Appendix A NOTICE CJ VIOLATION Union Electric Company Docket No. 50-483 Based on the inspection conducted on Aur.st 30 through September 2, 1977, it aopears that certain of your activities were in noncompliance with NRC requir :.ents, as noted below.

This item is an infrac tion.

Contrary to 10 CFR 50, Appendix B, Criterion XIII, SNUPPS PSAR Paragraph 3.12 and JNSI N45.2.2 Paragraph 6.4.2, th=

inspector determined on Septe=ber 1,1977, that insulation resistance readings of the motors for Room Coolers, Units 10 A & B; 12A & B; 13A & B had not been determined on a perindic basis.

f hK05000483 I2 811106 Di 7