Text
i eco 3
UNITED STATES 1
'f NUCLEAR REGULATORY COMMISSION
(-
,/
WASWNGTON, D C. 2055N August 3, 1993 Docket Nos. 50-325 and 50-324 Mr. R. A. Anderson, Vice President Carolina Power & Light Company j
Brunswick Steam Electric Plant Post Office Box 10429 Southport, North Carolina 28461
Dear Mr. Anderson:
SUBJECT:
REQUEST FOR ADDITIONAL INFORMATION REGARDING SERVICE WATER SYSTEM TECHNICAL SPECIFICATION AMENDMENT REQUEST - BRUNSWICK STEAM ELECTRIC PLANT, UNITS 1 AND 2 (TAC NOS. M85466 AND M85467)
By letter dated December 31, 1992, as supplemented by letter dated July 20, 1993, Carolina Power & Light Company (CP&L or the licensee) requested an amendment to the service water system technical specifications (TS) for the Brunswick Steam Electric Plant, Unit Nos. I and 2 (BSEP). Analyses that were developed using a computer model of the BSEP service water system and which were used to support the proposed TS amendment were provided as attachments to the letter dated July 20, 1993. The amendment request proposes:
(1) revision of the number of nuclear service water pumps (NSWPs) required to be operable from two NSWPs per unit to three NSWPs serving the site whenever either unit is in operational condition 1, 2, or 3; (2) revision of the action times associated with certain SWS pump configurations in all operational conditions; i
(3) incorporation of TS surveillance 4.7.1.2.c into proposed action b.4 of TS 3.7.1.2; addition of a quarterly surveillance of the pressure switch logic and valve actuation capability associated with the SWS supply to the emergency diesel generators (EDGs); and (4) complete revision of the bases for TS 3/4.7.1.2.
The staff has completed an initial review of the submittals. We have identified areas where additional information is required to complete our review. Our Request for Additional Information is provided as Enclosure 1.
Y.s hk 9308200122 930803 DR ADOCK 05000324 '
l, PDR j
August 3, 1993 Mr. R. A. Anderson The reporting and/or recordkeeping requirements contained in this letter affect fewer than ten respondents; therefore, OMB clearance is not required under P. L.96-511.
Should you have any questions, please contact me at 301-504-1457.
Sincerely, ORIGINAL SIGNED BY:
Patrick D. Milano, Senior Project Manager Project Directorate II-l Division of Reactor Projects - I/ll Office of Nuclear Reactor Regulation cc:
See next page DI ST RIP,UT ION:
Docket file NRC/ Local PDRs PD 11-1 Reading File S.A. Varga G.C. Lainas S.S. Bajwa C.E. Carpenter P.D. Milano C.E. McCracken 8-D-1 S.R. Jones 8-D-1 OGC ACRS (10)
E.W. Merschoff, R-Il cc:
Plant Service list OFC LA$Pk2'J :j)RPE PE:PD21:DRPE PM:PD21;DRPE AD:PD21:DRPE NAME PDNIINb CECarpenter:tmw PDMilano SSMA DATE 08/ h /93 08/ 1_/93 N
08/ O /93 08/'b/93 Document Name:
BRN85466.RAI
Mr. R. A. Anderson Brunswick Steam Electric Plant Carolina Power & Light Company Units 1 and 2 CC*
Mr. Mark S. Calvert Mr. H. A. Cole Associate General Counsel Special Deputy Attorney General Post Carolina Power & Light Compan)
State of North Carolina Post Office Box 1551 Post Office Box 629 Raleigh, North Carolina 27602 Raleigh, North Carolina 27602 Mr. Kelly Holden, Chairman Mr. Robert P. Gruber Board of Commissioners Executive Director Post Office Box 249 Public Staff - NCUC Southport, North Carolina 28422 Post Office Box 29520 Raleigh, North Carolina 27626-0520 Resident inspector U.S. Nuclear Regulatory Commission Mr. H. W. Habermeyer, Jr.
Star Route 1, P.O. Box 208 Vice President Southport, North Carolina 28461 Nuclear Services Department Carolina Power & Light Company Regional Administrator, Region II Post Office Box 1551 - Mail OHS 7 U.S. Nuclear Regulatory Commission Raleigh, North Carolina 27602 101 Marietta St., N.W., Ste. 2900 Atlanta, Georgia 30323 Mr. Dayne H. Brown, Director Division of Radiation Protection N.C. Department of Environmental, Commerce and Natural Resources Post Office Box 27687 Raleigh, North Carolina 27611-7687 Mr. J. M. Brown Plant Manager - Unit 1 Carolina Power & Light Company Brunswick Steam Electric Plant Post Office Box 10429 i
Southport, North Carolina 28461 i
Public Service Commission State of South Carolina
~
Post Office Drawer 11649 Columbia, South Carolina 29211 Mr. C. C. Warren Plant Manager - Unit 2 Brunswick Steam Electric Plant Post Office Box 10429 Southport, North Carolina 28461 l
ENCLOSURE I REQUEST FOR ADDITIONAL INFORMATION REGARDING BRUNSWICK STEAM ELECTRIC PLANT SERVICE WATER SYSTEM TECHNICAL SPECIFICATION REVISION 1.
Carolina Power & Light Company, the licensee for Brunswick Steam Electric Plant, is requested to provide Engineering Evaluation Reports 91-0039 and 91-0450 that document the acceptability of the calibration of the Unit I and Unit 2 service water system computer models to test data.
The licensee is also requested to provide the test procedure and most recent test results for Periodic Tests 1-PT-24.6.4 and 2-PT-24.6.4.
2.
The licensee is requested to describe the basis for the allowance of operator action greater than ten minutes after the onset of a design basis accident.
Remote operation from the control room should be addressed separately from local manual actuation.
3.
The licensee is requested to describe the current status of modifications to delete the minimum flow setpoints for service water valves 1(2)-SW-V103 and 1(2)-SW-V106.