A jg Q

j DC3 /'] WO Ila DISTRIBUTION NOV 101981

@ t Fil g:

DNussbaumer NRC PDR RFonner L PDR WCrow h

hGP Docket No. 50-285 e

ORB #3 Rdg STurk DEisenhut WOMill

!!r. W. C. Jones OELD

.g Division Manager, Production S 10 6

A I F' I fF d

Operations Omaha Public Power District JHeltemes ITL L ty..

1623 Harney Street h

zer-3 fi-NOV181981 7 '

9 Omaha, Nebraska 08102 I

CTrammell u.s. uuaru um C COMMIS5DH

Dear Mr. Jones:

Gray File "2,,

y In reply to your letter of August 27, 1981, the issuance of aut iMpiph to store source material in the fom of urarrium hexafluoride (UF6 Fort Calhoun site could be accommodated by the issuance of a source material license by the State of Nebraska or NRC. He have discussed this matter with Nebraska regulatory officials and they favor issuance of a license s

by NRC. We are therefore treating your letter of August 27, 1981, with its 3(tached technical infomation, as an application to MRC for on-site storage of UF. This course of action has been discussed with and agreed G

to by your staff.

In conducting a review of your August 27 letter, we have determined the need for cdditional infomation, identified in the enclosure to this letter, to complete ourcreview of this natter. Your response should be scheduled so as to allow us a 45-day period for final review and processing of your application.

We view your proposed activity as requiring a new source material 1,icense and therefore, pursuant to 10 CFR 170.31, a license fee of $140 will be required. You are requested to remit this amount with your response to this letter.

Plea e contact us if you have any questions concerning this request.

Sincerely, Onginal signed by Robert A. Clark Robert A. Clark, Chief 811130040781111$

Operating Reactors Branch #3 DR ADOCM 05000 Division of Licensing

Enclosure:

Request for Additional Infomation k

cc w/ enclosure:

IA 61 d(D See nort Dace a b...... m

)m.. ADA&m..... a. P [,,,,.QB,Q,,fM,,,, NBR;QL...,,,

Cg(ammelif,p omco Oa

,,,,{,,,,,,,,

WOMiller PFonner RAC1 ark P

,pe,,,,,, e r,,,

n

,[,

[ l..b/81..

.Ql.blal,,,

, //,/,f,?,181,,,

!/.l./.81,,,,,,..)/.j0a1,

.to,!. gal,,,, (l.,f)/,81,,,

/8

. om >

Nnc ronu sis oo noi nacn om OFFICIAL RECORD COPY usamon-m.e

k s.

Onaha Public Power' District cc:

Marilyn T. Shaw, Esq.

LeBoe'u'f, Lamb, Leiby & MacRae 1333 New Hampshire Avenue, N.'W.

Washington, D. C. ' 20036 -

Mr. Emmett Rogert Chairman, Washington County Board of Supervisors-Blair, Nebraska 68023 U.S._ Environmental Protection Agency Regidn.VII~

ATTH:

RegionaiRadiation Representative 124 East lith Street Kansas City, Missouri 64106 Mr. Frank Gibson W. Dale Clark Library 215 South 15th Street Omaha, Nebraska 68102 Alan H. Kirshen, Esq.

r i' an, 0.ansey & Kirshen e

1166 Wecc en Tc,er

". 2 a, 'ebraska 6SiO2 "r. Dennis Kelley

I. ','. S,. C. D.'a s i de r.t I n s p ec t o r 3

".. I c x 6 3 Oc rt Cal r.cun, ','ebraska 68023 "r. Charles B. Brinkman

'ianager - Washington Nuclear Operations C-E Power Systems Combustion Engineering, Inc.

4853 Cordell Avenue, Suite A-1 Bethesda, Maryland 20014 Ellis Simmons

~

Director, Division of Radiological ~

Health State Dept. of Health 301 Centennial Mall South' P. O. Box 95007 Lincoln, Nebraska 68509

b y

r

~.

REQUEST FOR ADDITIONAL INFORMATION A.

Storage Area A.l.

Provide a facility plot plan showing the proposed storage location and its relationship to ventilation 1ntakes and prevailing winds at the Fort Calhoun Station.

A.2.

Describe the cylinder storage conditions (e.g. existing ground with or without cylinder cradles, concrete or asphalt pad with or without cyclinder cradles, hold-down straps, inside or outside storage, security fences, stacking cylinders, cylinder valve pro-tection,. fire protection).

B.'~' Inspection Program B.1 Describe your ir(spection program for receipt and prior to transfer.

~

Include your criteria for rejecting the cylinder (s) and planned actions you will take to make the cylinder (s) acceptable for-receipt or transfer.

B.2 Describe your inspection program for long-te m storage.

Include your criteria for determining if. a cylinder is no longer acceptable for storage and planned actions you will take to make the cylinder acceptable for continued storage..

C.

Industrial Accidents C.

Provide a discussion and assessment of the following industrial accidents to include (1) preventive measures, (2) health, safety and environmental impact to cylinder storage area, other station areas (e.g. containment building, turbine building), and beyond the site boundaries if the accident should occur, and (3) your personnel, procedures, equipment and facilities for dealing with these accidents if they should occur.

C.1 Failure of a cylinder either during on-site handling or storage whe1 the cylinder contains only solid UF -

6 C.2 Failure of a cylinder either during on-site handling or storage when the cylinder contains gaseous UF.

6 C.3 Failure of a cylinder either during on-site handling or storage when the cylinder contains liquid UF. This is unnecessary if 6

it can be shown that such a condition is incredible.

I 8

y$

J D.

Natural Phenomena j

. 'D.. ~ Provide a' discussion and assessment of the following natural phenomena to.. include (1) health, safety.and environmental impacts to cylinder. storage area, other station areas (e.g. containment building, turbine building) and beyond the site boundaries and (2) your personnel, procedures, equipment and facilities for -

dealin~ with,these if they should occur.

g

~ lD.T 'Earthq0akss, 5

-1 D.2 Flooding -

~

-.., E -

'D3: Tornadoes E ~. Emergency Plans-i E.

Include a specific proposed section in the Fort Calhoun Station Emergency Plan to address potential accidents of the proposed storage of UF. It is suggested that this be'done as a separate 6

addendum to the Emergency Plan, iei, a UF6 Accident Contingency Plan.

4 F.

UF6 Cylinder Materials-F.

Clarify the mater'ials of construction for the Type 48X cylinders you plan to utilize.

I

....s e

4 t

1 i