ML20028E863

From kanterella
Jump to navigation Jump to search
Final Deficiency Rept Re Six Sheared Pinion Keys in Valve Motor Operators.Initially Reported on 820805.Pinion Keys Made of Resulfurized Carbon Steel Instead of Required Matl. Keys Replaced & List of Affected Operators Submitted
ML20028E863
Person / Time
Site: Marble Hill
Issue date: 01/18/1983
From: Shields S
PSI ENERGY, INC. A/K/A PUBLIC SERVICE CO. OF INDIANA
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
10CFR-050.55E, 10CFR-50-55E, 10CFR-50.55E, S82-19, SVP-0004-83, SVP-4-83, NUDOCS 8301280243
Download: ML20028E863 (2)


Text

..

=

  • ~

PUBLIC SERVICE.

INDIANA S. W. Shields January 18, 1983 3

Senbr Vice President.

Nucteer D' isi w

SVP-0004-83 i

j i

Mr. James G. Keppler, Docket Nos.: STN 50-546 Regional Administrator STN 50-547

?

U. S. Nuclear Regulatory Commission Construction Permit Nos.:

Region III CPPR - 170 799 Roosevelt Road CPPR - 171 Glen Ellyn, Illinois 60137 Marble llill Nuclear Generating Station - Units 1 and 2

Dear Mr. Keppler:

i l

On August 5, 1982, Mr. T. D. Geib of Public Service Company of Indiana, Inc. (PSI) notified your office of a potentially reportable item as required by 10 CFR 50.55(e).. During a field modification / inspection, Westinghouse discovered six sheared pinion keys in Limitorque Model SBO valve motor operators. The sheared pinion keys could result in the failure of the affected valves to perform their intended safety function. This operator is used on a number of valves in safety-related systems supplied by Westinghouse.

i I

Metallurgical evaluations of the sheared pinion keys have indicated that the keys were made of a resulfurized carbon steel (1100 series) in lieu of the required 1018' carbon steel material. Additionally, Limitorque has conducted i

extensive stall tests of the SB-9-25 motor operator with the 1918 pinion key material and verified the adequacy of this material for its intended use.

j As a result of the Limitorque and Westinghouse evaluations, Westinghouse will supply PSI with a list of affected motor operators and provide pinion i

keys fabricated from the required 1018 carbon steel material for replacement l

of those keys in question.

This letter is intended to fulfill the requirements of a final report as-required by 10 CFR 50.55(e).

If you have any questions regarding this matter, please contact me at your convenience.

Sincerely, 8301280243 830118

~

4 PDR ADOCK 05000546 44 a

1l S

PDR

./

S. W. Shields SWS/LGY/bak P. O. Box 190, New Washington, Indiana 47162 812. 289.1000 JAN 2123

o=

PUBUC SERVICE Letter: J. G. Keppler January 18, 1983 SVP-0004-83 cc: Director of Inspection and Enforcement U. S. Nuclear Regulatory Commission Washington, D. C.

20555 J. E. Konklin J. J. Ilarrison