Amends 78,74 & 47 to Licenses DPR-33,DPR-52 & DPR-68, Respectively,Adding Operability & Surveillance Requirements on Fire Doors & Dampers & Deleting Conditions Re Mods & Actions That Have Been Completed
ML20039A489
Person / Time
Site: Browns Ferry  
(DPR-33-A-074, DPR-33-A-078, DPR-33-A-74, DPR-33-A-78, DPR-52-A-74, DPR-68-A-047, DPR-68-A-47)
Issue date: 11/24/1981
From: Ippolito T
Office of Nuclear Reactor Regulation
To:
Shared Package
ML20039A490 List:
References
PDR-33-A-78, NUDOCS 8112170697
Download: ML20039A489 (12)


Text

.

b

[jf UNITED STATES

, ^,

NUCLEAR REGULATORY COMMISSION

{

j

e WACHING TON, D. C. 20555

.,,,e TENNESSEE VALLEY AUTHORITY DOCKET NO. 50-259 BROWNS FERRY NUCLEAR PLANT, UNIT NO. 1 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 78 License No. DPR-33

.l.

The Nuclear Regulatory Commission (the Commission) has found that:

The application for amendments by Tennessee Valley Authority (the A.

licensee) dated March 4,1981, as supplemented by letter dated April 29,1981, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.

There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health ard safety of the public, and (ii) that such activities will be conducted in cupliance with the Commission's regulations; D.

The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.

2.

Accordingly, Facility License No. DPR-33 is hereby amended by: (1) deleting paragraph 2.D. (1) and 2.D. (2), (2) renumbering paragrapn 2.D. (3) to be paragraph 2.C.(12) and (3) changing paragraph 2.C(2) to read as follows:

(2) Technical Specifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No. 78, are hereby incorporated in the license.

The licensee shall operate the facility in accordance with the Technical Specifications.

i 8112170697 811124 PDR ADOCK 05000259 P

PDR l

2 3.

This license amendment is effective as of the date of its issuance.

FOR THE NUCLEAR REGULATORY COMMISSION f

q:. - 6 0

1 Thomas

. Ippolito, Chief Operating Reactors Branch 12 Division of Licensing

Attachment:

Changes to the. Technical Specifications

. Da'te of -Issuance: November 24, 1981 I

1

+

i P

1

+

7 i.

i l

4 4

1 4

. -.. ~

m r.

_,.,_4

ATTACHMENT TO LICENSE AMENDMENT NO. 78 FACILITY OPERATING LICENSE N0. DPR-33 DOCKET N0. 50-259

- Revise Appendix A as follows:

1.

Replace the following page with the identically numbered page:

322 2.

Marginal lines.on this page indicate the area being revised. The 4

overleaf page is not being revised and should be retained.

I 4

1 a

i i

J-4 o

i.,... -,..

a LI!!ITING CONDITION' FOR OTERATION SURVEILLANCE REQUIREMENTS 3.11 F!RE PROTECTION SYSTEMS 4.11 FIRE PROTECTION SYSTEMS E.

All fire barrier penetrations, E.

Each required fire barrier includinn cable penetration penetration shall be verified barriers, fire doors and to be functional at least once fire dampers, in fire zone per 18 months by a visual inspect-boundaries protecting safety ion, and prior to restoring a related areas shall be funct-fire barrier to functional status ional at all times. With one following repairs or maintenance or more of the required fire by performance of a visual in-barrier penetrations non-spection of the affected fire functional within one hour es-barrier penetration, tablish a continuoos fire watch on at least one side of the affected penetration or verify the OPERABILITY of fire detect-ors on at least one side of the non-functional fire barrier and establish an hourly fire watch patrol until the work is com-pleted and the barrier is re-stored to functional status.

F.

The minimum in-plant fire protection organization and duties shall be as depicted in Figure 6.3-1.

322 Amendment No. g 78

E[4

'k

+

UNITED STATES g

NUCLEAR REGULATORY COMMISSION 5

.E i

WASHINGTON, D. C. 20555 I

%..... /

TENNESSEE VALLEY AUTHORITY 1

DOCKET NO. 50-260 BROWNS FERRY NUCLEAR PLANT. UNIT NO. 2 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No.

74 License No. DPR-52 1.

The Nuclear Regulatory Commission (the Commission) has found that:

The application for amendments by Tennessee Valley Authority (the A.

licensee) dated March 4, 1981, as supplemented by letter dated April 29,1981, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in confomity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.

There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations; D.

The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.

2.

Accordingly, Facility License No. DPR-52 is hereby amended by:

paragraph 2.0. (1) and 2.D. (2), (2) renumbering paragraph 2.D. (3) to(1) deleting be paragraph 2.C.(12) and (3) changing paragraph 2.C(2) to read as follows:

(2) Technical Specifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No. 74, are hereby incorporated in the license.

The licensee shall operate the facility in accordance with the Technical Specifications.

i 2

3. - This license amendment is effective as of the date of its issuance.

