o OPERATING DATA REPORT DOCKET NO. 050-010
~
DATE Oct.1,1982 COnPLETED BY B. A. Schroeder TELEPHONE (815) 942-2920 OPERATING STATUS NOTES 1.
Unit Name: Dresden I 2.
Reporting Period: September, 1982 3
Licensed Thermal Power (MWt):
700 4.
Nameplate Rating (Gross MWe):
209 5
Design Electrical Rating (Net MWe): 200 6.
Maximum Dependable Capacity (Gross MWe): 205 7
Maximum Dependable Capacity (Net MWe):
197 8.
If Changes Occur in Capacity Ratings (Items 3 Through 7) Since Last Report, Give-Reasons:
N/A 9
Power Level to Which Restricted, if Any (Net MWe): N/A 10.
Reasons For Restrictions, if Any: N/A f:
'C-This Month Yr-to-Date Cumulativo.
11.
Hours in Reporting Period 12.
Number of Hours Reactor Was Critical 13 Reactor Reserve Shutdown Hours 14.
Hours Generator On-Line 15 Unit Reserve Shutdown Hours 16.
Gross Thermal Energy Generated (MWH)
[* A-y ~
~
[" -
,[1,3
-=<
17 Gross Electrical Energy Generated (MWH)
J 18.
Net Electrical Energy Generated (MWH)
VO l + ~ C A-O,N, 19 Unit Service Factor 20.
Unit Availability Factor hgg7 21.
Unit Capacity Factor (Using MDC Net)
UU[
[L 22.
Unit Capacity Factor (Using DER Net) 23 Unit Forced Outage Rate 24.
Shutdowns Scheduled Over Next 6 Months (Type, Date, and Duration of Each):
N/A 25 If Shut Down At End Of Report Period, Estimated Date of Startup: Extended Modification Outage - Shutdowr.
Until June, 1986
(
8210180100 821001 PDR ADOCK 0b000010 R
OPERATING DATA REPORT DOCKET NO. 050-237 DATE Oct.1,1982 COMPLETED BY B. A. Schroeder TELEPHONE (815) 942-2920 0PERATIN(L STATUS _.
~
NOTES 1.
Unit Name:
Dresden II 2.
Reporting Period: September, 1982 3
Licensed Thermal Power (MWt):
2,527 4.
Nameplate Rating (Gross MWe):
828 l
5 Design Electrical Rating (Net MWe): 794 l
6.
Maximum Dependable Capacity (Gross MWe):
812 7
Maximum Dependable Capacity (Net MWe):
772 8.
If Changes Occur in Capacity Ratings (items 3 Through 7) Since Last Report, Give Reasons:
N/A 9
Power Level to Which Restricted, if Any (Net MWe):
N/A
'10.
Reasons For Restrictions, if Any:
N/A This Month Yr-to-Date Cumulative.
11.
Hours in Reporting Period 720 6551 108551 12.
Number of Hours Reactor Was Critical 562.72 6101.18 84.736.58 13.'
Reactor Reserve Shutdown Hours 0
0 0
14.
HouFs Generator On-Line 538.85 6007.97 80732.45 15 Unit Reserve Shutdown Hours 0
0 0
16.
Gross Thermal Energy Generated (MWH) 1,001,864 13,501,498 162,059,659
~17 Gross Electrical Energy Generated (MWH) 31QS65 4,344,801 51,928,113 16.~
Net Electrical Energy Generated. (MWH) 289,986 4,125,719 49,002.609 19 Unit Service Factor 74.84 91.71 74.3l 20.
Uni t Availability Factor 74.84 91.71 74.37 21.
Unit Capacity Fac*.or (Using MDC Net) 52.17 81.58 58.47 22.
Unit Capacity Factor (Using DER Net) 50.73 79.32 56.85 23 Unit Forced Outage Rate 25.16 6.75 11.81 24.
Shutdowns Scheduled Cver Next 6 Months (Type, Date, and Duration of Each):
January, 1983 Refueling Outage @ 12 weeks.
25.
If Shut Down At End Of Report Period, Estimated Date of Startup:
N/A
OPERATING DATA REPORT DOCKET NO.
050-249 DATE Oct. 1, 1982 l
COMPLETED BY B. A. Schroeder TELEPHONE en3g c47_797n OPERATING STATUS
{
NOTES 1.
Unit Name:
Dresden III 2.
Reporting Period: September, 1982 3
Licensed Thermal Power (MWt):
2,527 4.
