ML20035H120

From kanterella
Jump to navigation Jump to search

Informs That NRC Review of Amend Requests 200 & 67 Re Diesel Generator Testing Has Been Temporarily Put on Hold Pending Completion of Util Analyses (Currently in Progress) of Emergency Diesel Generators Performance Requirements
ML20035H120
Person / Time
Site: Beaver Valley
Issue date: 04/26/1993
From: Edison G
Office of Nuclear Reactor Regulation
To: Sieber J
DUQUESNE LIGHT CO.
References
TAC-M84225, TAC-M84226, NUDOCS 9305030168
Download: ML20035H120 (4)


Text

,

~,p* *t o

  1. ~

uq'o UNITED STATES I'

NUCLEAR REGULATORY COMMISSION c

g

.E WASHINGTON, D. C. 20555 t

j[

April 26, 1993 t

Docket No. 50-334 and 50-412 Mr. J. D. Sieber, Senior Vice President and Chief Nuclear Officer Nuclear Power Division

~

Duquesne Light Company Post Office Sox 4 Shippingport, Pennsylvania 15077-0004

Dear Mr. Sieber:

SUBJECT:

BEAVER VALLEY POWER STATION UNITS 1 AND 2, PROPOSED LICENSE AMENDMENT PEQUEST N05. 200 AND 67 REGARDING DIESEL GENERATOR TESTING (TAC NOS.

34225 AND M84226)

The purpose of this letter is to inform you that the NRC review of the subject license amendment request has been temporarily put on " Hold" pending your completion of the Duquesne Light Company (DLC) analyses (currently in progress) of emergency diesel generators (EDG) performance requirements.

In rniewing your license amendment proposal dated October 6,1992, which proposed a relaxation in EDG surveillance testing, the staff determined that the technical specifications (TS) for Units 1 and 2 do not specify certain EDG test performance parameters such as voltage, frequency, and time to come up to speed.

These parameters, as well as the proposed test relaxation, are specified in standard TS.

ne staff feels that it is important to specify these test parameters in the TS to assure quality testing, and to compensate for the proposed relaxation in testing.

In discussions with your staff (S. Sovick, et al.) during February 1993, it appears that the NRC staff and DLC agreed at that time to specify these test parameters as part of the TS change which would include relaxing the 8 hour9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> testing requirement to 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

In a subsequent discussion on April 22, 1993, DLC clarified for the staff that the appropriate values for the test parameters are being reanalyzed at this time.

We understand that parameters for Unit 1 may be available in October 1993 and for Unit 2 in April 1994.

Therefore, the staff cannot complete its 930503016e 930426 4' 3,.

PDR ADDCK 05000334

,],. e y

- - ~

,, a,.,.

p PDR I

QU

1 i

Mr. J. D. Sieber April 26, 1993 i

review at this time. When the needed information is available, DLC may submit i

a stand-alone supplement to the proposed license amendment which supersedes the October 6, 1992 request, and the staff will complete its review.

i Sincerely, i

i Original signed by:

Gordon E. Edison, Senior Project Manager Project Directorate I-3 Division of Reactor Projects - I/II Office of Nuclear Reactor Regulation '

.j v

cc: See next page j

i i

DISTRIBUTION:

Docket File NRC & Local PDRs PDI-3 Reading i

SVarga JCalvo WButler TClark GEdison OGC ACRS (10)

JLinville, RI 2'

crocE LA:PDI-3 PM:PDI-3/

D:PDI-3

\\l NAME(/JDiirE~~

GEdison:mw WButler L1/3/93 Y / / /93 Y /2(/93

//

/ /

f DATE OfflCIAL RECORD COPY

}$#

i FILENAME: A:\\BVM84225.LTR i

Mr. J. D. Sieber April 26, 1993

?

review at this time. When the needed information is available, DLC may submit a stand-alone supplement to the proposed license amendment which supersedes the October 6, 1992 request, and the staff will complete its review.

Sincerely, Gordon E. Edison, Senior Project Manager Project Directorate I-3 Division of Reactor Projects - 1/11 Office of Nuclear Reactor Regulation cc:

See next page

)

9 i

'4 Mr. J. D. Sieber Beaver Valley Power Station i

Duquesne Light Company Units 1 & 2 cc:

i Jay E. Silberg, Esquire Bureau of Radiation Protection Shaw, Pittman, Potts & Trowbridge Pennsylvania Department of l

2300 N Street, NW.

Environmental Resources i

Washington, DC 20037 ATTN:

R. Barkanic l

Post Office Box 2063 Nelson Tonet, Manager Harrisburg, Pennsylvania 17120 Nuclear Safety

~

Duquesne Light Company Mayor of the Borrough of Post Office Box 4 Shippingport Shippingport, Pennsylvania 15077 Post Office Box 3 Commissioner Roy M. Smith West Virginia Department of Labor Regional Administrator, Region -I Building 3, Room 319 U.S. Nuclear Regulatory Commission Capitol Complex 47S Allendale Road Charleston, West Virginia 25305 King of Prussia, Pennsylvania 19406 John D. Borrows Resident inspector Director. Utilities Department U.S. Nuclear Regulatory Commission Public Utilities Commission Post Office Box 181

f 180 East Broad Street Shippingport, Pennsylvania 15077 Columbus, Ohio 43266-0573 l

Director, Pennsylvania Emergency

[

Management Agency i

Post Office Box 3321 Harrisburg, Pennsylvania 17105-3321 I

Ohio EPA-DERR ATTN: Zack A. Clayton Post Office Box 1049 Columbus, Ohio 43266-01492 t

i L

i l

f I