ML20027D695

From kanterella
Jump to navigation Jump to search
Forwards LER 82-061/03L-0
Date released: 02/10/2020 Download: ML20027D695


LER 82-061/03L-0:on 820929,fan Damper Operator on Industrial Cooler Failed,Resulting in Reactor Bldg Average Air Temp Exceeding 130 F.Caused by Water in Instrument Air Sys Due to Personnel Failing to Close Valve FSV-250.Dampers Wired Open
ML20027D702
Person / Time
Site: Crystal River 
Issue date: 10/29/1982
From: Hughes P
FLORIDA POWER CORP.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML20027D702 (2)
Forwards LER 82-061/03L-0
ML20027D694
Person / Time
Site: Crystal River 
Issue date: 10/29/1982
From: Baynard P
FLORIDA POWER CORP.
To: OREILLY J P
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML20027D694 (1)