_._
~
3901035470 7
UNIT SHUTDOWNS AMD,POWEJ REDUCTIONS DOCKET NO. 50 - 353 UNIT NAME LINE.;IC2 UNIT 2 DATE APRIL 3, 1990 E
REPORT MONTH MARCH.' 1990 COMPLETED BV PHILADELPHIA ELECTRIC COMPANY O.
M4R?. WECM REPORTS SUPERVISOR D/D N
BUSINESS UNIT LINERICK GENERATING STATION TELEPHONE (215) 327-1200 EXTENSION 3320 g
04 l
l I
l NETHOD OF i LICENSEE ISYSTEMICOMPONENTl CAUSE AND CORRECTIVE ___.____
LC l
TYPElDURATIONl REASON l SHUTTING DOwNl EVENT l CODE I CODE I ACTION TO NO.!
DATE (1)l (HOURS)l (2) l REACTOR (3) l REPORT a I (4) l (5) l PREVENT RECT >RRENCE gg
..... _. - - = - - - - - - - - - - - -.. _ _....... _...
tmO->
I I
I i
i O Ut 4
900322 S
000.0 l
B l 4
l N/A ZZ l ZZZZZZ l LOAD WAS REDUCED 15% TO ACCOWODATE A bJ l
l l CONTROL ROD PATTERN ADJUSTMENT AND WAIN i
l H
l l TURBINE CONTROL VALVE TESTING.
l 1
l l
5 900325 i F l 062.
A l
4 N/A 1 ZZ l ZZZZZZ GENERATOR OFFLINE AND REACTOR POWER l
l l
l l
MAINTAINED AT 20% FOR REPAIR OF EHC OIL l
l l
' l l
l l
l SYSTEu FLUID ACTUATING SUPPLY LINE.
I I
I I
l
?
I I
6 900327 l F i 102.4 l
A Z
l l ZZ l ZZZZZZ l REACTOR WAS SHUTDOwM WHEN THE REACTOR l
l l
l l WATER CHEMISTRY CONDUCT!v!TV INDICATOR 1
l l
l l SPIMED. SUGGESTING A CONDENSER TUBE FAILURE.
l I -----
1 I
l l
8 l 164.4 l
1 l
l l
(1)
(2)
(3)
(4)
F - FORCED REASON WETHOD EXHIBIT G - INSTRUCTIONS S - SCHEDULED A - EGOIPMENT FAILURE (EXPLAIN) 1 - MANUAL FOR PREPARATION OF DATA B - MAINTENANCE CR TEST 2 - MANUAL SCRAM.
ENTRY SHEETS FOR LICENSEE C - REFUELING 3 - AUTOuATIC SCRAM.
EVENT REPORT (LER)
D - REGULATORY RESTRICTION 4 - OTHER (EXPLAIN)
FILE (NOREG-0161)
E - OPERATOR TRAIUING + LICENSE EXAMINATION F - ADMINISTRATIVE (5)
G - OPERATIONAL ERROR (EXPLAIN)
H-OTHER(EXPLAIN)
ERMIBIT I - SAWE SOURCE d CORRECTION MADE TO REFLECT BREAKER TO BREAKER REPORTING FOR SiRITDOWNS.
O e
-