Nameplate Rating (Gross MWe):
828 5
Design Electrical Rating (Net MWe): 794 6.
Maximum Dependable Capacity (Gross MWe): 812 l
7.
Maximum Dependaele Capacity (Net MWe):
773 l
8.
If Changes Occur in Capacity Ratings (items 3 Through 7) Since Last Report, Give Reasons:
N/A 9
Power Level to Which Restricted, if Any (Net MWe):
N/A l
10.
Reasons For Restrictions, if Any:
N/A This Month Yr-to-Date Cumu.l at ive.
11.
Hours in Reporting Period
~20 6551 98,136 12.
Number of Hours Reactor Was Critical 720 3661.85 74,310.40 i
13 Reactor Reserve Shutdown Hours 0
0 0
l 14.
Hours Generator On-Line 713.43 3558./5 71,451.58
~~
l 15 Unit Reserve Shutdown Hours 0
0 0
16.
Gross Thermal Energy Generated (MWH) 1,659,404 8,072,199 141,664,188 17 Gross Electrical Energy Generated (MWH) 542,350 2,600,860 46,063,966 l
18.
Net Electrical Energy Generated.(MWH) 514,345 2,456,659 43,651,421 l
19 Unit Service Factor 99.09 54.32 72.81 1
, 20.
Unit Availability Factor 99.09 54.32 72.81 21.
Unit Capacity Factor (Using MDC Net) 92.42 48.51 57.54 22.
Unit Capacity Factor (Using DER Net) 89.97 47.23 56.02 23 Unit Forced Outage Rate 0.91 1.83 13.59 24.
Shutdowns Scheduled Over Next 6 Months (Type, Date, and Duration of Each):
N/A 25 If Shut Down At End Of Report Period, Estimated Date of Startup:
N/A l
1 AVERAGE DAILY UNIT POWER LEVEL DOCKET NO.
050-010 UNIT I DATE Oct. 1, 1982 COMPLETED BY B. A. Schroeder TELEPHONE 815-942-2920 MONTH September, 1982 DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL (MWe-Net)
(MWe-Net) 1 0
17 0
2 0
18 o
3 0
19 0
4 0
20 0
5 0
21 0
6 0
22 0
7 0
23 0
8 0
24 0
0 9
0 25 0
10 0
26 0
11 0
27 0
12 0
28 13 0
29 0
14 0
30 0
4 15 0
31 16 0
AVERAGE DAILY UNIT POWER LEVEL DOCKET NO.
050-237 UtilT II DATE Oct. 1, 1982 COMPLETED BY B. A. Schroeder TELEPHONE 815-942-2920 MONTH September, 1982 DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL (MWe-Net)
(MWe-Net)
I 295 17 532 2
233 18 568 3
340 19 659 4
353 20 540 5
368 21 570 6
342 22 602 7
620 23 568 8
636 24 122 636 0
9 25 0
10 633 26 0
11 627 27 0
12 607 28 13 622 0
29 14 611 0
30 609 15 31 559 16 i
AVERAGE DAILY UNIT POWER LEVEL DOCKET NO.
050-249 UlliT III DATE Oct. 1, 1982 COMPLETED BY B. A. Schroeder TELEPHONE 815-942-2920 MONTH September, 1982 DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL (MWe-Net)
(MWe-Net) 1 781 17 788 2
781 18 779 3
784 19 552 4
782 20 672 5
612 21 768 6
702 22 793 7
770 23 791 8
777 24 792 781 9
25 795 10 706 26 757 793 ij 258 27 12 293 28 792 791 13 645 29 798 14 747 30 I
15 771 31
~
16 776
DOCKET NO. 050-010 UNIT NAME Dresden I UNIT SHUTDOWNS AND POWER REDUCTIONS DATE Oct. 1, 1982 COMPLETED BY B. A. Schroeder TELEPHONE 815-942-2920 REPORT MONTH September, 1982 METHOD OF LICENSEE CAUSE & CORRECTIVE NO.
DATE TYPEI DURATION REA30N2 SHUTTING EVENT SYSTEM COMPONENT ACTION TO (Il0URS )
DOWN REACTOR 3 REPORT #
CODE 4 CODES PREVENT RECURRENCE 8
78-10-31 S
720 C
3 Refueling, Turbine overhaul and chemical cleaning outage.
I 2
3 4
F:
Forced Reason:
Method:
Exhibit G-Instructions for i
S:
Scheduled A-Equipment Failure (Explain) 1-Manual Preparation of Data B-Maintenance or Test 2-Manual Scram Entry Sheets for Licensee i
C-Refueling 3-Automatic Scram Event Report (
) File D-Regulatory Restriction 4-Other (Explain)
E-Operator Training & License Examination F-Administrative G-Operational Error f
II-Other (Explain) i
DOCKET NO.
