, April 12, 1993
. Docket No. 50-331 DISTRIBUTION MRC & Local PDRs Docket File:
1 Mr. Lee Liu PDIII-3 r/f v0lII-3 Gray.
Chairman of the Board and J. Roe J. Zwolinski Chief Executive Officer M. Rushbrook R. Pulsifer Iowa Electric Light and Power Company OGC ACRS (10)'
Post Office Box 3';l E. Greenman, RIII Cedar Rapids, Iowa 52406
Dear Mr. Liu:
SUBJECT:
DUANE ARNOLD ENERGY CENTER (DAEC) PROPANE TANK l
As part of the resolution for Generic Safety Issue (GSI) 106, the staff-has raised a concern associated with the 500 gallon propane tank located about 25 feet from the turbine building at DAEC. The concern relates to the potential i
impact that this tank may have on the Emergency Diesel Generators (EDG) during i
a seismic event.
If a seismic event were to occur, a loss of offsite power -
could occur as a result of the failure of the ceramic insulators on the station transformer. This demand would start the EDGs.
The seismic event i
could also cause a failure of the subject propane tank.
The tank failure could result in a loss of the EDGs and result in a station blackout. 'It is postulated that the faiiure and damage to the EDGs would' be related to ingestion of propane-through the combustion air-intakes.
Enclosed is a copy of a memorandum dated February 11, 1993, which identified the concerns associated with the tank.
Your staff had verbally informed NRR that you plan to include the propane tank l
in your Individual Plant' Examination of External Events (IPEEE),
You should i~
be assured that DAEC is meeting its' licensing basis for EDG operability requirements. However, please confirm in writing that you will accomplish the above in your IPEEE program.
Sincerely,.
i ORIGINAL SIGED BY JON B. IDPKINS FOR:
l Robert M. Pulsifer, Project Manager Project Directorate III--3 Division of Reactor Projects III/IV/V Office of Nuclear Reactor Regulation 1
Enclosure:
Memorandum for John N. Hannon fm p.77m prigy
[3my3 BZ bu s W 6 Conrad E. McCracken dated 2/11/93 l-cc w/ enclosure:
See next page.
^3Y 9hV V
LA g
,-3 PM:PDIl I-3 DQDJ11-3 MRus k
RPulsifer:sw JRunnon 4/t/ 3 4/ /93 4/qj93 DOCUMENT NAME: G:\\DUANEAR PROPANE.LTR 9304200298 930412 L
- oa ^====gy b.r= c/
l m
,, - ~,
,-w
---n,-r w n n n -n r.-
v.,,,.e,n--~
,,-.,,.,-~s
+,---,-.mn.,
-- -,., n n
l Mr. Lee Liu Iowa Electric Light and Power Company Duane Arnold Energy Center cc:
Jack Newman, Esquire Kathleen H. Shea, Esquire Newman and Holtzinger 1615 L Street, N.W.
Washington, D.C.
20036 Chairman, Linn County Board of Supervisors Cedar Rapids, Iowa 52406 lowa Electric Light and Power Company ATTN: David L. Wilson Plant Superintendent, Nuclear 3277 DAEC Road Palo, Iowa 52324 Mr. John F. Franz, Jr.
Vice President, Nuclear Duane Arnold Energy Center 3277 DAEC Road Palo, Iowa 52324 Mr. Keith Young Manager, Nuclear Licensing Duane Arnold Energy Center 3277 DAEC Road Palo, Iowa 52324 U.S. Nuclear Regulatory Commission Resident Inspector's Office Rural Route #1 Palo, Iowa 52324 Regional Administrator, Region III U.S. Nuclear Regulatory Commission 799 Roosevelt Road Glen Ellyn, Illinois 60137 Mr. Stephen N. Brown Utilities Division Iowa Department of Cosamerce Lucas Office Building, 5th Floor Des Moines, Iowa 50319