ML20040B771

From kanterella
Jump to navigation Jump to search
Monthly Operating Repts for Dec 1981
ML20040B771
Person / Time
Site: Brunswick  
Issue date: 01/06/1982
From: Harrison F
CAROLINA POWER & LIGHT CO.
To:
Shared Package
ML20040B753 List:
References
NUDOCS 8201260399
Download: ML20040B771 (9)


Text

1 APPENDIX B AVERAGE DAILY POWER LEVEL DOCKET NO. 050-9325 UNIT BRUNSWICK UN',T 1 DATE 01/05/82 COMPLETED BY FRANCES HARRISON TELEPHONE 719-457-9521 DECEMBER 81 DAY AVG. DAILY POWER LEVEL DAY AVG. DAILY POWER LEVEL (MWE-NET)

(MWE-NET) 1 624.

17 749.

2 5.

18 742.

3

-11.

19 727.

4 50.

20 737.

5 556.

21 745.

6 652.

22 744.

7 638.

23 741.

8

739, 24 710.

9

743, 25 732.

10 752.

26 742.

11 758.

27 733.

12 751.

28 740.

13 749.

29 708.

14 750.

30 510.

15 743.

31 697.

16 750.

i 1.16 - 8 O$$$lfj4 0 K PDR

1 1

1.

j OPERATING DATA REPORT

}

DOCKET NO. 050-0325 DATE 01/05/82 I

COMPLETED BY FRANCES HARRIS 0N' j

TELEPHONE 919-457-9521 i

)

OPERATING STATUS j

1.

UNIT NAME: BRUNSWICK UNIT 1 I NOTES Il 2.

PEPORTING PERIOD: DECEMBER 81 I

Ii

3. LICENSED THERMAL POWER (MWT): 2436 I

I, 4.

NAMEPLATE RATING (GROSS MWE): 867.0 I

I

5. DESIGN ELECTRICAL RATING (NET MWE): 821.0 I

I' 6.

MAX DEPENDABLE CAPACITY (GROSS MWE): 815.0 I I

I 7.

MAX DEPENDABLE CAPACITY (NET MWE): 790.0 8.

IF CHANGES OCCUR IN CAPACITY RATINGS (ITEMS 3 THRU 7) SINCE LAST REPORT, GIVE REASONS:

}

}

9.

POWER LEVEL TO WHICH RESTRICTED IF ANY (NET MWE): NONE l

10. REASONS FOR RESTRICTION IF ANY:

THIS YR TO CUMUL j

MONTH DATE ATIVE 1

i i

11. HOURS IN REPORTING PERIOD 744.0 8760.0 42001.0 1
12. NUMBER OF HOURS REACTOR WAS CRITICAL 700.8 4463.2 28265.3 j
13. REACTOR RESERVE SHUTDOWN HOURS 0.0 0.0 1647.1 j
14. HOURS GENERATOR ON LINE 685.6 4157.8 26539.6 1
15. UNIT RESERVE SHUTDOWN HOURS 0.0 0.0 0.0
16. GROSS THERMAL ENERGY GENERATED (MWH) 1556278.8 8294071.7 54417804.6
17. GROSS ELECTRICAL ENERGY GENERATED (MWH) 495623.0 2675611.0 18001205.0
18. NET ELECTRICIAL ENERGY CENERATED (MWH) 480149.0 2556057.0 17303491.0
19. UNIT SERVICE FACTOR 92.2 47.5 63.2 2
20. UNIT AVAILABILITY FACTOR 92.2 47.5 63.2 l
21. UNIT CAPACITY FACTOR (USING MDC NET) 81.7 36.9 52.1
22. UNIT CAPACITY FACTOR (USING DER NET) 78.6 35.5 50.2 1
23. UNIT FORCED OUTAGE RATE 7.8 37.6 22.0
24. SHUTDOWNS SCHEDLLED OVER NEXT 6 MONTHS (TYPE, DATE, AND DURATION OF EACH):

1 c5. IF SHUTDOWN AT END OF REPORT PERIOD, ESTIMATED DATE OF START UP:

0/ O/ 0

26. UNITS IN TEST STATUS (PRIOR TO COMMERICIAL OPERATION): FORCAST ACHEIVED INITIAL CRITICALITY l

INITIAL ELECTRICITY COMMERICIAL OPERATION l

1.16 - 9 1

I

L

.___._____,I

1 APPENDIX B AVERAGE DAILY POWER LEVEL DOCKET NO. 050-0324 UNIT BRUNSWICK UNIT 2 DATE 01/06/82 COMPLETED BY FRANCES HARRISO TELEPHONE 919-457-9521 DECEMBER 81 DAY AVG. DAILY POWER LEVEL DAY AVG. DAILY POWER LEVEL (MWE-NET)

(MWE-NET) 1 606.

