u, y

TELECOPY TO NRC j]

cm

>z October 30, 198,1 g p.,

2a yk

-A o m

- I U. S. Nucicar Regulatory Co:inission

,9'Yh(fD/ fl j (8 D

y,@

Region II C

101 Marietta Street, NW ciG 1

NOVO 4 Iggi, 22 Suite 3100

^

S Atlanta, Georgia 30303 d u.%m ne N

b co w n e.

\\g SQRO-50-327/81125 Reported Under Technical Specification:

6.9.1.'12.i Date of Occurrence: October 29, 1981 Time of occurrence:

1900 CST Technical Specification Involved:

3.7.8.1 and 3.0.3 Conditiono Prior to Occurrence:

Unit 1 Mode 1 28% Power Unit 2 Mode 4 0% Power Identification and Description of Occurrence:

During review of Preoperational Test Report 2-FT-703, it was determined that during a sicamic event a direct path Irom the auxiliary building to the environment could be opened via a 3 ft. x 3 ft. pipe chaec which paanes through wall "Al" at elevation 685. Under this condition the Auriliary Lu11 ding Gas Treatment System (ABGTS) would be inoperable Since it could not maintain the required negative % inch pressure.

Apparent _Cause of Occurrence:

Releasca from the auxiliary building to the environtncut due to a sicamic event thraugh this pipe chase van overlooked during initial design.

Other Related Evente:

None Corrective Action Taken or Planned:

The ABCTS vas declared im perable on both units at 1900 CST. The pipe chase vao scaled with RTV foam at 2345 on October 29, 1981; therefore,

'T 9 ).

the units vere in cornpliance with the requirements of LCO's 3.7.8.1 and 3

ll'/

3.0.3, and the ABCTS declared operable.

D

\\lALD!ngg79g L

DIRECTop'

c. c. nason

^SSISTANT To OlRECTOR Power Plant Superintendent OIRECTCY, ppp; Sequoyah Nucicar Plant DIRECioy,gp93 Dl RECTO ~ ", ENF/lNV D!pECTO2, E7f 8111050765 ei103o PDR ADOCK 05000327 PUBUC AFFNRS OFFICFO S

PDR

,