l McGUIRE NUCLEAR STATION REANALYSIS OF MATH MODELS FOR ENVELOPE SPECTRA l

t AUGUST 14, 1981 i

8108310358 810824 PDR ADOCK 05000369 P

PDR

1

1.0 INTRODUCTION

This report summarizes the results of the reanalysis of 22 piping math models for McGuire Nuclear Station, Unit 1, which was required by the Nuclear Regulatory Commission in its letter of April 8, 1981 ( AttachTent 1). These math models were identified in Duke Power's report, " Review of Piping Seismic Analysis Methods" of March 2,1981, as using spectra analysis methods different from the envelope of all spectra as specified in the Standard Revied Plan 3.7.3.

The NRC letter requested these math models to be reanalyzed to include the envelope spectra method. Table 1 is a listing of the 22 math models which fall in the scope of this reanalysis.

The topics addressed in this summary report are listed in Part 2 of Attachment 1.

The following sections and tables summarize the analysis results of each math model and present the acceptance criteria for each topic.

2.0 ANALYSIS RESULTS 2.1 Loading Conditions The piping in all the reanalyzed math models is ASME Class 2 or 3 or non-ASME (Duke Classes B, C or F). Table 3.9.2-1 of the McGuire FSAR (Attachment 2) lists the loading conditions for these particular classes of pipe.

The loading conditions reanalyzed for these math models were the Operating Basis Earthquake (0BE) and the Safe Shutdown Earthquake (SSE). The results of the other loading conditions were obtained from existing analysis and combined with the OBE and SSE loads for evaluating code combined stresses, support /

restraint design and nozzle loads on equipment, as appropriate,

F 2.2 Code Computed Stresses The McGuire Nuclear Station, Unit 1 piping analysis was performed using the load and stress criteria listed in Attachment 2 and the correspcoding code equations in paragraph NC-3652 of the 1971 ASME Section III Code, Winter 1972 Addenda, the Code of Record for McGuire piping analysis.

Since the reanalysis of the 22 math models involved only the OBE and SSE loads, only the Upset (ASME Equation 9) and Faulted Conditions were evaluated. All other design conditions were met by the previous analysis. The Dynamic Internal Fluid Loads (DSL) noted on Attachment 2 were actually combined with the Upset loads, as required by Equation 9, as well as the Faulted loads.

The largest Upset (Equation 9) stress is tabulated in Tables 2 and 3 for each math model along with the corresponding allowable stress (1.2 S ).

The sixteen (16) math models in Table 2 were reanalyzed h

to include the appropriate Reactor Building spectra because these math models attached to this structure at a containment penetration.

As seen from Table 2, no math model had an Equation 9 stress to exceed its allowable value.

Table 3 lists the six (6) math models which were previously identified as using multiple spectra methods for seismic analysis. The math models were reanalyzed with their appropriate boundaries to include the envelope spectra for each. Again, no math model had Equation 9 stresses to exceed its allowable value.

Safe Shutdown Earthquake stresses were not directly evaluated for McGuire Nuclear Station, Unit 1.

It can be seen from Attachment 2 that stresses combined for the Faulted Condition are identical to the Upset plus DLS when the SSE stresses are substituted for the OBE stresses.

Since SSE stresses are 15/8 OBE and the allowable stress for the Faulted Condition is two times that for the Upset Condition, it can be seen that if the Upset stresses are less than the Upset allowable stresses, the Faulted stresses will be less than the Faulted allowable stresses.

2

t 2.3 ASME Service Level Allowables The allowable stresses listed in Attachment 2 were used for each design condition rather than the ASME Service Level allowables.

The service level allowables were introduced in a version of the code later than the Code of Record for McGuire Nuclear Station.

l 2.4 Support / Restraint Loads New SSE loads were generated for all support / restraints (S/R) in each reanalyzed math model.

For this reanalysis, SSE response spectra were used with the allowed SSE damping values listed in Regulatory Guide 1.61.

