APPENDIX'A NOTICE OF VIOLATION Omaha Public Power District Docket: 50-285-Fort Calhoun Station Operating License: DPR-40 l '
l During an NRC inspection conducted on March 12-15, 1990, a violation of NRC requirements was identified. The violation involved the failure to establish adequate abnormal operating procedures.
In accordance with the:" General Statement of Polic and Procedure for NRC Enforcement Actions," 10 CFR Part 2 j
AppendixC(1989)y(EnforcementPolicy),theviolationislistedbelow:
j Inadequate Abnormal Operating Procedures Technical. Specification'5.8.1 requires that. " Written procedures,
shall be established, implemented.... that meet or. exceed the minimum requirements of. sections 5.1 and 5.3 of ANSI N18.7-1972 and Appendix A of-USNRC Regulatory Guide 1.33...."
l f
Regulatory Guide 1.33, Appendix A, Section 6, requires procedures for i
combating emergencies and other significant events. This includes the.
]
'following:
Expected transients Lossofelectricalpower.(and/ordegradedpower. sources)l 1
Fort Calhoun Station Updated Safety Analysis Report, Section l'2.3.2, states, " Plant operation during abnormal conditions are conducted in accordance with written..
procedures. These emergency procedures have a
been written such that the operator can readily perform the immediate V
action necessary based on a given set.of-conditions-..._."
4 Contrary to the above, the following are examples of procedures. that were -
not adequately established.
q" 1.
Abnormal Operating Procedure A0P-16 " Loss of. Instrument Bus Power,"
Revision 0(January 4,1990),didnotaddressthelossofvital' equip-ment powered from the four-120V-AC inverter buses, such as1 radiation monitoring panels and steam generating level controls iThe procedure did not provide guidance for operations during the potential off-normal conditions' associated with the loss, or degradation of'a 120V AC inverter bus.
j 2.
Written procedures had not been established addressing-the loss or degradation of the following vital electrical power sources:
4160V AC Vital Bus 1A3 or 1A4 480V AC Vital Buses 1B3A, 1B3B, IB3C, IB4A, 184B, 184C, 3A-4A, i
]
125V DC Vital Bus DC-1 (EE-8F), AI-41A or DC-2 (EE-8G), AI-41B 9005040183 900427 DR ADOCK 0500 b_
!)
i This is a Severity 1.evel IV violation.
(SupplementI)
(285/9014-01)
Pursuant to the provisions of 10 CFR 2.201, Omaha-Public Power District is hereby required to submit to this office, within 30 days of the date of the letter transmitting this Notice, a written statement or explanation in reply, including for each violation:- (1) the reason for the violation if admitted,-