Notice of Violation from Review on 910221.Violation Noted: Failure to Promptly Identify & Correct Deficiencies W/Safety Related Instrumentation Loop Scaling Documentation
ML20029A786
Person / Time
Site: Comanche Peak  Luminant icon.png
Issue date: 02/26/1991
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
To:
Shared Package
ML20029A773 List:
References
50-445-90-47, 50-446-90-47, NUDOCS 9103040254
Download: ML20029A786 (1)


Text

.

9 e

APPENDIX A NOTICE Of VIOLATION TU Electric Docket '40. 50-445/90-47 Comanche Peak Steam Electric Station. Unit 1 License No. hPF-87 During an NRC review completed on February 21, 1991, a violation or NRC requirements was identified.

In accordance with the " General Statement of Policy and Procedure for NRC Enforcement Actions," 10 CFR Part 2, Appendix C (1990),theviolationislistedbelow:

Criterion XV.; of 10 CFR Part 50, Appendix 8. " Corrective Action," statet, in part, that " measures shall be established to assure that conditions adverse to quality,-such as failures, malfunctions, deficiencies, deviations, defective material and equipment, and nonconformances, are promptly identified ano corrected."

Contrary to the above, established measures did not assure that deficiencies with safety-rel?ted instrumentation loop scaling docurrentation were promptly identified and corrected. Significant involvement from a former employee over an extended period was required before deficiencies were identified and ultimately corrected. The fonner employee initially identified design-related scaling concerns in the 1986/1987 timeframe.

These concerns fonned the basis for the documented deficiencies identifica in a letter (NE-19097) from TU Electric, Engineering, to Stone and Webster Engineering Corporation, dated May 10, 1988,

Subject:

Comanche Peak Steam Electric Station Resolution of Technical Concerns on Westinghouse 7300 Systems. As of August 1989, the scaling documentation for CPSES, Unit 1, contained hundreds of errors, omissions, discrepancies, and deficiencies.

Actions to ioentify and correct deficiencies with scaling documentation were completed in 1990.

This is a Severity Level IV violation.

(SupplementII)(445/9047-01; 446/9047-01)

Dated at Arlington, Texas, this T.6 +4 day of Fdo,vp 1991 l

9103040254 910227 P'~

ADDCK 05000445 PDR P_,,