Docket Nos.. 50-52 /529 nV 53u 50 55(e) Report p
3
\\
n' P. oL BOX 21666 PHOENIX, ARIZON A 85036 November 13, 1981 ANPP-19458-GHD/BSK U. S. Nuclear Regulatory Commission Region V J
' rg Creekside Oaks Office Park f
f, 7
d'g%
1450 Maria Lane - Suite 210
/
Walnut Creek, California-94596-5368 f
7 Attention:
Mr. B. H. Faulkenberry, Chief 2
'ks'yy, kg%h /-
4 (Og Reactor Construction and Engineering Support Branch Y
u, C /'
Subject:
Interim Report - DER 81-37 u
A 50.55(e) Potentially Reportable Deficiency
^
1' Relating to Foxboro Displays Which Failed Environmental Qualification Testing File:
81-019-026 D.4.33.2
Reference:
Telephone Conversation between J. Eckhardt and G. Duckworth on October 14, 1981
Dear Sir:
The NRC was notified of a potentially reportable deficiency in the referenced telephone conversation.. At that time, it was estimated that a determination of reportability would be made within thirty (30) days.
Due to the extensive investigation and evaluation required, an Interim Report is attached.
It is now expected that this information will be finalized by January 29, 1982, at which time a complete report will be submitted.
Very truly yours, W
E. E. Van Brunt, Jr.
APS Vice President Nuclear Projects ANPP Project Director
~~, C M 3 EEVBJr/GHD:ske Attachment tyg :ll ;.,"f g l Ag,ij lJ i
cc: See Attached Page 2 EM odd s
hDRADOCK0500shg
- [l 8111240869 EME
.PDR h ~M3C_
L
(_.
U. S. Nuclear Regulatory Commission Attention:
Mr. B. H. Faulkenberry, Chief ANPP-19458-G3D/BSK November 15, 1981 Page 2 cc: Victor Stello Office of Inspection and Enforcement U. S. Nuclear Regulatory Commission Washington, D. C.
20555 J. A. Roedel D. B. Fasnacht G. C.
' ndognini F. W. Hartley J. M. Allen A. C. Rogers B. S. Kaplan W. E. Ide J. Vorees J. A. Brand A. C. Gehr W. J. Stubblefield W. G. Bingham R. L. Patterson R. W. Welcher R. M. Grant D. R. Hawkinson L. E. Vorderbrueggen Ms. Patricia Lee Hourihan 6413 South 26th Street Phoenix, Arizona 85040 A-
- m m
. m.
m u
r INTERIH REPORT - DER 81-37 POTENTIAL REPORTABLE DEFICIENCY ARIZONA PUBLIC SERVICE COMPAY (ADS)
PVNGS UNITS 1, 2 AND 3 I.
Potential Problem Foxboro Model 270 Displays are required to be environmentally and seismically qualified per specification requirements and IEEE Standards 323-1974 and 344-1975; however, these units were delivered to the jobsite prior to qualification as authorized by Bechtel Supplier Deviation Disposition Request (SDDR) No. 2605. Operational failures were experienced by Foxboro during the final seismic testing following the environ-mental tests. The failures are attributed to corrosion of Burndy connectors within the display electronics. This equip ment is being purchased by Bechtel and also Combustion Engi-neering as part of the NSSS contract.
II.
Approach To and Status Of Proposed Resolution Foxboro has notified Bechtel that a corrective action plan is being developed; however, the specific details have not been finalized.
III.
Projected Completion of Corrective Action and Submittal of the Final Report The evaluation, resolution and final report are forecast to be completed by January 29, 1982, i
L