17 761.

2 607.

18 339.

3 606.

19

-12.

4 607.

20

-12.

5 603.

21 412.

6 605.

22 663.

7 602.

23 658.

8 600.

24 673.

9 604.

25 669.

10 619.

26 382.

11 691.

27 521.

12 627.

28 680.

13 653.

29 673.

I 14 745.

30 674.

15 759.

31 680.

i l

16 759.

i 1

1 1.16 - 8 i

OPERATING DATA REPORT DOCKET NO. 050-0324 l

DATE 01/06/82 COMPLETED BY FRANCES HARRISON 1

TELEPHONE 919-457-9521 i

OPERATING STATUS 1.

UNIT NAME: BRUNSWICK UNIT 2 I NOTES I

2. REPORTING PERIOD: DECEMBER 81 I

I j

3. LICEtBED THERMAL POWER (MWT): 2436 I

I i

4.

NAMEPLATE RATING (GROSS MWE): 867.0 I

I i

5. DESIGN ELECTRICAL RATING (NET MWE): 821.0 I

I i

6.

MAX DEPENDABLE CAPACITY (GROSS NWE): 815.0 I I

7.

MAX DEPENDABLE CAPACITY (NET MWID : 790.0 8.

IF CHANGES OCCUR IN CAPACITY RA"INGS (ITEMS 3 THRU 7) SINCE LAST REPORT, GIVE REASONS:

9. POWER LEVEL TO WHICH RESTRICTED IF ANY (NET MWE): NONE
10. REASONS FOR RESTRICTION IF ANY:

i i

THIS YR TO CUMUL j

MONTH DATE ATIVE

11. HOURS IN REPORTING PERIOD 744.0 8760.0 54025.0
12. NUMBER OF HOURS REACTOR WAS CRITICAL 701.0 6144.6 35166.9
13. REACTOR RESERVE SHUTDOWN HOURS 0.0 0.0 0.0 i
14. HOURS GENERATOR ON LINE 680.1 5805.0 32769.3
15. UNIT RESERVE SHUTDOWN HOURS 0.0 0.0 0.0
16. GROSS THERMAL ENERGY GENERATED (MWH) 1375144.5 10386156.7 59997537.6
17. GROSS ELECTRICAL ENERGY GENERATED (MWH) 448079.0 3429491.0 19993937.0 j
18. NET ELECTRICIAL ENERGY GENERATED (MWH) 433241.0 3283984.0 19189413.0 l
19. UNIT SERVICE FACTOR 91.4 66.3 60.7
20. UNIT AVAILABILITY FACTOR 91.4 66.3 60.7
21. UNIT CAPACITY FACTOR (USING MDC NET) 73.7 47.5 45.0
22. UNIT CAPACITY FACTOR (USING DER NET) 70.9 45.7 43.3
23. UNIT FORCED OUTAGE RATE 8.2 30.9 17.1
24. SHUTDOWNS SCHEDULED OVER NEXT 6 MONTHS (TYPE, DATE, AND DURATION OF EACH):

.i i

25. IF SHUTDOWN AT END OF REPORT PERIOD, ESTIMATED DATE OF START UP:

0/ O/ 0

]

26. UNITS IN TEST STATUS (PRIOR TO COMMERICIAL OPERATION): FORCAST ACHEIVED

{

INITIAL CRITICALITY

]

i INITIAL ELECTRICITY COMMERICIAL OPERATION 14 16 - 9

-.._.-..~_.-_,,_.~,_..,-___,-,-,.m.,...,-,.,..r1

n n

n 050-0325 DOCKET NO.

UNIT SilUTDOWNS AND POWER REDUCTIONS UNIT N AME Brunswick 1 DATE Januarv 1982 COMPLETED BY Frances Harricon i

REPORT MONT11 December 1981 TELEPif0NE ( 914M 57-9521 3

~.

c 3?

'h

..' ll 9, Licensee

,E-r, Cause & Corrective No.

Date c.

=

i; E E l~i Event 3 "9 Q

Action to S

js 3,3 Report :

tE 0 Prevent Recurrence u

d.81-049 81 12 02 F

58.4 B

1 NA

.lb\\

Turbine Turbine generator separated from grid-pack leaking on IB21-F005.

