ML20040F284
| ML20040F284 | |
| Person / Time | |
|---|---|
| Site: | Palo Verde |
| Issue date: | 01/28/1982 |
| From: | Van Brunt E ARIZONA PUBLIC SERVICE CO. (FORMERLY ARIZONA NUCLEAR |
| To: | Faulkenberry B NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV) |
| References | |
| 10CFR-050.55E, 10CFR-50.55E, ANPP-20012-GHD, NUDOCS 8202090039 | |
| Download: ML20040F284 (3) | |
Text
.-
-[
Docket Nos. 50-528/529/530 50 55(e)' Report dmM@i&L FFJUanHC 5lmtfrIMICFm @@hTPMJW P. O. BOX 216 6 6 PHOENIX, ARIZON A 85036 January 28, 1982 ANPP-20012-GHD/BSK to A
U. S. Nuclear Regulatory Commission R)
Region V REC 3MD 9
1450 Maria Lane - Suite 210 p
Creekside Oaks Office Park Walnut Creek, California 94596-5368 FEB 8 1982 6 Z Attention:
Mr. B. H. Faulkenberry, Chief dM$,"
W Reactor Construction and Engineering Support Branch
'I
- I l t ys Subj ect:
Interim Report - DER 81-54 A 50.55(e) Potentially Reportable Deficiency Relating to Unit 1 Steam Generator #2 Has h" Visible Linear Indication in Nozzle Outlet Weld, Not Shown By Previous Radiographic and Ultrasonic Tests File: 82-019-026 D 4.33.2
Reference:
Telephone Conversation between J. Eckhardt and G. Duckworth on December 30, 1981
Dear Sir:
The NRC was notified of a potentially reportable deficiency in the referenced telephone conversation. At that time, it was estimated that a determination of reportability would be made within thirty (30) days.
Due to the extensive investigation and evaluation required, an Interim Report is attached.
It is now expected that this information will be finalized by March 24, 1982, at which time a complete report will be submitted.
Very truly yours, CLQ \\
%.LL E. E. Van Brunt, Jr.
APS Vice President Nucleat Projects ANPP Project Director 3, g,,
EEVBJr/GHD:ske Attachment U d :l ((J l - g j y cc: See Attached Page 2 LLu I 6il anem l
C202090039 820128 I
PDR ADOCK 05000528
{
S PDR
,e e'
U.-S. Nuclear Regulatory Commission Attention:
Mr. B. H. Faulkenberry, Chief ANPP-20012-GHD/BSK January 28, 1982 Page.2 cc:
Richard DeYoung, Director Office of Inspection and Enforcement U. S.-Nuclear Regulatory Commission Washington, D. C.
20555 J. A. Roedel D. B. Fasnacht G. C. - Andognini F. W. Hartley J. M. Allen A. C. Rogers B. S. Kaplan W. E. Ide J. Vorees J. A. Brand A. C. Gehr W. J. Stubblefield W. G. Bingham R. L. Patterson R. W. Welcher R. M.. Grant D. R. Hawkinson L. E. Vorderbrueggen R. L. Greenfield Assistant Attorney General Bataan Memorial Building Santa Fe, New Mexico' 87503 Ms. Patricia Lee Hourihan 6413 South 26th Street Phoenix, Arizona 85040 m
(
t
.=
J INTERIM REPORT - DER 81-54 POTENTIAL REPORTABLE DEFICIENCY ARIZONA PUBLIC SERVICE COMPANY (APS)
PVNGS UNIT 1 I.
Potential Problem.
During an internal cleanliness inspection of Steam Generator #2, a linear indication in the nozzle outlet (Bechtel Weld W-001) was discovered by visual inspection. The indication is approxi-mately h" in length and appears to run parallel with the root bead in the root and heat affected zone. Prior to the visual discovery, the following NDE's were completed as satisfactory on the subject weld, e RT Inspected to ASME III, August 13, 1980 e PSE UT Test Per ASME XI, August 20, 1980 o PWHT Completed, September 24, 1980 II.
Approach To and Status Of Proposed Resolution
-Bechtel Construction is currently taking the necessary steps to investigate and correct this indication by alternately perform-ing a light grinding operation followed by a PT inspection until the indication is removed.
III.