050-237 UNIT NAME Dresden II UNIT SHUTDOWNS AND POWER REDUCTIONS DATE_ Oct. ]
1982 COMPLETED BY
- b. A. whroeder TELEPHONE 815-942-2920 REPORT MONTH September, 1982 METHOD OF LICENSEE CAUSE & CORRECTIVE NO.
DATE TYPEI DURATION REASOH2 SHUTTING EVENT SYSTEM COMPONENT ACTION TO (HOURS)
DOWN REACTOR 3 REPORT #
CODE 4 CODES PREVENT RECURRENCE 8
82-9-1 F
11:15 A
3 Iow water level caused by 2A RFP tripping on low oil pressure. Mechanical shaft seal failed. Repaired.
9 82-9-24 F
527:36 A
3 Main Generator output breakers tripped. Caused by short in current transformers which became water soaked frcm leak on hydrogen cooling system.
Replaced current transformers and repaired water leak.
l l
1 2
.3 4
F:
Forced Reason:
Method:
Exhibit G-Instructions for S:
Scheduled A-Equipment Failure (Explain)
'8 1-Manual Preparation of Data B-Maintenance or Test 2-Manual Scram Entry Sheets for Licensee i
C-Refueling 3-Automatic Scram Event Report (
) File D-Regulatory Restriction 4-Other (Explain)
E-Operator Training & License Examination F-Administrative j
l G-Operational Error i
H-Other (Explain)
?
DOCKET NO.
050-249 UNIT NAME Dresden 111 UNIT SHUTDOWNS AND POWER REDUCTIONS DATE Oct. 1, 1982 COMPLETED BY B. A. Schroeder TELEPHONE 815-942-2920 REPORT MONTH September, 1982 METHOD OF LICENSEE CAUSE & CORRECTIVE HO.
DATE TYPEl DURATION REASON 2 SHUTTING EVENT SYSTEM COMPONENT ACTION TO (HOURS)
DOWN REACTOR 3 REPORT #
CODE 4 CODES PREVENT RECURRENCE 5
82-9-12 E'
06:34 A
4-Rx DIC system experienced electro-remained cri-nic control problems. Repaired, tical; only turbine taken off line.
I 1
1 2
3 4
l F:
Forced Reason:
Method:
Exhibit G-Instructions for l
S:
Scheduled A-Equipment Failure (Explain) 1-Manual Preparation of Data l
B-Maintenance or Test 2-Manual Scram Entry Sheets for Licensee C-Refueling 3-Automatic Scram Event Report (
) File D-Regulatory Restriction 4-Other (Explain)
E-Operator Training & License Examination F-Administrative G-Operational Error i
H-Other (Explain)
?
DRESDEN UNIT 2 SAFETY RELATED MAINTENANCE - SEPTDIBER, 1982 s
NATURE OF LER OR OUTAGE HAL FUNCTION-CAUSE RESULT CORRECTIVE'? ACTION EQUIPMENT.
i.AllCENANCE NUMBER
^
SDV Drain Valve Preventive W.R. #22242 N/A N/A Adjusted Closed 2-302-22 limit.
IIead Seal Leak Preventive W.R. #22309 N/A N/A Adjusted Limit Off Valve' switches.
IIFCI Exhaust Preventive W.R. #18771 N/A N/A Cleaned and'lubri-Drain Pot Drain cated. Tested good.
Valvp Reinstalled.
IIead Spray Test Preventive W.R. #21612 N/A N/A Tightened down on Valve packing.
ID MSIV Preventive W.R. #20585 N/A N/A.
,Repiaced Limit switch 3A.
Drywell High Range Preventive W.R. #20255 N/A N/A Canpleted steps F5 Rad. Ibnitors and F4A-C of DIS 1600-16.
Installed Air to Preventive W.R. #20666 N/A'
.N/A TOOk a visual check
.Drywell A.O.
of valve operati.on.
Worked ok.
Operating Dept.
checked timing.
Timing was 1.44'sec.
IRM #18 Preventive W.R. #21423 N/A N/A Cleaned Range switch contacts.
