Notice of Violation from Insp on 900128-0317.Violation Noted:Senior Resident Inspector Found Paper & Hoses in Red Floor Area 6 W/O Continuous Fire Watch Being Present
ML20033G976
Person / Time
Site: Quad Cities  
Issue date: 04/04/1990
From: Shafer W
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To:
Shared Package
ML20033G974 List:
References
50-265-90-02, 50-265-90-2, NUDOCS 9004130233
Download: ML20033G976 (1)


Text

.

NOTICE OF VIOLATION l

l Commonwealth Edison Company Docket No. 50-265 As a result of this inspection conducted on January 28 through March 17, l

1990, and in accordance with 10 CFR Part 2, Appendix C -- General Statement l

of Policy and Procedure for NRC Enforcement Actions (1989), the following violation was identified:

I i

10 CFR Part 50 Appendix B, Criterion V, states that activities affecting t

quality shall be accomplished in accordance with documented procedures.

l I

Technical Specification 6.2.A.11 states that Fire Protection Program implementation procedures shall be adhered to.

l I

I l

The Transient Combustible and Water Protection Surveil)ance Procedure, QOS 4100-15, Revision 9, Step 1, states that at the beginning and the middle of each shif t an inspection shall be conducted of each red floor area listed in this procedure to verify that no transient combustibles are present in the area without a continuous fire watch, j

The Transient Combustible and Water Protection Surveillance Procedure, 005 4100-15, Revision 9, Step 4, defines " transient combustibles" as being such items as wuod (treated and untreated), hoses, cloth, paper, flammable i

j and combustible liquids, and compressed gas cylinders, j

l The Transient Combustible and Water Protection Surveillance Procedure, i

005 4100-15, Revision 9, Step 6, lists the Unit 2 South CR0 Bank on the 595 foot elevation as being red floor area Number 6.

l Contrary to the above, on February 3, 1990, the Senior Resident Inspector found paper and hoses in red floor Area 6 without a continuous fire watch being present.

l This is contidored a Severity level IV violation (Supplement 1).

(265/90002-01)

Pursuant to the provisions of 10 CFR 2.201, you are required to submit to this office within thirty days of the date of this Notice a written statement or explanation in reply, including (for each violation: (1) corrective action taken and the results achieved; 2) corrective action to be taken to avoid i

further violations; and (3) the date when full compliance will be achieved.

Consideration may be given to extending your response time fur good cause shown.

l APR 0 41990

._{.

~

Dated W.

. Sha f er, CMAL) eactor Projects Branch 1 1