Text
{{#Wiki_filter:, December 4,1981 Docket No. 50-213 LS05 12-010 N Mr. W. G. Counsil, Vice President \\ fff 9 Nuclear Engineering and Operations \\ Connecticut Yankee Atomic Power Company T Post Office Box 270 p. DEC8 yggN ' p 1 Hartford, Connecticut 06101 v.3, % ~ E8aD.'
Dear Mr. Counsil:
M J/ SUBJECT.: HADDAM NECK - SEP TOPICS XV-8 AND XV-12
- [L REQUEST FOR ADDITIONAL INFORMATION We have reviewed the topic assessments on the above topics that you submitted on September 30,19G1, and we find that additional informa-tion is needed to complete our safety evaluation.
Please provide the requested information within 30 days of receipt of this letter. The reporting and/or recordkeeping requirements contained in this letter affect fewer than ten respondents; therefore, 051B clearance is not required under P.L. 96-511. Sincerely, Dennis M. Crutchfield, Chief Operating Reactors Branch No. 5 Division of Licensing
Enclosure:
As stated l cc w/ enclosure: See next page j.-(t'lpe[S 55*4 \\ S]I JS" ps4 M G112090169 811204 PDR ADOCK 05000213 P PDR Jg SA:DL
- l.......{. I
- h...........
.................Q..g SEPB10L SEPB: )L 0 PM
- B SEPB:DL I.. t*/.
h.... d../..'k'............ OF F6CE k ...I eid GL#Tnas 6..Crut W con D suauwe>.....E..M..c..K..e..nna..: d t S.UL WRossell ......................) .....u.......... ......../e..'\\.4..1....1 ..12../. 7...../.8.1...... .. 12../.1./..../. 8.1... ..12..h...I /.81... 12/N.../.81 12 ....../.0\\.../.81 12 onep NRC FORM 318 (10-80) NACM J24 i OFFICIAL RECORD COPY usoeo: --mwo
Mr. W. G. Counsil' cc Day, Berry & Howard Counselors at Law One Constitution Plaza Hartford, Connecticut 06103 Superintendent Haddam Neck Plant RFD #1 Post Office Bcx 127E East Hampton, Connecticut 06424 Mr. Richard R. Laudenat Manager, Generation Facilities Licensing Northeast Utilities Service Company P. O. Box 270 Hartford, Connecticut 06101 Russell Library 119 Broad Street Middletown, Connecticut 06457 Board of Selectmen Town Hall c Haddam, Connecticut 06103 Connecticut Energy Agency ATTN: Assistant Director. Research and Policy Development Departnent of Planning and ^ Energy Policy 20 Grand Street Hartford, Connecticut 06106 U. S. Environmental Protection Agency Region 1 Office ATTN: Regional Radiation Representative JFK Federal Building Boston, Massachusetts 02203 Resident Inspector Haddam Neck Nuclear Power Station c/o U. S. NRC East Haddam Post Office East Haddam, Connecticut 06423 P 4 w-< ~ - o-- e e-m p>=
l o 4-SYSTEMATIC EVALUATION PROGRAM TOPICS XV-8 AND XV-12 HADDAM NECK REQUEST FOR ADDITIONAL INFORMATION TOPICS XV-8, CONTROL R0D MISOPERATION XV-12, SPECTRUM 0F CONTROL ROD EJECTION ACCIDENTS 1. According to your submittal, the last analysis. of these topics was done for the FDSA in 1965: Would you please supply a comparison of the results obtained with the methods used with resultsobtained with either currently approved methods or present day state-of-the-art methods? If this is not possible, we will require calculations with ( present state-of-the-art or approved methods. 2. The Standard Review Plan Section 15.4.8, Spectrum of Rod Ejection Accidents (PWR), states three acceptance criteria. Your stated results meet Criteria A and B. You state that you meet Criteria.C because the fuel enthalpy is less than 200 cal /gm and thus there is no fuel clad damage and no fuel rods in DNB. The staff does not accept the 200 cal /gm as a. limit for. clad damage. Thus you need to supply the percentage or number of rods calculated to experience I departure from nucleate boiling. This number will then be used in. l the radiological evaluation. 6 9 e-- ~ < +
==}}