The previous analysis of these math models used OBE spectra and OBE damping values with the results being ratioed by 15/8 to obtain SSE results. The conservatism of this ratio method in obtaining S/R loads was substantiated from the reanalysis.

Even though higher floor spectra were used in the envelope reanalysis, only a small percentage of the total number of 5/R's actually had SSE load increases over the previous analysis and, furthermore, no additional S/R's were required.

Table 2 summarizes the S/R results of the envelope spectra reanalysis of the 16 containment penetration math models.

Seven of these 16 math models had no SSE load increases. This was mainly due to the conservatism of the previously discussed method for obtaining SSE loads.

Table 3 presents a summary of the S/R results for the six math models previously analyzed using multiple spectra methods. These math models were analyzed with their appropriate overlap boundaries and using the envelope spectra methods.

Since the steam generator spectra was included in the envelope for these math models, a higher percentage of S/R had SSE load increases.

3

I 2.5 Support / Restraint Acceptance Criteria The S/R loads generated by the envelope spectra analysis were compared to the allowable loads in each S/R design calculation. All existing S/R designs for the math models listed in Table 2 were acceptable for the new loads except for one S/R in Math Model FWA. This S/R required field modification under the station modification program.

All but seven (7) S/R's for the math models listed in Table 3 were likewise acceptable. These seven S/R's are in math models which attach to the Steam Generator at a single nozzle which theoretically required its spectra to be included in the envelope.

However, due to the large size of the math models, an analysis was performed to determine the portions of the piping systems actually influenced by this spectra. This analysis determined that the seven S/R's are not on a portion of the pipe which is excited by the Steam Generator.

Des.igns for these S/R's are qualified for the envelope spectra applicable to that portion of the piping system by which they are excited.

As such, designs for these S/R's are adequate without modification.

2.6 Equipnent Nozzle Loads and Acceptance Criteria The equipment nozzle loads generated by the envelope spectra analysis l

were reviewed against the allowable loads. All equipment had allowable nozzle loads higher than the new loads.

2.7 I.E.Bulletin 79-02 The reports which were previously submitted by Duke Power Company stating its compliance with IE Bulletin 79-02 are still valid for S/R's in the math models which were reanalyzed for envelope spectra.

Therefore, no new data concerning this Bulletin is required.

4

r 3.0 McGUIRE NUCLEAR STATION, UNIT 2 The procedures for piping analysis for McGuire Unit 2 require the use of envelope spectra. Hence, no further information is required to show compliance with Attachment 1 for this unit.

4.0 CONCLUS SN The reanalysis of the twenty-two (22) McGuire Nuclear Station, Unit 1 piping math models for envelope spectra provided evidence of the conservatisms in the existing design of piping and support /

restraint components as well as in analysis methods. The allowable stress was not exceeded for any piping component in any of these math models.

Evidence of additional conservatisms comes from the review of the support / restraint designs.

Only one S/R required hardware changes for the envelope spectra loads. The majority of the support /

restraints (83%) had no load increases from the previous analysis, mainly due to the use of OBE damping values in calculating SSE loads instead of the higher SSE damping values allowed in Regulatory Guide 1.61.

The reanalysis of 22 piping math models described in this report demonstrated adequate safety nargins in piping stress levels and pipe support loads.

5

,y y" p, f(k[.N NifCLIlh'R RhGd TOdY COMMISSION

,,f

/.E n ASHINGTord. D. C. 20555 ATTACHMENT 1

../{Shd[j8 APR LO Page 1 of 3

{

E O

,.. fi.,. h Nlb Dcciet Nos. : -50'-369 and 50-370 Duke Powei Company ATTil:

Mr. William O. Parker, Jr.

