ML20040F402
| ML20040F402 | |
| Person / Time | |
|---|---|
| Site: | La Crosse File:Dairyland Power Cooperative icon.png |
| Issue date: | 02/05/1982 |
| From: | James Keppler NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III) |
| To: | Linder F DAIRYLAND POWER COOPERATIVE |
| References | |
| NUDOCS 8202090160 | |
| Download: ML20040F402 (3) | |
Text
- _ _ _
e' February.5,'1982 N
Docket No. 50-409
\\
R 9
Dairyland Power Cooperative g
M?CElVED y/
p g
ATTN:
--Mr. F. W. Linder h{i " "g 3 1982s General Manager
~QW"* tar.ek 2615 East Avenue - South bf H rn
\\\\
La Crosse, WI 54601
y
,G Gentlemen:
7y(9 We have reviewed your submittal of December 17, 1981, responding to our emergency preparedness implementation appraisal report transmitted to you by letter dated October 29, 1981, from Mr. J. G. Keppler.
Regarding Attachment 1 of your letter '"Significant Appraisal Deficiencies" your response to Items.1, 3, 4, 5, 6,-7, 8 and 10 are acceptable and we will examine these items during a subsequent inspection. We have specific comments on Items 2, and 9 which appear in Attachment 1 of.this letter.
Regarding Attachment 2, " Appraisal Improvement Items" we have a comment on Item 30 which appears in Attachment 2 of this letter. The other responses t.-
to" appraisal improvement items are acceptable and we will examine these items during a subsequent inspection.
Please provide us with a copy of your Emergency Plan, upgraded according to Appendix D attached to our October 29, 1981 letter to you.
Your cooperation with us is appreciated.
Sincerely, Drigin3I Signed by Jar =s G. Ecppler James G. Keppler Regional Administrator
Enclosures:
- 1.
- 2.
cc w/encls:
R. E. Shimshak, Plant Superintendent DMB/ Document Control Desk (RIDS)
Resident Inspector, RIII John J. Duffy, Chief Boiler Inspector 8202090160 820205
~ Stanley York, Chairman hDR ADOCK 05000 Public Service Commission RIII RII
- RIII, RII RI RIII RIII Pahl
/so Ax n
Pap ello ad g
K p.er 2/2/ L
> f/fp R 3. IA
+
ATTACHMENT 1 Deficiency 2.
The minioum shift staffing proposed in your respone is unacceptable because it doec not meet the guidance recommended in NUREG-0654, Table B-1 i.e., you do not provida a SRO-Foreman, a Rad / Chem Tech, nor a Communicator. We understand that you intend to request an exempt. ion from the guidance in Table B-1.
Until the exemption is approved, your minimum shift staffing is unacceptable and inadequate compensatory measures are in place.
Deficiency 9.
The offsite assembly area at Genoa-1 would be unacceptable in adverse wind conditions during an emergency involving a release of radioactivity.
There would be a potential of contaminating evacuees during egress from the evacuation assembly area when evacuees are released to return to their homes.
Please clarify how this problem can be solved.
e
. ATTACHMENT 2 Item 30 The provision'of measuring devices, film badges, or dosimeters to.the-
.U.S. Coast Guard is the responsibility of DPC irrespec_tive of'the source of these devices. Please cover. provision of - these devices in the Agreement Letter executed with the U.S. Coast Guard, Twin Cities District Office, St. Paul,' Minnesota.
t i
4 4