a

.+

1-

~

q s.

c.m y t ne e

DISTRIBUTI0ft:

TERA MFai rtile g

V, c@ cket File 3 flSIC RIngram

~

llRC PDR ORB #4 Rdg KEccleston L PDR DEisenhut 0 ELD Dockets f:os. 50-277 AE0D and 50-270 d'TT:DN"-k'f ',N I E-3 ACRS-10 7-Gray File-2 s

i!r. Edtard r.. Dauer, dr.

'i s

s j

Vice Prcsi ' ;t and General Counsel i

Philadelphia ilectric conpany 4

k: \\

j Col Market $treet

+~

y,7 Philadelphia, Pennsylvania 19101 g,

Daar ! r. Bauer:

4 // -

y The Philadelphia Electric Company letter of Cacerber 21, 1931 reques te l that testino of the stran discharqe systen instrurent volune level suitches be discontinued upon corpletion of the piping rodifications bet'leen the scran discharac volune and the instrarent volure and the relocation of the leval suitch sensinq lines.

These roJirications do contribute nore reliability to the Peach Botton Station scran systcns and in particular increase reliability of the level s'ritches and inprove hydraulic coupling.

Uu do not agree ut th you that level suitch testing tw/ be discontinuel becau';a of the nodifications. Our position is stated in Iten 4.2.0.3 of the C'.fR Scran discharge Systen Safety Evaluation dated Decerher 1, lot.

Iten <1.2.4.3 (Desian Criterion 3) require.! both rn lifications anJ functional testinq of the level switches (usinq uater) after each scran.

T'ierefore, based on Iten 4.2.4.3, we concla to thct functional testing of the level suitches af ter each scran rust continue. You nay request a reuvaluation of our position af ter sufficient operating experience with the rodified systen has been obtained.

Si nce rely,J1c'.m 37 N.C ! J..

\\ [ < q L:,f /

dohn F. Stolz, Chief Operating Reactors Branch i'"

Divisien of Licensino cc:

See nc_xt page 8202100155 820121 PDR ADOCK 05000277 P

PDR

  • See nrevious 318 for concurrence.

omer >

. 9.RB.6,,:D.L.,

0RM2,: DL,,,,,,,C-0,RB,6,; D L,

11Fairtile KEccleston*

Rtol z l

uma

. 3.gygg.(y.

37goygg-.

3g7g7- -.

..gg.

4..

om>

OFFICIAL RECORD COPY usw e-am memwaisoo% umem

~~,

r.

DISTRIBUTION Docket File NRC PDR L PDR TERA Dockets Nos. 50-277 NSIC and 50-273 ORB #4 Rdg DEisenhut 0 ELD AE0D Mr. Edward G. Bauer, Jr.

IE-3 Vice President and General ACRS 10 Counsel MFairtil e Philadelphia Electric Company RIngram 2301 Market Street Gray File Philadelphia, Pennsylvania 19101 KEccleston bear Mr. Bauer:

The Philadelphia Electric Company letter od December 21,19981 requested that testing of the scram discharge system instrument volume level switches be discontinued upon completion of the piping modifications between the scram discharge volume and the instrument volune and the relocation of the level switch sensing lines. ' These modifications do contribute more reliability to the Peach Bttdom Station scram systaas and in particular increase reliability of the level switches and improve hydraulic coupling.

We do not agree with you that level switch testing may be discontinued because of the modifications. Our position is stated in Item 4.2.4.3 of the BilR Scram Discharge System Safety Evaluation dated Docenber 1,1981.

Item 4.2.4.3 (Design Criterion 3) required both the modifications and functional testing of the level switches (using water) after each scram.

Therefore, based on Iten 4.2.4.3, we conclude that functional testing of the level switches after each scram must continue. You may request a reevaluation of our position after sufficient operating experience with the modified systen has been obtained.

Sincerely,

John F. Stolz, Chief Operating Reactors Branch #4 Division of Licensing cc: See next page not as

/NMURB#4:DL ORB #2:'d("

C-0RB#4:DL o r,,c,,

. M..)F.a i r.,7g....c.f..K.Ec..cl es.t.o n

g. lz tile;

..J St.o...jg...

suruu m >

g

).j g

om>