ML20038C674

From kanterella
Jump to navigation Jump to search
Part 21 Rept Re Weld Fractures Possibly Attributable to Modified Installation Procedure for Mounting of Battery Rack.Encl Notices Have Been Sent to Facilities Receiving Similar Frames for L Size Cell Racks
ML20038C674
Person / Time
Site: Palisades 
Issue date: 12/03/1981
From: Davis T
INDUSTRIAL BATTERIES & CHARGES
To: Ebneter S
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
References
REF-PT21-81-534-000 PT21-81-534, PT21-81-534-000, QA-3026, NUDOCS 8112140022
Download: ML20038C674 (8)


Text

$d'd W DO BAT'TERIES DIVIslON OMA)

Industrial Batteries and Chargers 3043 WALTON RO AD, PLYMOUTH MEETING. PEN NSYLVANI A 19462 "ELEPHONE: 215-828-9000. TELETYPE: 510-660-8436 December 3, 1981

)

L t..

Office of Inspection & Enforcement k

g i g jg@j'.>

Region I

,,pqn U. S. Nuclear Regulatory Commission

{

' ' icoccH 631 Park Avenue f

King of Prussia, PA 19406 h-YQYy \\

Attn:

Mr. Stewart Ebneter Consu M ower Co.

Palisades Plant Bechtel Job 12447-057 10CFR21 Report QA-2991 (11/13/81)

Gentlemen:

C8:D Batteries has received and evaluated sectioned frame welds noted in the reference.

C&D is not able to determine a visual difference of those from the Palisades site and those welds on the similar frames involved in the Wyle Lab tests of 11/16/76.

Further, it is obvious the modified installation procedure was contributory.

However, to preclude any subsequent situation, C&D has determined those sites have received similar frames for racks of "L" size cells.

The attached notices have been sent to those indicated.

With this report, we consider our obligations under 10CFR21 to have been fulfilled. We will keep you advised of any adverse con-ditions reported in response to the attached notices, Very truly yours,

/. l. / w T. P. Davis, P. E.

Director Quality Assurance TI'D/h' cc:

.f.;.G. Koppler, Region III NRC

('

,J.7 1. Dotson, Bechtel Power Corp.

<{

UI Gi I

co.___

8112140022 811203 i

an! Eltra company PDR ADOCK 05000255 s

PDR u- - -

t EE BATTERIES DIVISION Ds0

~

Industrial Batteries and Chargers 3043 WALTON ROAD. PLYMOUTH MEETING. PENNSYLVANIA 19462 TELETvPf; 510-660-0436 TELE 8MONE: 215-828-9000 December 2, 1981 Re: Customer P. O. F8856-E-119-BC C&D Invoice # 7-35540; 7-35545 Battery Model - If-25; If-25 Rack Model -

RD-937; RD-937 Bechtel Power Corp.

P. O. Box 3965 San Francisco, CA 94119 Attn: Project Engineer Job No. 8856

Dear Sir:

This communication is to advise you of a possible condition associated with a specific battery rack as supplied by CLD Batteries. The circum-stances causing us to call your attention to this matter involve a rack of similar design recently in the process of installation at a new nuclear generating plant. However, in this particular case, the installers chose to relocate the mounting holes for bolting the rack to the floor, and in some cases used metal shims only on one side of the anchor bolts to level the frames of the rack.

This procedure introduced forces to the welds un-common to normal installation procedures. The result of this modified technique was to cause fractures in several welds, thereby reducing the structural integrity of the battery rack.

Since we cannot be certain that the weld fractures are directly at-tributable to the modified mounting of this particular rack or to deficient welds, we recommend that you inspect your rack (s) frame members in the specific areas described on the attached drawing.

Please advise us of any deficiencies which you may find so that we may take immediate corrective action.

We wish to thank you in advance for your cooperation in this matter, and apologize for any inconveniences which we may have caused you.

Please contact the writer by letter following your inspection or, if you require immediate assistance, call us at telephone number (215) 828-9000 extension 345 or Mr. David Emery on extension 321.

Very truly yours, T. P. Davis, P. E.

Director Quality Assurance TPD/h Eltra an company

EE BATTERIES DIVISION Omo industrial Batteries and Chargers

~ ~ * "

3043 WALToN RO AD. PLYMOUTH MEETING. PENNSYLVANI A 19462 TELEP*ONE : 2tl.02 8 9000

  • TELETvPE* S10 880.e436 December 2, 1981 Re: Customer P.O. #78K4-823476 C&D Invoice #8-64806 Battery Model 33 Rack Model - RD-659 Tennessee Valley Authority Knoxville Office Complex Knoxville, TN 37902 Attn: Chief, Quality Engineering Branch

Dear Sir:

This communication is to advise you of a possible condition associated with a specific battery rack as supplied by C&D Batteries. The circum-stances causing us to call your attention to this matter involve a rack of similar design recently in the process of installation at a new nuclear generating plant.

However, in this particular case, the installers chose to relocate the mounting holes for bolting the rack to the floor, and in some cases used metal shims only on one side of the anchor bolts to level the frames of the rack.

