Date of occurrence:
5/27/81 Time of Ocetzrrence:
1415 hrs.
Unit 2 Techa.ica.1 Specification Involved! Tabic 3.1.A Conditions Prior to Occurrenco Unit 1 in ref witng outage: unica 2 and 3 in normi operatico at 1,083 sud 1,055 We, respectively.
1 Identification and Description of occurrence During routine surveillance testing (Surveillance Instruction 4.1. A.14) turbine first-stage pe_ruissive switches PS-1-81A and B. and PS-1-91A and B were found above technical specification limits. The greatest out of tolerance was 5.9 percent.
Apparent _Ca_use of Occurrence Setpoint drift.
Other Ec1Ated events BFRO-50-259/7908, -260/7916, -296/7907, and -259/8058.
Cor'rective__ Action Taken or Planned Setpoints were reset to the proper value, and the surveillance instruction coupleted satisfactorily. Additionally, a design ebange request (DCR 1398) has been initiated to replace these svitt.has with an analog transmitter with a trip switch.