ML20029E137
| ML20029E137 | |
| Person / Time | |
|---|---|
| Site: | LaSalle (NPF-11-A-099, NPF-11-A-99, NPF-18-A-083, NPF-18-A-83) |
| Issue date: | 05/10/1994 |
| From: | Office of Nuclear Reactor Regulation |
| To: | |
| Shared Package | |
| ML20029E138 | List: |
| References | |
| NUDOCS 9405170067 | |
| Download: ML20029E137 (2) | |
Text
-
~
o ELECTRLCALPQWER SYSTEMS LIMITING CONDITION FOR OPERATION (Continued)
- For the purposes of completing maintenance, modification, and/or technical specification surveillarce requirements, on the 0 diesel generator and its support systems during a refuel outage, as part of pre-planned maintenance, modifications, and/or the surveillance program, the requirements of action statement b are modified to:
1.
Eliminate the requirement for performing technical specification surveillance requirements 4.8.1.1.1.a on each operable AC source, immediately and once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter, when the 0 diesel generator is declared inoperable.
2.
Allow an additional 96 hours0.00111 days <br />0.0267 hours <br />1.587302e-4 weeks <br />3.6528e-5 months <br /> in excess of the 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> allowed in action statement b for the 0 diesel generator to be inoperable.
Provided that the following conditions are met:
A.
Unit 2 is in operational condition 4 or 5 or defueled prior to taking the 0 diesel generator out of service.
B.
Surveillance requirements 4.8.1.1.la and 4.8.1.1.2a.4 are successfully completed, for the offsite power sources and the 1A and 2A diesel generators, within 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> prior to removal of the O diesel generator from service.
C.
No maintenance is performed on the offsite circuits or the 1A or 2A diesel generators, while the 0 diesel generator is inoperable.
D.
Technical specification requirement 4.8.1.1.la is performed daily, while the O diesel generator is inoperable.
E.
The control circuit for the unit cross-tie circuit breakers between buses 142Y and 242Y are temporarily modified to allow the breakers j
to be closed with a diesel generator feeding the bus, while the 0 diesel generator is inoperable.
)
l The provisions of technical specification 3.0.4 are not applicable.
j LA SALLE - UNIT 1 3/4 8-l a Amendment No. 72, 99 l
9405170067 940510 PLMt ADOCK 0:K)D0373 -
p PDR-
J-ELECTRI{AL POWER SYSTEMS LIMITING CONDITION FOR OPERATION (Continued)
- For the purposes of completing maintenance, modification, and/or technical specification surveillance requirements, on the 0 diesel generator and its support systems during a refuel outage, as part of pre-planned maintenance, modifications, and/or the surveillance program, the requirements of action statement b are modified to:
1.
Eliminate the requirement for performing technical specification surveillance requirements 4.8.1.1.1.a on each operable AC source, immediately and once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter, when the 0 diesel generator is declared inoperable.
2.
Allow an additional 96 hours0.00111 days <br />0.0267 hours <br />1.587302e-4 weeks <br />3.6528e-5 months <br /> in excess of the 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> allowed in action statement b for the 0 diesel generator to be inoperable.
Provided that the following conditions are met:
A.
Unit 1 is in operational condition 4 or 5 or defueled prior to taking the 0 diesel generator out of service.
8.
Surveillance requirements 4.8.1.1.la and 4.8.1.1.2a.4 are successfully completed, for the offsite power sources and the 1A and 2A diesel generators, within 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> prior to removal of the 0 diesel generator from service.
C.
No maintenance is performed on the offsite circuits or the 1A or 2A diesel generators, while the 0 diesel generator is inoperable.
D.
Technical specification requirement 4.8.1.1.la is performed daily, while the 0 diesel generator is inoperable.
E.
The control circuit for the unit cross-tie circuit breakers between buses 142Y and 242Y are temporarily modified to allow the breakers to be closed with a diesel generator feeding the bus, while the 0 diesel generator is inoperable.
The provisions of technical specification 3.0.4 are not applicable.
LA SALLE - UNIT 2 3/4 8-1a Amendment No. 56, 83
-