{{#Wiki_filter:o ~ %,r g MARCH 0 2 1982 ' DISTRIBUTION: L PDR DChaney Docket File ORB #4 Rdg OELD NRC PDR DEisenhut AE0D RIngram IE Docket flo. 50-313 GVissing ACRS-10 ,i,,e, O1^ 4/ H0rns tein Gray File ./ N EBlackwood f ,m' i ? m !!r. William Cavanaugh, III Senior Vice President, 2 f.UiR5 1932b-Energy Supply 0-g m y., g _; 7 Arkansas Power & Lig'it Company m /a -{ weu. jQ M P. O. Box 551 Little Rock, Arkansas 72203 g O) i g

Dear !!r. Cavanaugh:

lie have reviewed your submittals related to the Inservice Inspection Progran for Arhnsas !!ucicar One, Unit flo.1 and have detemined we need additional infomation, Enclosure 1. We request the additional infomation within 30 dvs from receipt of this letter. The reporting and/or recordkeeping requirements of this letter affect fewer than ten respondents; therefore, ole clearance is act required under P. L. 96-511. I Sincerely, v.m. a sicant .30.i:i 2. SIOJi48 John F. Stolz, Chief Operating Reactors Branch #4 Division of Licensing

Enclosure:

Request for Additional Infomation cc w/ enclosure: See next page l omee >..QR. D.L,,,,,, 0RB #4,1 L,,, D sunnur > ng/.cb JS 3 82 3/b82 " 8203190513 820302 ~ " ' " ' ' ' ' " ~ " " " " " " " " " " ' " " ~ ' " ~ " " " " " ~ " " PDR ADOCK 05000313 FICIAL RECORD COPY uscro: m - m m l NRC F0F G PDR

P[ [q,, UNITED STATES 4, p, NUCLEAR REGULATORY COMMISSION g

l WASHINGTON, D. C. 20555 Narch 2,1982 Docket No. 50-313 M. William Cavanaugh, III Senior Vice President, Energy Supply Arkansas Power & Light Company P. O. Box 551 Little Rock, Arkansas 72203

Dear Mr. Cavanaugh:

We have reviewed your submittals related to the Inservice Inspection Program for Arkansas Nuclear One, Unit No.1 and have determined we need additional information, Enclosure 1. We request the additional infonnation within 30 days from receipt of this letter. The reporting and/or recordkeeping requirements of this letter affect fewer than ten respondents; therefore, OMB clearance is not required under P. L. 96-511. Sincerely,rf, ~ \\ Jom F. Stolz, Chief erating Reactors Branch #4 Division of Licensing

Enclosure:

Request for Additional Information cc w/ enclosure: See next page i l

~ Arkansas Power & Light Company cc w/ enclosure (s): Mr. : John R. Marshall Manager, Licensing Arkansas Power & Light Company P. O. Box 551 Director, Bureau of Environmental Little Rock, Arkansas 72203 Health Services 4815 West Markham Street Mr. James P. O'Hanlon Little Rock, Arkansas 72201 General Manager Arkansas Nuclear One P. O. Box 608 Russellville, Arkansas 72801 Mr. William Johnson U.S. Nuclear Regulatory Commission P. O. Box 2090 Russellville, Arkansas 72801 Mr. Robert B. Borsum Babcock & Wilcox Nuclear Power Generation Division Suite 220, 7910 Woodmont Avenue Bethesda, Maryland 20814 Mr. Nicholas S. Reynolds Debevoise & Liberman 1200 17th Street, NU Washington, DC 20036 Arkansas Tech University Russellville, Arkansas 72801 Honorable Ermil Grant Acting County Judge of Pope County Pope County Courthouse Russellville, Arkansas 72801 Regional Radiation Representative EPA Region VI 1201 Elm Street Dallas, Texas 75270 Nr. John T. Collins, Regional Administrator U. S. Nuclear Regulatory Commission, Region IV l 611 Ryan Plaza Drive, Suite 1000 l Arlington, Texas 76011 l l

~~ REQUEST FOR ADDITIONAL INFORMATION INSERVICE INSPECTION PROGRAM Arkansas 1 4 1. General Under the change in regulation,10 CFR 50.55a effective November 1, 1979, your ISI program, when finally approved, will cover the last 80 months of your current 10-year inspection interval, i.e., 'fron April 19, 1978 to December 19, 1984. Does this result in any changes you wish to make in your relief requests? Do you require other ISI relief? 2. Extant of Volumetric Examinations (Question 1, Ref. 2)- In this question you were asked whether full volumetric examinations can a be performed in accordance with code requirements for all Class 1 and 2 systems. Your response suggested that the plant has some partially inaccessible welds for which relief requests have not been prepared. For example, the use of Article I-5121 to record limited examination is discussed and the suggestion is made that "a supplemental... surface examination could be performed". Formal relief requests should be submitted on welds for which complete compli-ance with code requirements is not possible. The fraction of the weld which is inaccessible should be estimated as well as the total fraction of inaccessible welds or weld length in a given ' code item. As appropriate, a definite commit-ment should be made to perform any supplemental, alternative examinations. 3. Exemption due to Paragraph IWC-1220 of Section XI (Question 6, Ref. 2) In your response you identified Class 2E systems on your P&lD's as being ~ exempted from examination because of paragraph IWC-1220. The NRC does not accept the " chemistry control" provision of the S-75 addenda as a basis for exempting systems for inspection. You should develop an ISI program for the ECC, RHR, and CHR (containment heat removal) systems that complies with the intent of the.S addenda, in which the " chemistry control" provision has been deleted. A commit- ~ ment to such a program,with any necessary relief requests for reasons other than chemistry control, should be provided in response to this inquiry. 1 .-o, .m m

4 -~. o 4. Item B5.6, Volumetric Examination of Pump Casing Wel_ds, and Others (Ref. 2) Your response to Question 2 indicates "that relief request on this item is to follow at a later date". Possible relief requests are also pending on: (a) Question 6 - pressure testing of Class 2E systems, (b) Question 7 - pressure testing of service water system, and (c) Question 9 - supplementary information (resulting from !4 arch 1,1979 outage) re. HPI and core flood l'ine welds. P. lease provide as much of the missing information as possible. REFEREf1CESi 1. Cavanaugh, APL to Davis, 11RC, #1-107-7, October 19, 1977. ' 2. Williams, APL to Reid, flRC, #1-128-3, December 15, 1978. 3. Williams, APL to Reid, f1RC, #1-019-2, January 10, 1979. + 0 e e 4 8 e 2 -}}