FOR THE NUCLEAR REGULATORY C0W.ISSI0li

/'

h. %,97 A t d o Thomasf(. Ippolito, Chief -

Operating Reacters Branch #2 Division of Licensing

Attachment:

Changes to the Technical Specifications Date of Issuance:

November 24, 1981 J

1 4

,,_7

I-ATTACHMENT TO LICENSE AMENDMENT NO.74 FACILITY OPERATING LICENSE NO. DPR-52 DOCKET NO. 50-260 Revise Appendix A as follows:

1.

Replace the following page with the. identically numbered page:

322 2.~ Marginal. lines on this page indicate.the area being revised.

The Overleaf page is not being revised and should be retained.

d i

)

s O

k

.m.-..,.m

LIMITING CONDITIONS FOR OPERATION SURVEILLANCE REr)UIREMEhiS 3.11 FIRE PROTECTION SYSTEMS 4.11 FIRE PROTECTICN SYSTEMS f

4 I

E.

All fire barrier penetrations.

E.

Each required fire barrier including cable penetration penetration shall be verified barriers, fire doors and to be functional at least once fire dampers, in fire zone per 18 months by a visual inspect-boundaries protecting safety ion, and prior to restoring a related areas shall be funct-fire barrier to functional status ional at all times. With one following repairs or maintenance or more of the required fire by performance of a visual in-barrier penetrations non-spection of the affected fire functional within one hour es-barrier penetration.

tablish a continuons fire vacch on at least one side of the affected penetration or verify the OPERABILITY of fire detect-ors on at least one side of the non-functional fire barrier and establish an hourly fire watch patrol until the work is com-pleted and the barrier is re-stored to functional status.

F.

The minimum in-plant fire protection organization and duties shall be as depicted in Figure 6.3-1.

4 322 Amendment No., fry 74

8 a uru g,

4 UNITED STATES -

(

g NUCLEAR REGULATORY COMMISSION

E WASHINGTON, D. C. 205S5 t,i e

%...../

TENNESSEE VALLEY AUTHORITY DOCKET N0. 50-296 BROWNS FERRY NUCLEAR PLANT, UNIT N0. 3 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 47 License No. DPR-68 1.

The Nuclear Regulatory Commission (the Conmission) has found that:

A.

The application for amendments by Tennessee Valley Authority (the licensee) dated March 4,1981, as supplemented by letter dated April 29,1981, complies with the standards and requirerents of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's rules and regulations set forth in 10 CFR Chapter I; 8.

The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.

There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations; D.

The issuance of this arendnent will not be inimical to the common de.fense and security or to the health and safety of the public; and E.

The issuance of this anendment is in accordance with 10 CFR Part 51 of the Conmission's regulations and all applicable requirements have been satisfied.

2.

Accordingly, the lice.nse is amended by changes to the Technical Spec-ifications as indicated in the attachment to this license amendment and paragraph 2.C(2) of Facility License No. DPR-68 is hereby amended to read as follows:

(2) Technical Specifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No. 47, are bereby incorporated in the license. The licensee shall operate the facility in accordance with the Technical Specifications.

2 3.

This license amencment is effective as of the date of its issuance.

FOR THE NUCLEAR REGULATORY COMMISSION Thoma' ppolito, Chief Operating Reactors Branch #2 Division of Licensing

Attachment:

Changes to the Technical i

Specifications Date of Issuance: Novebmer 24, 1981

.i 1

l 0

4 4

5 A

O i

ATTACHMENT TO LICENSE AMENDMENT NO.47 FACILITY 0PERATING LICENSE N0. DPR-68 DOCKET N0. 50-296 Revise Appendix A as follows:

1.

Remove the following page and replace with the identically numbered page:

354 2.

Marginal lines on the above page indicate revised area.

4 t

I

+

l 1

LIMITING CONDITIONS FOR OPERATION SURVEILLANCE REQUIREMENTS v

3.11 FIRE PROTECTION SYSTEMS 4.11 FIRE PROTECTION SYSTEMS E.

All fire barrier penetrations, E.

Each required fire barrier including cable penetration penetration shall be verified barriers, fire doors and to be functional at least once fire dampers, in fira zone per 18 months by a visual inspect-boundaries protecting safety ion, and prior to restoring a related areas shall be funct-fire barrier to functional ctatus ional at all times. With one following repairs or maintenance or more -f the required fire by performance of a visual in-barrier penetrations non-spection of the affected fire functional within one hour es-barriee penetration.

tablish a continuons fire watch on at least one side of the affected penetration or verify the OPERABILITY of fire detect-ors on at least one side of the non-functional fire barrier and establish an hourly fire watch patrol until the work is com-pleted and the barrier is re-stored to functional status.

F.

The minimum in-plant fire protection organization and duties shall be as depicted in Figure 6.3-1.

l l

354 i

l Amendment No.,)sP 47