ML20030D715

From kanterella
Jump to navigation Jump to search
IE Insp Repts 50-454/81-12 & 50-455/81-10 on 810812-13. Noncompliance Noted:Failure to Provide Measures for Protection & Preservation of safety-related Equipment
ML20030D715
Person / Time
Site: Byron  
Issue date: 09/01/1981
From: Hayes D, Neisler J
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To:
Shared Package
ML20030D710 List:
References
50-454-81-12, 50-455-81-10, NUDOCS 8109150570
Download: ML20030D715 (4)


See also: IR 05000454/1981012

Text

_

'

I

.

U.S. NUCLEAR REGULATORY COMMISSION

OFFICE OF INSPECTION AND ENFORCEMENT

REGION III

Report No. 50-454/81-12; 50-455/81-10

Docket No. 50-454; 50-455

License No. CPPR-130; CPPR-131

Licensee: Commonwealth Edison Company

l

P. O. Box 767

-

Chicago, IL 60960

j

Facility Name: Byron Station Units 1 and 2

..

'

Inspection At: Byron, IL

Inspection Conducted: August 12-13, 1981

Inspector:

J. H. Neisler

[f

- /- 8/

Approved By:

D. W

by

f'

7[/

/

,

Reactor Projects ection IB

/'

,

l

Inspection Summary

Inspection on August 12-13, 1981 (Report No. 50-454/81-12; 50-455,'80-10)

Areas Inspected:

Licensee's corrective action relative to previo2s inspec-

tion findings. Followup items reported pursuant to 10 CFR 50.55(e). Followup

Inspection and Enforcement Bulletin action. Reactor Protective System instru-

mentation work activities and records. The inspection involved a total of

12 inspector-hours onsite by one NRC inspector including 0 inspector-hours

onsite during offshifts.

Results: Of the four areas inspected, no items of neacompliance were identi-

fied in three areas. One item of noncompliance was identified in one area

(violation-protection and preservation of equipment).

l

l

1

!

l

l

8109150570 910907.

PDR ADOCK 05000854

0

?DR

.-

..

.

_

__

_ _ . _

1

DETAILS

I

,

-.1.

Persons Contacted

f

Principal L'censee Employees

i

  • G. Sorensen, Construction Superintendent

i

  • M. A. Stanish, Quality Assurance Superintendent
  • P. Wicyk, Field Engineer
  • L. A. LaBanca, QA Engineer
  • R. Tuetken, Assistant Project Superintendent
  • R. B. Klingler, QA Supervisor
  • H. H. Kaczmarek, QA Engineer

L. S. Combs,.QA Engineer

H. Harger, Field Engineer

l

  • Denotes those persons attending exit interview.

l

2.

Licensee Action on Previously Reported Items

50-454/80-20-01 (Closed) Unresolved item.

Incomplete welds in boron

system on level 401 in the auxiliary bui!4ing. The fourteen incomplete

welds have been completed, inspected and required NDE performed. This

item is considered resolved.

50-454/80-25-17 (Closed) Noncompliance.

Identification of instrument

lines by colored tags. Licensee has devised a calor coding system for

identifying redundant instrument lines during installation to assist

in the verification that the separation criteria is maintained. The

lines will be color coded with multi-colored tapes until permanent

metal tags can be attached. This item is closed.

50-454/79-18-01 (Closed) Noncompliance. Failure to document corrective

actions on controlled documents. The nonconformance and corrective

actions have been properly documented. Procedures are in place re-

quiring contractor to initiate nonconformance reports for nonconform-

ances identified on vendor supplied items requiring corrective actions.

l

This item is closed.

l

50-454/80-?5-05 (Closed) Noncompliance. Measures to identify and

l

document cable routing deviations. Hatfield procedure No. 10,

l

Revision 10 Issue 2 dated June 8,.1981, includes instructions and

l

requirements for the identification and documentation of cable routing

deviations,. checklist HP 105 Part III.A. requires verification of

'

cable routing by Quality Control inspectors. This item is closed.

50-454/80-25-12-(Closed) Noncompliance.

Identification of nonconforming

components.

Instructions for placing h>1d tags on generic type noncon-

'

formances have been established. Tags ' nave been placed for those non-

conforming items identified in the nonc ompliance.

See also IE Inspection

Report No. 50-454/81-02. This item is considered closed.

-2-

!

~

,

.-

.

-

.

-

-,

,-

,

. - - - .

,

3.

Inspection and Enforcement Bulletins

IEB 80-03

" Loss of Charcoal from Standard Type II, 2-inch

Tray Absorber Cells." Filters to be used at Byron

have been examined and tested by the vendor, Farr

Filter Corperation. The vendor's examination and

test revealed no deficiencies in the rivet spacing

or screet/ casing separation. This bulletin is closed.

IEB 80-05

" Vacuum Condition Resulting in Damage to Chemical

Volume Control System (CVCS) Hoidup Tanks." The

l

tanks are designed for an external pressure. A

nitrogen cover blanket is supplied by a header.

High and low pressures in the header are annunciated

locally and alarmed on the main control board.

In

case of rapid removal of liquid from the tank, a

cover gas makeup path sized to admit gas at the maximum

l

liquid removal rate is provided. This Bulletin is

closed.

IEB 81-03

Flow Blockage of Cooling Water to Safety System

,

'

Components by Corbicule Sp. (Asiatic Clam) and

Mytilus Sp. (Mussel). Asiatic clams have not been

l

found in the Rock River, the source of cooling water

l

for Byron, and should not cause cooling water flow

blockage to safety systems. This bulletin is closed.

4.

Items Reported Pursuant to 10 CFR 50.55(e)

l

Incorrect weights for Velan globe valves identified when compared to

i

drawings. Correct weights have been determined by recalculation and/

or actual weighing by Velan Valbe Corporation and the affected drawings

l

have been corrected and redistributed. This item is closed.

!

l

S.

Instrumentation

!

!

The inspector observed the installation of pressure and flow instru-

mentation associated with the reactor protective system and examined

installation and inspection documentation relative to those instruments

for which installation activities are complete.

The inspector noted that instruments had been calibrated and installed

on their respective racks. The instruments on rack IPL 75J were being

l

used as storage hangers for coiled welding hoses, welding face shields,

hats, grinding masks, and as storage racks for scrap pipe.

Hoses and other welder's equipment were observed on rack IPL 52J.

This

failure to provide measures for the protection and preservation of safety

related equipment is considered an item of noncompliance with 10 CFR 30,

Appendix B, Criterion XIII as described in Appendix A of the report

transmittal letter.

(50-454/81-12-01).

-3-

.

. _ .

(-

-

--

.,

,

f

I

l

6.

Exit Int rview-

l

The inspector met with licensee representatives (denoted under Persons

'

Contacted) at the conclusion of the inspection on August 13, 1981.

The inspector sununarized the scope and findings of the inspection.

'The licensee acknowledged the findings reported herein.

,

i

i

!

4-

-

-,

-

, . - -

_

-n

.

-w ns-

3

,-,

s_

-,--..

--

t