed to perform, need not be done because another test (Simulated Loss of All A/C Power) will be performed.

The RCIC tests to be deleted involved the following:

A.

Startup of the RCIC System after Loss of AC Power to the

system, B.

Operation of the RCIC system with a sustained loss of AC power to the system, and C.

RCIC operation to demonstrate DC separation.

These tests are within the scope of preoperational testing described in Regulatory Guide 1.68 ( Appendix A.l.d.).

The Special Simulated Loss of All A/C Test is not a satisfactory substitute for these tests because it will not be performed prior to operation. Therefore, the staff will require that the tests listed above be performed or that your presently planned initial test program be expanded, as necessary, to accomplish the objectives of these tests.

He request that you provide your reply on this matter not later than April 1,1982.

If you require any clarification of this request, please contact fl. D. Houston, Project Manager, (301)-492-8430.

Sincerely, I

A. Schwencer, Chief Licensing Branch No. 2 Division of Licensing t