a Ramset.
Ramset fastening Systems R O. Box 30-275 275 WinchesterAvenue NewHaven, Connecticut 06511 A Division ofOlin Corporation (203) 789-5000 Telex:62826 October 27, 1981
% I #
Director Novo;gIb8lb 2-8 Office of Inspection & Enforcement I
dad U.
S.
Nuclear Regulatory Commission
'\\
p/
q/
Washington, D.C.
20555
~
Gentlemen:
The attached copies have been sent to both Daniels and Bechtel Power Corporation advising them of a change in the material used in Ramset's 1/4" Trubolt fasteners.
Wolf Creek is the only nuclear site using the 1/4" anchors with a specification listing higher tensile strenghts.
We regret any inconvenience this may cause you.
If additional information is required, please feel ~ free to contact me.
Ver uly y s,
cu~-) h j
Paul Hollenbach Technical Sales Nuclear Specialist PH;mlm enclosures 16l9 Se,q i
8111060505 811027 PDR ADOCK 05000482 A
PDR L
I
.a
.' ' ~
gyyf Ramset fastening Systems P O. Box 30-275 275 Winc/resterAvenue NewHawn. Connecticut 06511 A Division ofOlin Corporation (203) 789-5000 Telex:52826 October-27, 1981 Daniel International. Corp.
P.
O.
Box 146 New Strawn, KS 66839 Attention:
Mr. Chris Phillips, Civil Eng.
RE:
Spec #10466 QA-1 PO 7158-SR-15030
Dear Mr. Phillips:
This will confirm the information given verbally regarding material specificativa for the Ramset 1/4" Trubolt fasteners.
The. material specification for standard Trubolt fasteners listed in Catalog 810-5-77, which is the referenced data in PO#7158-SR-15030 for Daniel Construction Company at Wolf Creek as follows:
Bolt:
AISI 1144 Tensile Strength - 108,000 psi (min)
Yield Strength - 90,000 psi (min)
Expansion Sleeve:
AISI 1008 Cold Rolled Steel Nut:
ASTM.A563 Grade A Washer:
AISI C1010-1020 Plating:
0.0002" - 0. 0003" Zinc Plate with Clear Chromate Finish The current material specification as listed in our current Catalog (GC-AE 8/81), attached, is as follows:
l Bolt:
3/8" l'/4" AISI 1144 l
Tensile Stcength - 108,000 psi (min)
Yield Strength - 90,000 psi (min) 1/4" S300 Pb/AISI 12Ll4 I
Tensile Strength - 78,000 (typical)
Yield Strength - 60,000 psi (typical) i Expansion sleeve:
AlS1 1008 Cold Rolled Steel t
Nut:
ASTM A563 Grade A Washer:
Alsl C1008-1018 Plating:
0.0002 - 0.0003" Zinc Plate with Clear Chromate Finish l
l l
[
=
e Danijl InterF onal Corp.
October 27, 1981 E<'O.
Box 146 New Strawn, KS 66839 Page 2
Attention:
Mr. Chris Phillips, Civil Eng.
The only anchors directly affected are the 1/4" Trubolts and your records should be updated to show the. decreased tensile strength of 78,000 psi (typical).
Ramset has evaluated the bmpact of using the previously published data of 108,000 psi tensile strength material.
Using a tensile stress area of.032 for 1/4" anchors the tensile strength of anchors with 78,000 psi tensile steel should be 2496 lbs. which is well above design loads assigned 1/4" anchors.
We apologize for any inconvenience this change may cause you.
Ramset has, in accordance with 10CFR21 advised the NRC regarding this change.
If you have any questions or require additional technical assistance regarding this matter, please feel free to c
[ tact me.
V y
ruly r s, aul Ivlleabach Technical Sales Nuclear Specialist PH:mlm enclousre cc:
Bechtel Power Corp.
NRC f
T---7e-
, m v u-d w.
r-
'F
~ '-"
- ?m"l-+
-m""
-T'w e
7----
--r 4w-