Vice President - Steam Production P. O. Box 33189 422 South Church Street Charlotte, North Carolina 28242

Dear Mr. Parker:

Subject:

Piping Seismic Analysis Methods (McGuire Nuclear Station, Units 1 & 2)

Your report, " Review of Piping Seismic Analysis Methods" of March 2,1981 indicates that in 22 out of 355 piping math models, the seismic analysis portion of the design used reponse spectra other than the envelope spectra as required by Standard Review Plan 3.7.3.

We find that the information submitted is not acceptable to justify this deviation from the SRP.. We will, therefore, require that the safety margin of these piping math c.edels be cetermined by reanalyzing and including the envelope of the spectra in the seismic portion of the analysis.

Specifically, we request that you provide the following information:

1.

A list of all reanalyzed problems.

2.

For each piping problem:

a.

Prescribed loading conditions.

vb. / The largest code computed stresses for the combined loading conditions and its locat' ion.

v c.

Corresponding ASME Service Level allowable.

d.

Internal loads on all supports, and at equipment nozzles.

e.

Corresponding allowable loads and the basis for their acceptability.

f.

t Confirmation of Base ' plate bolt ' factors of' safety pertIE rBulletin 79-02.

A

.h L

]

/

ro Page 2 of 3 r,:

APR 8 1981 2-We consider that submittal of the requested infonnation will meet our 90 day reanalysis requirement described in Section 3.7.2 of Supplement No. 5 to the Safety Evaluation Report.

Sincerely, kJ ~bE.<0Ac.4cz.

Robert L. Tedesco, Assistant Director for Licensing Division of Licensing cc:

See next page o

6 B

n e

i e

7

.me

-e

- O j

fir. William 0. Parker, Jr.

Page 3 of 3

]

i-

' lice President, Steam Production Duke Power Company P. O. Box 2178 422 South Church Street Charlotte, North Carolina 28242 cc: Mr. W. L. Porter Mr. Tom Donat Duke Power Company Resident Inspector McGuire NPS P. O. Box 2178 c/o U.S. Nuclear Regulatory Commission 422 South Church Street

. Post Office Box 216 Charlotte, North Carolina 28242 Cornelius, North Carolina 28031 Mr. R. S. Howard Shelley Blum, Esquire Power Systems Division 1402 Vickers Avenue Westinghouse Electric Corporation Durham, North Carolina 27707 P. O. Box 355 Pittsburgh, Pennsylvania 15230 Dr. Richard F. Cole Administrative Judge Mr. E. J. Keith U. S. Nuclear Regulatory Commission EDS Nuclear Incorporated Washington, D. C.

20555 220 Montgomery Street San Francisco, California 94104 Mr. J. E. Houghtaling NUS Corporation 2536 Countryside Boulevard Clearwater, Florida 33515 Mr. Jesse L. Riley, President The Carolina Environmental Study Group 854 Henley Place Charlotte, North Carolina 28207 J. Michael McGarry, III, Esq.

Debevoise & Liberman 1200 Seventeenth Street, N. W.

Washington, D. C.

20036

/

Robert M. Lazo, Esq., Chairman Atomic Safety and Licensing Board U. S. Nuclear Regulatory Commission Washington, D. C.

20555.

Dr. Emmeth A. Luebke Atomic ifety and Licensing Board U. S. Nuclear Regulatory Commission Washington, D. C.

20555 8

ATTACitMENT 2 s'

Table 3 9.2-1 l%

Stress Criteria for Piping Duke Classes 8. C and F C0tJD I T 10fl LOADS CRITERIA 1.

Normal ThermalDisplacemenh ASME lil, Class 2 Pressure Weight

~

l 2.

Upset Thermal Displacement-N OBE (Displacement)

} (Secondary Stresses)

=g S

Pressure Weight

)(PrimaryStresses)

= 1.2 Sh OBE (inertia) l 3

Faulted Pressure Weight

] (Primary Stresses)

= 2.4 S l

SSE (inertia) h q

51 DSL*

1 4.

