Significant Deficiency Rept SD 413-414/81-09 Re Incorrectly Specified Fillet Welds,Initially Reported on 810508.Process Control Forms Originated & Checked to Ensure Accuracy. Personnel Retraining Will Be Completed by 810701
ML20030C027
Person / Time
Site: Catawba  
Issue date: 06/08/1981
From: Parker W
DUKE POWER CO.
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
10CFR-050.55E, 10CFR-50.55E, NUDOCS 8108250324
Download: ML20030C027 (2)


Text

.Cfg f_ : DUKE POWER COMPANY *, - Cog

O.g -

Powen Buxt.ntwo 422 SocTn Cnuncu STnezr, CnAa'thrTz,N.f y C.2824a

  • ' ' U:"

'q,-. U * ]Q wt L LI AM O. PA R M E R. J R. v.c, P.cs or~v June 8, 1981 Tct c.-o~ c:A c.7o. 373-4083 Sicau Paoovction pt 002 0 ab fl O d7-03lJ Mr. James P. O'Reilly, Director y ~ U. S. Nuclear Regulatory Commission d1 ,f h r tra Street, Suite 3100 . %SDl5 C3 Atlanta, Georgia 30303 ,_m. ~n a j N Ek p'4 Re: Catawba Nuclear Station ", p Units 1 and 2 9' Docket Nos. 50-413 and 50-414 J ch

Dear Mr. O'Reilly:

Pursuant to 10CFR 50.55e, please find attached Significant Deficiency Report SD 413-414/81-09. Very truly yours, O h M j t William O. Parker, Jr. RWO/dj s Attachment 1 cc: Director IIRC Resident Inspector j Office of Inspection and Enforcement Catawba Nuclear Station l U. S. Nuclear Regulatory Commission l Washington, D. C. 20555 l l l 1 1 i 1 0108250324 810608. PDR ADOCK 05000413 0 PDR 6,-27 3 , /r

s CATAWBA NUCLEAR STATION REPORT NUMBER: SD 413-414/81-09 REPORT DATE: June $, 1981 FACILITY: Catawba Nuclear Station, Unit 1 IDENTIFICATION OF DEFICIENCY: Fillet welds incorrectly specified. INITIAL REPORT: On May 8,1981, Mr. J. Bryant of Region 11 was notified of this deficiency by Mr. W. O. Henry of Duke Power Company, Charlotte, NC 28242 DESCRIPTION OF DEFICIENCY: During fitup, improper weld sizes were found to have been issued on some welding process control. When the undersized welds were found at fitup and returned for correction, the weld sizes were again incorrectly specified: Two welds (1 SA 31-1 and 1 SA 31-2) were found to be undersized and in violation of design criteria (ASME Section 111). These welds are further identified as follows: Sys: SA-Main Steams Supply to Auxiliary Equipment Loc: Auxiliary FDW Pump Turbine Exhaust Piping Size: " 0.D. Sch. 80 Code: ASME Section lil, Class ll, Duke Class B l SAFETY IMPLICATIONS: Failure to indicate the proper size welds on process control could result in undersized welds that would not be detected during inspection. This condition might result in failure l of system function or reduced conservatism. l CORRECTIVE ACTION: The process control forms are originated and checked to insure accuracy. Personnel performing these functions will be retrained in the need for accuracy and independent second checks of this work. T raining will be completed by July 1,1981. l l 9PT k}}