Performed DIS 700-4.
[EM-16 Preventive W.R. #22032 N/A
'N/A Replaced Meter.
Checked for pr_oper operation via DIS 700-4.
_n.,
DRESDEN UNIT 2 SAFETY RELATED MAINTENANCE - SEPTEMBER, 1982 h
NATURE OF LER OR OUTAGE HALFUNCTION-CAUSE RESULT CORRECTIVEFACTION EQUIPMENT.
MAlHTENANCE NUMBER HFCI Valve AO Preventive W.R. #22279
~ N/A N/A Had Operator open 2301-31 valve and adjusted one turn down, then
~
operated two more times.
2E Electrm.atic Preventive W.R. #22314 N/A N/A Rbthreaded 3/8 nipple Relief and put old 3/8 to 1/2 reduce on and tightened all lines.
2-2301-7 Valve Preventive W.R. #21576 N/A
,N/A Removed plug and seal rings. Found Seal Ring Stem cut
'in one area, also stem cut in one area of rilug-machined plug and installed seal ring valve.
Body was ok.
. HFCI Pipe Preventive W.R. #22250 N/A N/A Found cap screws Restraint turned between.25 to 50 lbs. Torque.
Tightened to 93 lbs.
and rechecked 24 hrs, later. Still 93 lbs.
2A & SBIE Pump Preventive W.R. #20736 N/A N/A Replaced with 5 Packing rings per plunger.
3 rings lantern ring than 2 rings packing.
d t -
i
1 DRESDEN UNIT 2
.l.
SAFETY RELATED MAINTENA!1CE - SEPTDEER,1982
+
NATURE OF LER OR OUTAGE MALFUNCTION-CAUSE RESULT CORRECTIVC? ACTION EQUIPMENT.
MAlHTENANCE NUMBER 2E Electrcxnatic Preventive W.R. #21616 N/A N/A Rethread pipe nipple Relief and install new union.g, reduce and bushin Pu:rp Discharge Preventive W.R. #22317 N/A N/A Tightened attachment Line Hanger b61ts in ceiling and wall hanger to 93 ft.
lbs. Red head t
sleeves were tight.
.HPCI 2301-7 Valve PreventiveW.R.h22229 N/A
,N/A Disassemble-and in-
.spect valves.
Replace operated and l
' indicator pins. Con-dition of seat and disk *was good.
i 2D CC94 Pipe Preventive.W.R. #22103 N/A N/A Stuffing box lantern ring out of position.
~,
repositioned and packed accordingly.
1B & O.B.
Both ok.
To be adjusted when PP is run.
CRD Select Matrix Preventive W.R. #22676 N/A N/A Replaced Rod selec-tor switch for. Rod L-9.
ceu:n. 38-39 Preventive W.R. #22611 N/A-N/A Found old packing dry and brittle.
I Replaced for fresh, i
1 t
l
DRESDEN UNIT 2 SAFETY RELATED tiAINTENAllCE - SEPIDEER,1982 NATURE OF LER OR OUTAGE 14ALFUNCT10N CAUSE RESULT CORRECTIVE ACTION.
EQUIPriENT tiAINTENA!1CE NUtiBER HPCI Pipe Preventive W.R. #22248 N/A N/A Replaced missing bolt Restraint and torqued to 93 1.bs.
Checked and retorqued all other bolts.
Fuel Pool Rad Preventive W.R. #22748 N/A N/A Found Sensor Convertor Mon. A had excessive spiking.
Replaces Sens'r Conver-tor. Checked calibra-tion via DCP 2700-12.
HPCI Pipe Preventive W.R. #22249 N/A N/A 1/8" gap below pipe Restraint before torque.
Re-
. torqued to 200.ft. lbs.
Maintained 1/8" gap.
IRM #14 Preventive W.R. #22326 N/A N/A Fail'ed to respond due to the high voltage cable coming loose tran the chassing.
Reconnected cable and checked for proper res-ponse.
O
DRESDEN UNIT 3 SAFETY RELATED MANTENANCE - SEPID1BER,1982 NATURE OF LER OR OUTAGE MALFUNCTION EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION 3D LFCI Pump Preventive W.R. #17037 N/A N/A Rebuilt ptmp. Lett pump as found except for gas-kets and seal. Rearrange bearing clearance.006.
Wear ring clearance.016.
