ATTACHMENT 2 PEACH BOTTOM ATOMIC POWER STATION UNITS 2 AND 3 Docket Nos. 50-277 50-278 License Nos. DPR-44 DPR-56 TECHNICAL SPECIFICATION CHANGES l

List of Attached Pages Unit 2 Unit 3 240f 240f i

l l

l l

9308260196 930820 FI PDR ADDCK 05000277 M P

PDR 13

t Unit 3 PBAPS

^

LIMITING CONDITIONS FOR OPERATION SURVEILLANCE REQUIREMENTS 3.14;A (Cont'd)

c. Hose station valve c.

Turbine Building operability and blockage d.

Circulating Water Pump check - once every 3 years.

{

Structure

d. Hose hydrostatic test at a 6.

When a hose station serving pressure at least an area which contains 50 psig greater than equipment which is required the maximum pressure to be operable becomes available at that hose inoperable; establish a station but not less j

continuous fire watch than 150 psig, or replace equipped with portable with and appropriately

+

fire suppression equip-tested hose. Testing ment within I hour frequency shall be annually and provide equivalent for hose stored outside, and protection to the area every 3 years for interior served by the inoperable hoses.

station from the operable hose station within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> 6.

None f

l 7.

Except as specified in 7.

The SGTS fire suppression 3.14.A.8 below, the spray system testing fire suppression spray system shall be performed as follows:

serving a Standby Gas Treatment System charcoal filter train

a. Manual activation test 'every shall be operable when a train is 18 months.

required to be operable.

b. Inspection of nozzles 8.

If the requirements of 3.14.A.7 and spray header-i cannot be met, once every 18 months l

l

a. establish a fire watch patrol
c. Header and nozzle air to inspect the area with flow test - once every inoperable fire suppression 3 years l

equipment at least once per shift.

b. restore the system to an i

operable status within 14 1

days, or in lieu of any other report required by l

Specification 6.9.2 submit a l

Special Report to the l

Commission pursuant to Specification 6.9.3 within 31 days outlining the cause of the malfunction and the plans for restoring the system to an operable status. The SGTS may be considered operable for the purposes of Specification 3.7.B.

i l

-240 f-j

Unit 2 PBAPS LIMITING CONDITIONS FOR OPERATION SURVEILLANCE REQUIREMENTS 3.14:A (Cont'd)

c. Hose station valve c.

Turbine Building operability and blockage d.

Circulating Water Pump check - once every 3 years.

Structure

d. Hose hydrostatic test at a 6.

When a hose station serving pressure at least an area which contains 50 psig greater than equipment which is required the maximum pressure i

to be operable becomes available at that hose inoperable; establish a station but not less continuous fire watch than 150 psig, or replace equipped with portable with and appropriately fire suppression equip-tested hose. Testing i

ment within I hour frequency shall be annually and provide equivalent for hose stored outside, and protection to the area every 3 years for interior served by the inoperable hoses.

station from the operable hose station within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> 6.

None 7.

Except as specified in 7.

The SGTS fire suppression 3

3.14. A.8 below, the spray system testing fire suppression spray system shall be performed as follows:

l serving a Standby Gas Treatment l

System charcoal filter train

a. Manual activation test every shall be operable when a train is 18 months.

l required to be operable.

l

b. Inspection of nozzles l

8.

If the requirements of 3.14.A.7 and spray header-cannot be met, once every 18 months l

a. establish a fire watch patrol
c. Header and nozzle air to inspect the area with flow test - once every inoperable fire suppression 3 years l

equipment at least once per shift.

b. restore the system to an operable status within 14 days, or in lieu of any other report required by l

Specification 6.9.2 submit a Special Report to the Commission pursuant to i

Specification 6.9.3 within 31 days outlining the cause of the malfunction and the plans for restoring the system to an operable status. The SGTS may be considered operable for I

the purposes of Specification l

3.7.B.