' 'd USHRCIM
'h}yER COMPANY ATLAIN
' Powru 13rst.ntxo 422 Sourn Cstt:acu STyEET, CHAutOTTE, N. C. asa4a A$ = 3 8itt0V B WILLIAM O. PA R K E R. J R.
Scr Patssecut Ttt t Pao'e t:Asta 704 cita= Paeovcito=
November 2, 1981 n>*ces
%'.L..
c)
Mr. James P. O'Reilly, Director
.s U. S. Nuclear Regulatory Commission-Y Yh.'N i
Region II N hh
) '.
101 Marietta Street, Suite ~i100 f
NOVO 91981= -ti t J
Atlanta, Georgia 30303 "k b s macuAt UGM[Qgg Re: McGuire Nuclear Station
'Q) pM Unit 2 Docket No. 50-370
/
7 f
Dear Mr. O'Reilly:
Pursuant to 10 CFR 50.55e, please find attached Significant Deficiency Report SD 370/81-09 concern *ng Rockbestos Cable (Model RSS-6-104) vsed for the McGuire Unit 2 High Range In-Containment Radiation Monitors.
V y truly yours, p
/-
- d. t/)
h$'
William O. Parker, Jr.
PBN/smh Attachment cc: Director Ms. M. J. Graham Office of Inspection & Enforcement NRC Resident Inspector U. S. Nuclear Regulatory Commission McGuire Nuc1 car Station Washington, D. C.
20555 i
f
~
S'l L nUP 6111100523 911102 C
PDR ADOCK 05000370 S
POR
-i a,
-,.,c
l O
McGUIRE NUCLEAR STATION REPORT NUMBER:
SD-370/81-09 REPORT DATE: November 2, 1981 FACILITY: McGuire Nuclear Station, Unit 2 IDENTIFICATION OF DEFICIENCY: High range in-containment radiation monitor cable is not qualified for all postulated LOCA environments per General Atomic letter dated September 23, 1981.
INITIAL REPORT:
On October 15, 1981, A. Ignatonis, NRC Region II, Atlanta, Georgia, was notified of the deficiency by W. O. Henry and T. C. McMeekin of Duke Power Com-pany, Charlotte, N.C.
COMPONENT AND/OR SUPPLIER: The component identified as having a deficiency is Rockbestos Cable, Model RSS-6-104, supplied by General Atomic Company for the high range in-containment radiation monitors.
DESCRIPTION OF DEFICIENCY: Due to a manufacturing deficiency, the identified cable is not fully qualified for all postulated LOCA environments. There is approximate-ly 300 feet of this cable associated with each high range in-containment radiation monitor. There are two such monitors located inside the McGuire Unit 2 containment.
ANALYSIS OF SAFETY IMPLICATIONS:
If a loss of coolant accident occurred and the cable was subjected to the worst case postulated accident conditions, the post accident monitoring function provided by the high range in-containment mrnitors could be degraded or lost.
CORRECTIVE ACTION: The subject cable will be replaced prior to fuel load with qualified cable to be supplied by General Atomic.
s w