3 ADMINISTRATIVE CONTROLS RECORDRETENTION(Continued) e.

Records of transient or operational cycles for those facility components identified in Table 5.7.1-1.

f.

Records of reactor tests and experiments.

g.

Records of training and qualification for current members of the unit staff.

h.

Records of in-service inspections performed pursuant to these Technical Specifications.

i.

Records of Quality Assurance activities required by the Operational Quality Assurance Manual.

j. Records of reviews perforned for changes made to procedures or equipment or reviews of tests and experiments pursuant to 10 CFR 50.59.

k.

Records of meetings of the ORC and the SRC.

1.

Records of environmental qualification which are covered under the Provisions of Section 6.13.

6.11 RADIATION PROTECTION PROGRAM Procedures for personnel radiation protection shall be prepared consistent with the requirements of 10 CFR Part 20 and shall be approved, maintained and adhered to for all operations involving personnel radiation exposure.

6.12 HIGH RADIATION AREA 6.12.1 In lieu of the " control device" or " alarm signal" or " locked barrier with positive control over each individual entry" required by paragraph 20.203 (c)(2) of 10 CFR 20, each high radiation area in which the intensity of radiation is greater than 100 mrem /hr shall be barricaded and conspicuously posted as a high radiation area.

Entrance to these areas without a " control device" or

" alarm signal" or " locked barrier", shall be controlled by requiring issuance of a Special Work Permit (SWP).* Any individual or group of individuals per-mitted to enter such barricaded areas shall be provided with or accompanied by one or more of the following:

  • Health Physics personnel or personnel escorted by Health Physics personnel shall be exempt from the SWP issuance requirement during the performance of l

their assigned radiation protection duties, provided they comply with approved 4

radiation protection procedures for entry into high radiation areas.

6-18 LACBWR R110020240 810924 PDR ADOCK 05000409 p

PDR

ADMINISTRATIVE CONTROLS HIGH RADIATION AREA (Continued) a.

A radiation monitor'lng device which continuously indicates the radiation dose rate in the area.

b.

A radiation monitoring device which continuously integrates the radiation dose ratu in the area and alarms when a preset integrated dose is received.

Entry into such areas with this monitoring device may be made after the dose rate level in the area has been estab-lished anc personnel have been made knowledgeable of them, c.

An individusi qualified in radiation protection procedures who is equippad with a radiation dose rate monitoring device. This indi-vidual shall be responsible for providing positive control over the activities within the area and shall perform periodic radiation surveillance at the frequency specified by the unit Health Physicist in the Specic' hi Permit.

6.13 ENVIRONMENTAL QUALIFICATION

  • A.

By no later than June 30, 1982, all safety-related electrical equipment in the facility shall be qualified in accordance with the provisions of:

Division of Operating Reactors " Guidelines for Evaluating Environmental Qualification of Class IE Electrical Equipment in Operating Reactors" (DOR) Guidelines"; or, NUREG-0588, " Interim Staff Pcsition on Environmental Qualification of Safety-Related Electrical Equipment", December 1979.

Copies of these documents are attached to Order for Modification of License DPR-45 dated October 24, 1980.

B.

By no later than December 1,1980, complete and auditable records must be available and maintained at a central location which describe the environmental qualification method used for all safety-related electrical equipment in sufficient detail to document the degree of

' compliance with the D0R guidelines or NUREG-0588. Thereafter, such records should be updated and maintained current as equipment is replaced, further tested, or otherwise further qualified.

  • NRC Order dated 10/24/80.

6-19 LACBWR