f "%,

f j'"

UNITED STATES g

n a 3.i

.,1 NUCLEAR REGULATORY COMMISSION _

p

' WASHINGTON, D.C. 20S56 g..... /

r May 19, 1993 1

q l

I Docket No. 50-260 N0ED 93-6-017

-Dr. Mark 0. Medford, Vice President j

Technical Support Tennessee Valley Authority 1

3B Lookout Place 1101 Market Street

]

Chattanooga, Tennessee 37402-2801 7

Dear Dr. Medford:

SUBJECT:

NOTICE OF ENFORCEMENT DISCRETION FOR TENNESSEE VALLEY AUTHORITY REGARDING BROWNS FERRY NUCLEAR PLANT UNIT 2 l-!

By letter dated May 17, 1993, the Tennessee Valley Authority (TVA) requested j

~

the U.S. Nuclear Regulatory Commission (NRC) to exercise its discretion not to-enforce compliance with the required a::tions of technical specification l

Limiting Condition for Operation (LCO) 3.5.8.9.

TVA informed the KRC that required repairs to an inboard residual heat removal (RHR) injection valve would render the Browns Ferry Nuclear Plant (BFN) Unit 2 incapable of.

i providing an automatic low pressure coolant injection (LPCI) flow path as required by LC0 3 5.B.9.

TVA provided, as justification for continued operation, a commitment that both

[i Core Spray loops will remain operable during repair activities.

Furthermore, TVA stated that the RHR loop being used for shutdown cooling will retain.the

-l capability to be manually realigned for operation in'the LPCI mode. TVA also stated that plant operators are trained and have procedures available to-perform this realignment, and that these procedures would be reviewed with the plant operators prior to utilizing this enforcement discretion.

i Based on our review of your justification, including the compensatory measures' identified above, we have concluded that this course of action involves minimum or no safety impact, and we are satisfied that this exercise of.

.i enforcement discretion is warranted from a public health and safety perspective. Therefore, it is our intention to exercise discretion for the period from 4:00 p.m. Eastern Daylight Time, Monday, May 17, 1993 until 4:00 a.m. Eastern Day!ight Time, Friday, May 21, 1993. However, we will j

t E C H E CEidT B1 CGPY 9306010205 930519

ADOCK 0500 0

gDR g

1 1

I Dr. Mark 0. Medford consider enforcement action, as appropriate, for the conditions that -led to the need for this exercise of enforcement discretion. NRC staff review of TVA's December 23, 1992 request for a license amendment, including revisions i

to LCO 3.5.B.9, is continuing.

Sincerely, Original signed by Gus C. Lain 2s,-Assistant Director for Region II Reactors Division of Reactor Projects - I/II Office of Nuclear Reactor Regulation cc: See next page i

i

.e i

P e

i

  • Previously concurred RII-PDII-4/LA PDII-4/PMr./ PDII-4/PM PDII-4/D
  • DSSA Ah1

/ff A

\\yd 7alecon FHebdonh61-MVirgilio EMerschoff Gdh$nas MSanders JWilliams:as TRoss 3'//7/93 3~//7 /93

('/19/93 s/pg/93 s /1g /93 05/17/93

['/h/93 DOCUMENT NAME:

BFN\\N0ED93-6.017 L

e

~

[

t Tennessee Valley Authority Browns Ferry Nuclear Plant ATTN: Dr. Mark 0. Medford CC:

Mr. W. H. Kennoy, Director State Health Officer Tennessee Valley Authority Alabama Dept. of Public Health ET 12A 434 Monroe Street 400 West Summit Hill Drive Montgomery, Alabama 36130-1701 Knoxville, Tennessee 37902 Mr. R. M. Eytchison, Vice President Regional Administrator Nuclear Operations U.S.N.R.C. Region II Tennessee Valley Authority 101 Marietta Street, N.W.

3B Lookout Place Suite 2900 1101 Market Street Atlanta, Georgia 30323 Chattanooga, Tennessee 37402-2801 Mr. Charles Patterson Site Licensing Manager Senior Resident Inspector Browns Ferry Nuclear Plant Browns Ferry Nuclear Plant Tennessee Valley Authority U.S.N.R.C.

P.O. Box 2000 Route 12, Box 637 Decatur, Alabama 35602 Athens, Alabama 35611 Mr. O. J. Zeringue, Vice President Manager, Nuclear Assurance Browns Ferry Nuclear Plant and Licensing Tennessee Valley Authority Browns Ferry Nuclear Plant P.O. Box 2000 Tennessee Valley Authority Decatur, Alabama 35602 P. O. Box 2000 Decatur, Alabama 35602 Mr. M. J. Burzynski, Manager Tennessee Valley Authority Nuclear Licensing and Regulatory Affairs SB Lookout Place 1101 Market Street Chattanooga, Tennessee 37402-2801 TVA Representative Tennessee Valley Authority 11921 Rockville Pike Suite 402 Rockville, Maryland 20852 General Counsel Tennessee Valley Authority ET llH 400 West Summit Hill Drive j

Knoxville, Tennessee 37902 Chairman, Limestone County Commission P.O. Box 188 Athens, Alabama 35611

c

-Distribution Docket' File-NRC & Local PDRs BFN Reading T. Murley F. Miraglia J. Partlow W. Russell S. Varga G. Lainas F. Hebdon M. Sanders J. Williams 4

T. Ross OGC.

i D. Hagan L

G. Hill (2)

Wanda Jones i

C, Grimes A. Thadani

-ACRS (10)

OPA c

OC/LFDCB J. Lieberman, OE 1

S. Dembek, Acting

{

E. Merschoff, RII 1

P, Frederickson, RII C. Patterson, RII 1

4

+

i I

't

..my-