This procedure introduced forces to the welds un-common to normal installation procedures. The result of this modified technique was to cause fractures in several welds, thereby reducing the structural integrity of the battery rack.

Since we cannot be certain that the weld fractures are directly at-tributable to the modified mounting of this particular rack or to deficient welds, we recommend that you inspect your rack (s) frame members in the specific areas described on the attached drawing.

Please advise us of any deficiencies which you may find so that we may take immediate corrective action.

We wish to thank you in advance for your cooperation in this matter, and apologize for any inconveniences which we may have caused you.

Please contact the writer by letter following your inspection or, if you require immediate assistance, call us at telephone number (215) 828-9000 extension 345 or Mr. David Emery on extension 321.

Very truly yours, T. P. Davis, P. E.

Director Quality Assurance TIV/h Eltra an company

CD BATTERIES DIVISION Osm)

Industr:el Batteries and Chargers

~*"

3043 WALToN ROAD. PLYWouTH MEETING. PENNSYLVANIA 19462 TELEPHONE-215 828 0000 TELETVPE' $10-660 8436 December 2, 1981 Re: Customer P.O. FA-66842-S C&D Invoice #9-79941 Battery Model - If-21 Rack Model - RD-903 Wisconsin Electric Power Co.

P. O. Box 2046 Milwaukee, Wisconsin 53201 Attn: R. E. Hei den Engineer, Quality Assurance

Dear Sir:

This communication is to advise you of a possible condition associated with a specific battery rack as supplied by C&D Batteries. The circum-stances causing us to call your attention to this matter involve a rack of similar design recently in the process of installation at a new nuclear generating plant. However, in this particular case, the installers chose to relocate the mounting holes for bolting the rack to the floor, and in some cases used metal shims only on one side of the anchor bolts to level the frames of the rack. This procedure introduced forces to the welds un-common to normal installation procedures. The result of this modified technique was to cause fractures in several welds, thereby reducing the structural integrity of the battery rack.

Since we cannot be certain that the weld fractures are directly at-tributable to the modified mounting of this particular rack or to deficient welds, we recommend that you inspect your rack (s) frame members in the specific arcas described on the attached drawing.

Please advise us of any deficiencies which you may find so that we may take immediate corrective action.

We wish to thank you in advance for your cooperation in this matter, and apologize for any inconveniences which we may have caused you.

Please contact the writer by letter following your inspection or, if you require immediate assistance, call us at telephone number (215) 828-9000 extension 345 or Mr. David Emery on extension 321.

Very truly yours, T. P. Davis, P. E.

Director Quality Assurance TPD/h Eltra cn comp.ny

EE BATTERIES DIVISION OmM Industrial Batteries and Chargers

~~

3043 WALToN ROAD. PLYWouTH MEETING, PE NNSYLVANI A 19462 TELEPMONE; 2t$ 820 9000 TELETvPE: 5t0 660 8436 December 2, 1981 Re: Customer P.O. /tNY-422545 C&D Invoice #7-71893 Battery Model - II-25 Rack Model - RD-938 Florida Power & Light Co.

Ebasco Services Inc., Agent Two World Trade Center New York, N.Y.

10048 Attn: Chief Electrical Engineer St. Lucie F2 Project

Dear Sir:

This communication is to advise you of a possible condition associated with a specific battery rack as supplied by CLD Batteries. The circum-stances causing us to call your attention to this matter involve a rack of similar design recently in the process of installation at a new nuclear generating plant.

However, in this particular case, the installers chose to relocate the mounting holes for bolting the rack to the floor, and in some cases used metal shims only on one side of the anchor bolts to level the frames of the rack.

This procedure introduced forces to the welds un-common to normal installation procedures. The result of this modified technique was to cause fractures in several welds, thereby reducing the structural integrity of the battery rack.

Since we cannot be certain that the weld fractures are directly at-tributable to the modified mounting of this particular rack or to deficient welds, we recommend that you inspect your rack (s) frame members in the specific areas described on the attached drawing.

Please advise us of any deficiencies which you may find so that we may take immediate corrective action.

We wish to thank you in advance for your cooperation in this matter, and apologize for any inconveniences which we may have caused you.

Please contact the writer by letter following your inspection or, if you require immediate assistance, call us at telephone number (215) 828-9000 extension 345 or Mr. David Emery on extension 321.

Very truly yours, T. P. Davis,

P. E.

Director Quality Assurance TPD/h Eltra in compsny

a EE: ATTERIES DIVISION Omo

~""

industrial Batteries and Chargers 3043 WALToN RoAO. PLYMOUTH MEETING, PENNSYLVANIA 19462 TELEYvPE* 610-660 8436 Y ELE PMONE : 215-828-0000 December 2, 1981 Re: Customer P.O. #24043 C&D Invoice F9-86526 Battery Model - 1f-21 Rack Model - RD-903 Niagara Mohawk Power Corp.

