LER 82-050/03L-0:on 820817,charging Pump Svc Water Low Pressure Alarm Sounded.Svc Water Pump 10B Auto Started But Did Not Restore Sys Pressure.Caused by Insufficient Npsh. Svc Water to Chiller Reduced & Pump Vented
ML20027B295
Person / Time
Site: Surry 
Issue date: 09/10/1982
From: Joshua Wilson
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML20027B295 (3)
LER 82-081/03L-0:on 820823,steam Flow Transmitter FT-1-495 Failed Low.Caused by Faulty Power Supply.Power Supply Replaced.Affected Instrument Channel Checked Satisfactorily & Returned to Svc
ML20027B293
Person / Time
Site: Surry 
Issue date: 09/10/1982
From: Joshua Wilson
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML20027B293 (2)
LER 82-048/03L-0:on 820813,discovered That Uncollected Leakage of 2-CH-P-1C Was in Excess of Tech Spec Limit.Two Pumps Simultaneously Inoperable,Contrary to Tech Specs.Leak Caused by Loose Flange Bolt.Bolt Lubricated
ML20027B292
Person / Time
Site: Surry 
Issue date: 09/10/1982
From: Joshua Wilson
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML20027B292 (2)
Forwards LERs 82-048/03L-0,82-081/03L-0 & 82-050/03L-0
ML20027B290
Person / Time
Site: Surry 
Issue date: 09/10/1982
From: Joshua Wilson
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To: OREILLY J P
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML20027B290 (1)