U-3 APal #3 Preventive W.R. #21664 N/A N/A Replace LPR1 card 24-25C, no stop on selector rvitch. Replaced power.
supply on 32-33B due to low voltage 47VDC.
Initiated W.R. for shorted detector 48-33D.
LPRi9 3D-23-33 Preventive W.R. #21743 N/A.
N/A By performing DIP 700-15 wiskers burned off LPR1 A node repairing the high resistance short LPal 3D-24-33 good.
Refuel Grapple Preventive W.R. #22155 N/A N/A Could not find any pro-blem. Spring ok.
U-3 UPS for ESS Preventive W.R. #22498 N/A N/A Burned-up relay.
Re-placed with "Like for Like".
U-3 APal 2 Preventive W.R. #22473 N/A N/A Performed DIS 700-5 and adjusted Setdown rod Block to 1290 and scram at 14.5%.
Also per-formed DIS 700-6, AP21
- 2. Operating ok.
f' i.
.i I-m.
DRESDEN UNIT 3 SAFETY RELATED MANTENANCE - SEPTDIBER,1982 NATURE OF LER OR OUTAGE MALFUNCTIGN EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION 903-5 Back Preventive W.R. #22525 N/A N/A Removed four wires.
Panel CRD F-12 Preventive W.R. #20206 N/A N/A Found block connection behind panel loose because new screw wasn't tight. Caused switch on Consore Panel to make and break. Repaired.
U-3 Rod Move-Preventive W.R. #20500 N/A N/A Bad contact on Rod ment Control Select Permissive Relay.
Switch Changed out 112 Relay contacts scorched and pitted.
3-302-20A and Preventive W.R. #20501 N/A N/A Rebuilt 3-302-2A and 20B 20B Valve valves.
Main Turbine Preventive W.R. #22341 N/A N/A Replaced and adjusted 03 Control Limit switch arm on Valve 10% fast acting solenoid.
Tested.
3-1601-23 Preventive W.R. #22355 N/A N/A Dropped Press switch set Valve point to allow normal valve operation at supply press. Funct. test ok<
on DIS-1600-11.
D3 CRD S/N Preventive W.R. #20335 N/A N/A Disassemble the CRD per 620C DMP 300-10 D3 CRD S/N Preventive W.R. #20334 N/A N/A Disass'trbled per DIP e
725C 300-10.
I I
I
DRESDEN UNIT 3 SAFETY RELATED MANTENANCE - SEPTDEER,1982 NATURE OF LCR OR OUTAGE MALFUNCTION EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION -
D3 CRD S/N Preventive W.R. #15493 N/A N/A Rebuilt per DMP 300-10, 62429 D3 CRD S/N Preventive W.R. #15980 N/A N/A Rebuilt per DIP 303-10.
956 D3 CRD S/N Preventive W.R. #15990 N/A N/A Rebuilt CRD per DIP 6409 300,10.
D2 CRD S/N Preventive W.R. #20333 N/A N/A Disassembled the CRD 6425 per miP 300-10.
D3 CRD S/N Preventive W.R. #15988 N/A N/A Rebuilt CRD per DMP 6356 300-10.
D3 CPD S/N 6215 Preventive W.R. #15986 N/A N/A Rebuilt CRD per DIP 300-10.
Refuel Plat-Preventive W.R. #22592 N/A N/A Replaced switch. Need torm functional check fran Fuel Handlers.
93 Diesel Preventive W.R. #22400 N/A N/A Carpleted Electrical Generator and Mechanical Inspec-tion.
Unit 3 D.C.
Preventive W.R. #15872 N/A N/A Inspected motors per Motors miP 8300-4.
ACAD/ CAM DN Preventive W.R. #20988 N/A N/A Replaced Flow trans-Inlet Flow mitter and recalibrated.
GA3-2540-15A Works good. Bad Ampli-fier board in Flow transmitter was found defective./
DRESDEN UNIT 3 SAFETY RELATED MANTENANCE - SEPIDEER,1982 NATURE OF LER OR OUTAGE MALFUNCTION EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION D3 CRD S/N Preventive W.R. #15475 N/A N/A Rebuilt CRD per EMP 755C 300-10.
3 Dg Air Inleft Preventive W.R. #21424 N/A.
N/A Found drain plug was Filter loose. Tightened up and added a little oil.
/
h I
l
DRESDEN UNIT 2/3 l
SAFETY RELATED MAINTENAtlCE - SEPITMBER,1982 NATURE OF LER OR OUTAGE MALFUNCTION-CAUSE RESULT CORRECT I VE'"ACT I ON.
