ML20035A258

From kanterella
Jump to navigation Jump to search
Forwards T Oneils Responses to G Galletti Note to M Ross Re NRC Review of GE ABWR Remote Shutdown Panel Inventory of Displays,Controls & Alarms
ML20035A258
Person / Time
Site: 05200001
Issue date: 03/18/1993
From: Fox J
GENERAL ELECTRIC CO.
To: Poslunsy C
Office of Nuclear Reactor Regulation
References
NUDOCS 9303250060
Download: ML20035A258 (2)


Text

.

4'

(

)

GE Nuclear Energy i

00:r3 lem:? 2:Orr, :T, 3 cm n ece sz.mc. cw:.

March 18,1993 Docket No. STN 52-001 i

r Chet Poslusny, Senior Project Manager f

Standardization Project Directorate Associate Directorate for Advanced Reactors i

and License Renewal Office of the Nuclear Reactor Regulation

}

Su ject: Submittal Supporting Accelerated ABWR Review Schedule - NRC i

t Comments on RSS Panel

[

l

Dear Chet:

Enclosed are Tim O'Neil's responses to Greg Galletti's note to Monty Ross pertaining to NRC review of the GE ABWR remote shutdown panel inventory of displays, controls and j

alarms.

Please provide a copy of this transmittal to Greg Galletti.

Sincerely, A

ack Fox I

Adv-aced Reactor Programs j

cc: Norman Fletcher (DOE)

[

Keith Gregoire (GE)

Tim O'Neil (GE) i i

9303250060 930318 PDR ADOCK 05200001 A

PDR

.,~

Advanced Reactor Progra

-i March 15,1993 TO:

M. A. Ross FROM:

T. J. O'Neil

SUBJECT:

NRC COMMENTS FROM REVIEW OF ABWR RSS PANEL INVENTORY OF CONTROLS AND DISPLAYS AS LISTED IN SAR SUBSECTION 7.4.1.4.4 REFS.:

(1)

NOTE (UNDATED) FROM G. GALLETTI (NRC) TO MONTY ROSS (GE), SAME SUBJECT (2)

ABWR SSAR, PAGE 7.4-8, RSS CONTROLS AND INDICATORS Reference (1), item 1, requests that both valves in a HPCF test line be included. We do not concur. HPCF testing will not be performed from RSS panels. The RSS function is to isolate the test line during shutdown cooling operation from RSS panels.

Only one valve is required to perform this isolation function.

Reference (1), items 2a and 2c request that RHR heat exchanger " inlet" be changed to heat exchanger " outlet" valve. We concur and will make changes to conform.

Reference (1), item 2b, requests that both valves in the RHR drywell spray line be included. We do not concur. The drywell spray function will not be controlled from RSS panels. One valve is controlled from RSS to assure isolation of the line during shutdown cooling. Only one valve is required for isolation.

Reference (1), item 2d, requests that RHR heat exchanger outlet temperature indication be added to RSS. We concur and will make changes as necessary.

Reference (1), item 3, requests that Spent Fuel Pool (SFP) level and temperature be indicated on the RSS panels. We do not concur. The RSS design does not permit the RHR Fuel Pool Cooling function to be performed during shutdown cooling operations controlled from RSS panels.

M9 O)R i

T. J. O'Neil t

.