Repacked valve E

I 2

3 4

F: Forced Reason:

Method:

Exhibit G. Instructions S: Scheduled A 1qmpment Failure (Explain) 1 -Manual for Prepwation of Data n Maintenance of Test 2 Manual Seram.

Entry Sheets for Liecusee C Refucting 3 Automatic Scram.

Esent Report (LER) File (NUREG.

D. Regulatory Restriction 4 Continuations 0161)

E Operator Training & License Examination 5-Load Reductions 5

F Administrative 6-Other Exhibit I Same Source G-Operational Errur (Explain)

(9/77)

Il-Other (Esplain)

APPENDIX i

Docket No:

050-325 Unit:

Brunswick No. 1 Date:

December 1981 Completed By:

Frances Harrison OPERATIONS

SUMMARY

BRUNSWICK UNIT NO. 1 4

Brunswick Unit No. 1 operated at 92.2% availability factor for the month of i

December with an 81.7% capacity factor.

There was one "off-line" outage.

It is detailed in Appendix D, the unit shutdowns and power reduction log.

l There are 476 BWR and 160 PWR spent fuel bundles in the Brunswick Unit No. 1 fuel pool.

i 1

i 1

I

b b

050-0325 DOCKETNO.

UNIT SilDTDOWNS AND POWER REDUCTIONS UNIT N AME Brunswick 2 DATE Awa r" lor' COMPLETED F.Y Frances Harricon REPORT MONTil Decenber 1981 TELEPllONE (41 M57 os?!

E E

jg 3

4 ;! '.i Licensee 3 r,

$"o Cause & Corrective

[3 o.

Action to No.

Date r-

2 i

EEJ Event n7 S

j$

}d Report :

iN0 U

Prevent Recurrence d.81-047 81 1,2 18 F

57.2 A

3 NA IE INSTRU Faulty high steam flow switch caused Group 1 isolation.

Flow switches were checked. Analog mod will give Operations indication bs to when steam line flow functions have reset and also decrease the deadband.

I 2

3 4

F: Forced Reason:

Method:

Exhibit G. Instructions S: Scheduled A 1 quipment Failure (Explain) 1 Manual for Preparation of Daia 11 Maintenance of Test 2 Manual Seram.

Entry Sheets for Licensee C Refucting

3. Automatic Scram.

Esent Report (LER)Fde(NUREG-D Regulatory Restriction 4 Continuations 0161)

E Operator Training & License Examination 5-Load Reductions i

5 l

F. Administrative 6-Other G-Operational Error (Explain)

Exhibit I-Same Source c/77)

Il-Other (Explain)

O O

O DOCKET NO. 050-0325 UNIT SliUTDOWNS AND POWER REDUCTIONS UNIT N AME un m c-e i e t-DATE.Tanuarv 1982 rrnnce c ",vrfcnn COMPLETED BY REPORT MONTil DeceMer 1981 TELEPl!ONE (919)457-9521 J,

E 3

jg "h

4 j '.i Licensee

[-r, je.

Cause & Corrective No.

Date c

iE i

E E c'$

Event

'?

c.3 Action to S

js 5

3e d Report :

80

$U Prevent Recurrence u

6 81-051 81 12 26 F

6.7 A

1 NA CH Instru Removed generator f rom grid to repair leak on east MSR drain tank manway.

Casket on east MSR tank blew out.

Replaced manway gasket.

I 2

3 4

F: Forced Reason:

Method:

Exhibit G-Instructions S: Scheduled A l'quipment Failure (Esplain) 1 Manual for Preparation of Data B-Maintenance of Test 2 Manual Scrarn.

Entr> Sheets for Licensee C-Refucting 3 Automatic Scram.

Event Report (LER) File (NUREG-D Regulatory Restriction 4 Continuations 0161i E-Operator Training & License Examination 5-Load Reductions S

F-Administrative 6-Other Exhibit I-Same Source G-Operational Error (Explain) en/77) li-Other (Explain)

APPENDIX Docket No:

050-324 Unit:

Brunswick No. 2 Date:

December 1981 Completed By:

Francc3 Ilarrison OPERATIONS

SUMMARY

BRUNSWICK UNIT NO. 2 Brunswick Unit No. 2 operated at a 91.4% availability factor for the month of December with 73.7% capacity factor. There were two off-line outages this month. They are detailed in Appendix D, the unit shutdowns and power reduction log.

1 There are 264 BWR and 144 PWR spent fuel bundles in the Brunswick Unit No. 2 fuel pool, i

l i

...