EQUIPMENT MAltlTENANCE NUMBER Rx Bldg. Over-Preventive W.R. #22524 N/A N/A Performed surveillance.
head Crane as specified in work instructions. Everything checked out ok.
, 2/3 Diesel Preventive W.R. #21791 N/A N/A Completed 6 month Elec.
Generator trical and Mechanical Inspection per Procedure.
MSIV 3-Way &
Preventive W.R. #21447 N/A N/A Found grease slightly 4-Way Valve dry. Weep hold posi-tiened at 2 o' clock instead of at 6 o' clock.
Also found that the spring was weak and possibly a little short.
Quad Cities Rx Preventive W.R. #20456 N/A N/A Mounted valve on test Safety Valve stand and popped setting and proper test sheet.
Quad Citiex Rx Preventive W.R. #2'1454 N/A N/A bbunted valve cn test Safety Valve stand popped. Reset nut.to proper setting and popped per test sheet.
I Spare ASCD Preventive W.R. #21792 N/A N/A Lubricated all spare i
Solenoids for valves and returned 220-44, 220-46, to Storeroom.
l 220-47 Spare Versa Preventive W.R. #21784 N/A N/A Rebuilt valve.
Valve 2402-1031 O
h
DRESDEN UNIT 2/3 SAFETY RELATED MAINTENANCE - SEP1D"BER,1982 NATURE OF LER OR OUTAGE MALFUNCTION-CAUSE RESULT CORRECTIVE 9ACT10N EQUIPHENT.
MAINTENANCE NUMBER Soak Back Pump Preventive W.R. #21201 N/A N/A Replaced Soak Back.. Oil 2/3 Diesel Pump. Replaced coupling motor to pump.
Spare 2013 Preventive W.R. #
N/A N/A Rebuilt Traget Rock Target Rock valve according to Tech.
Valve Specification Sec 4.6.E, also 21P 200- 37.
Spare Feed Water Preventive W.R. #22065~
N/A N/A Machined O-ring groove Check Valve in bottom of seat ring and stamped.005 on one
.and.006 on the other one.
Spare Electro-Preventive W.R. #22648 N/A N/A Assembled valve as per matic Relief DMP 200-35.
N
~
l i
l
k-i i
I
SUMMARY
OF OPERATING EXPERIENCE UNIT ONE i
i September, 1982 i
i l
9-1 to 9-30 Unit One was shutdown for the entire i
I j
month, awaiting license approval for j
j the chemical cleaning. Major work i
l scheduled to be completed following i
i chemical cleaning is as follows: HPCI l
l installation for ECCS upgrading, equip-l t
i I
ment upgrade to IEEE 279, major in-
}
l i
service inspection, and refuel.
f 3
I r
h i
I l
l i
i k
l k
_. ---.. ~.. - _
l t
i 1
i SUtHARY OF OPERATING EXPERIDKE 1
UNIT 'INO l
i September,1982 i
i f
i 9-1 to 9-2 Unit 'Iko entered the month operating at a power level l
of 692 We. However, shortly thereafter the unit j-scramed due to low water level caused by 2A RFP tripping l
on low oil pressure. A shaft seal failure was to blame.
I Imediate repairs were made and the unit returned to power.
f 9-2 to 9-24 The unit operated normally with no major problems attaining l
a power level of 692 me during this period.
i 9-24 to 9-30 A minor water leak in the hydrogen cooling system caused the unit to be shutdown the remainder of the period. The j
I leaking water soaked sane of the current transformers on 1
I the main generator output leads. They shorted to ground causing the generator output breakers to trip open. The f
leak was repaired and the current transformers replaced.
(Unit back on line 10-1-82)
- 1 l
The unit attained a maximum average level of 671 m e over the entire period. A capacity factor of 51.71% and an availability of 74.84% were achieved for the month.
l
i-i j
SLM ERY OF OPERATING EXPERIENCE i
j UNIT THREE l
September, 1982 l
4 9-1 to 9-12 Unit Three entered the month operating at a power level of 821 bMe and operated continuously until an electronic pro-blem developed in the EHC system. 'Ihe generator was tempo-rarily taken off line to make repairs.
9-12 to 9-30 Some six hours later the generator was back on the grid. The unit operated the remainder of the period attaining a maxinum average level of 830 BMe. A capacity factor of 90.53% and an availability of 99.08% were achieved for the month.
]