Faulted Pressure 110*6

)'._ (Primary Stresses)

= 2.4 S 2

Weight I

Pipe Rupture i

N l

l f Dynamic Internal Fluid Loads Associated with Plant Faulted Condition.

"e l

l 0

Revision 5 9

.n+-.,..

.-,,-.-,n--

.n.._,

, _ _ ~ _, -,, _ _ -...., - -

TABLE 1 MATH MODELS REANALYZED FOR ENVELOPE SPECTRA SYSTEM MATH MODELS

1.. Steam Generator Blowdown Recycle - BB 1.

BBW, BBX, BBY, BBZ 2.

Auxiliary Feedwater - CA 2.

CAM, CAN, CAO, CAP 73.

Feedwater - CF 3.

CFC 4.

Refueling Water - FW 4.

FWA 5.

Residual Heat Removal - ND 5.

NDA 6.

Safety Injection - NI 6.

NIB, NID, NIE, NIK, NIU 7.

Chemical and Volume Control - NV 7.

NVA, NVS, NVU 8.

Containment Ventilation Cooling

~

8.

RVA Water - RV 9.

Main Steam - SM 9.

SMA 10.

Containment Air - VX 10.

VXA i

i l

I i

l i

1 i

8/14/81

1 TABLE 2 l

CONTAINMENT PENETRATION MATH MODELS r

l STRESS AND SUPPORT / RESTRAINT REANALYSIS

SUMMARY

Stress Summary Support / Restraint Suninary i

Largest ASME No. of S/R No. of S/R With Basis l

Eq. 9 Eq. 9 Stress per SSE Load for Math Model Stress Allowables Ratio M.M.

Increases Acceptance

[

BBW 16111 19080

.844 54 3

S/R Design Review BBX 16566 19080

.868 57 None BBY 15502 19080

.812 53 6

S/R Design Review BBZ 18278 19080

.958 56 None l

FWA 17928 19680

.911 149 16 Note 1 NDA 20012 21492

.931 117 9

S/R Design Review NIB 12205 21492

.568 25 8

S/R Design Oeview 1

NID 19074 21360

.893

_17 None NIE 12794 20635

.620 9

2 S/R Design Review NIK 14904 21492

.693 45 None NIU 18132 22320

.812 23 9

S/R Design Review NVA 18088 20640

.876 Note 2

~--

NVS 15724 19522

.805

-35 10 S/R Design Review NVU 11208 21000

.534 30 None RVA 14284 18000

.794 22 None VXA 3708 18000

.206 6

None Notes:

1.

One support / restraint was identified as not being acceptable for the new loads. A station modification project was initiated to update the support / restraint to handle the envelope spectra loads.

2.

The piping in this math model was rerouted for a station mr.dification. Envelope spectra was used and support / restraints. were redesigned for new locations and loads.

8/14f l

TABLE 3 t

PREVIOUSLY MULTIPLE SPECTRA MATH MODELS STRESS AND SUPP0P.T/ RESTRAINT REANALYSIS

SUMMARY

4 L

Stress Sumary Support / Restraint Sumary t

l Largest ASME No. of 5/R No. of S/R With Basis Eq. 9 Eq. 9 Stress per TSE Load for i

Math Model Stress Allowables Ratio M.M.

...c reased Acceptance 4

I CAM 17110 18000

.951 93 21 S/R 1.esign Review l

CAN 19933 21000

.949 77 7

S/R Cisign Review CAO 20378 21000

.971 97 35 S/R Design Review CAP 20384 21000

.971 92 13 S/R Design Review CFC 17164 18000

.954 148 26 Note 1 M

SMA 12639 21000

.602

- 94 60 Note 1 l

Notes:

1.

All supports / restraints were approved by the S/R Design Group and approved Tcr t.he envelope of all spectra except for 4 in Math Mooel CFC and 3 in Math Model SMA for all spectra.

Acceptance of these seven S/R's is discussed in Section 2.5 of this report.

i 3

i 8/14/81