300 Erie Blvd. West Syracuse, N.Y.

13202 Attn:

R. R. Consaul

Dear Sir:

This communication is to advise you of a possible condition associated with a specific battery rack as supplied by C&D Batteries. The circum-stances causing us to call your attention to this matter involve a rack of similar design recently in the process of installation at a new nuclear generating plant.

However, in this particular case, the installers chose to relocate the mounting holes for bolting the rack to the floor, and in some cases used metal shims only on ane side of the anchor bolts to level the frames of the rack.

This procedure introduced forces to the welds un-common to normal installation procedures. The result of this modified technique was to cause fractures in several welds, thereby reducing the structural integrity of the battery rack.

Since we cannot be certain that the weld fractures are directly at-tributable to the modified mounting of this particular rack or to deficient welds, we recommend that you inspect your rack (s) frame members in the specific areas described on the attached drawing.

Please advise us of any deficiencies which you may find so that we may take immediate corrective action.

We wish to thank you in advance for your cooperation in this matter.

l and apologize for any inconveniences which we may have caused you.

Please contact the writer by letter following your inspection or, if you require immediate assistance, call us at telephone number (215) 828-9000 extension 345 or Mr. David Emery on extension 321.

Very truly yours, T. P. Davis, P. E.

Director Quality Assurance TPD/h Eltra Cn co,ng.ny

EE BATTERIES DIVISION ~

Omo

-~'"

industrial Batteries and Charger 4 3043 WALTON ROAD. PLYMOUTH MEETING. PENNSYLVANIA 19462 TELE pMONE ; 215 828-9000. TELETvPE-5'0 68 k 8 4 36 December 2, 1981

]

C s

,m Re: Custo P.O..FC-15183

'y Contract ' K-2988

- C&D Ihvoice (8-53404

~ Bat tery Model - If-17,,

~

Rack. Model - C-955 Baldwin Associates P. O. Box 306 Clinton, ILL 61727 Attn:

Mgr. Quality Control

Dear Sir:

This communication is to advise you of A. possible condition associated with a specific battery rack as supplied by C&D Batteries. The circum,

stances causing us to call your attention to this matter involve a rack of similar design recently in the process of indtallation at a new nuclear generating plant.

However, in this particular case, the' installers chose to relocate the mounting holes for bolting the rack to the floor, and in some cases used metal shims only on one side of the anchor bolts to level the frames of the rack.

This procedure introduced forces to the welds un-common to normal installation procedures.

The result, of this modified technique was to cause fractures in several welds, tboreby reducing the structural integrity of the battery rack.

~

Since we cannot be certain that the weld fractures are directly at-tributable to the modified mounting of this particular rrck or to deficient l

welds, we recommend that you inspect your rack (s) frame' members in the l

specific areas described on the attached drawing.

Please advise us of any deficiencies which you may find so that we may take immediate corrective action.

We wish to thank you in advance for your cooperation in this matter, and apologize for any inconveniences which we may base, caused you.

l Please contact the writer by letter following your inspection or, if l

you require immediate assistance, call us at telephone number (215) 828-9000 i

extension 345 or Mr. David Emery on extension 321.

Very truly yours, 1

l T. P. Davis, P. E.

l Director Quality Assurance j

TPD/h l

1 Eltra cn cornpany

m i

A k

-s

~..

' VDEBATTERIES DIVISION Osw0 Industrial Batteries and Chargers

~ ~ ' "

' +

3043 WALToN ROAD. PLvuouTH ug TING. PENNSYLVANIA 19462 T ELEpwoNE : 215-828 9000 TELETvPE. 510-660 8436 December 2, 1981

(

Re: Customer P.O. #9645-E-019.1 s

C&D Invoice #7-30543, 4 7-30547, 8 Battery Model - If-29 Rack Model - RD-659 Bechtel Power Corp.

P. O. Box 607 Gaithersburg, MD 20760 Attn:

Project Engineer Job No. 9645

Dear Sir:

This comunication is to advise you of a possible condition associated with a specific battery rack as supplied by CLD Batteries. The circum-stance 3 causing us to call your attention to this matter involve a rack of similar design recently in the process of installation at a new nuclear gene rating plant. However, in this particular case, the installers chose to relocate the mounting holes for bolting the rack to the floor, and in some :ases used netal shims only on one side of the anchor bolts to level the frames of the r this procedure introduced forces to the welds un-common to normal !

cion procedures. The result of this modified technique was to ca

.e fractures in several welds, thereby reducing the structural integrity of the battery rack.

Since we cannot be certain that the weld fractures are directly at-tributable to the modified mounting of this particular rack or to deficient welds, we recommend that you inspect your rack (s) frame members in the specific areas described on the attached drawing.

Please advise us of any deficiencies which you may find so that we may take immediate corrective action.

We wish to thank you in advance for your cooperation in this matter, and apologize for any inconveniences which we may have caused you.

Please contact the writer by letter following your inspection or, if you require immediate assistance, call us at telephone number (215) 828-9000 extension 345 or Mr. David Emery on extension 321.

Very truly yours, T. P. Davis, P. E.

Director Quality Assurance TPD/h Eltra cn company

.