ML20024G315

From kanterella
Jump to navigation Jump to search
Ack Receipt of 711210 Telegram Re Three Main Steam Relief Valves Ejecting from Headers During Hot Functional Test of Sys.Informs That Headers of This Kind Not Installed in Plant
ML20024G315
Person / Time
Site: Monticello 
Issue date: 12/17/1971
From: Wachter L
NORTHERN STATES POWER CO.
To: Grier B
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
Shared Package
ML20024G313 List:
References
NUDOCS 9102110285
Download: ML20024G315 (1)


Text

-=

NORTHERN STATES POWER COMPANY MIN N E A f*O Lle. MIN N E S OTA 58401 December 17, 1971 Boyce H Grier, Regional Director Region III Compliance Office United States Atomic Energy Commission 799 Roosevelt Road Glen Ellyn, Illinois 60137 Dear Mr. Grier MONTICELLO NUCLEAR GENERATING PLANT DOCrJIT NO. 50-263 LICENSE NO. DPR-22 In your telegram of. December 10, 1971, you transmitted information from another nuclear power facility describing the ciretastance in which three main steam relief valves were ejected from their headers during a hot functional test of that system. You requested that we provide you within ten days in writing as to whether-headers as described are installed in the steam lines of our facility. The following description of the head-ers was given.

"The failed header assemblies each consist of two valves mounted vertically in a dead end, 12-inch diameter pipe projecting 90 degree horizontal angle from the main steam line. The two head-ers are mounted at 180 degrees to each other on the opposite sides of the main steam line. The headers were designed to meet Section 1 of the ASME Code by the Bechtel Corporation."

Headers as described above are not installed at the Monticello Nuclear

[

Generating Plant. Each of the four main steam lines have their respec-tivesafetyvalveandsafr',y/reliefvalveattacheddirectlytothe18 o

inch, schedule 80 steam..no as opposed to being located on a dead end header described above. Our piping was designed by the Bechtel Corpora-l tion to meet Class I criteria for nuclear power plants.

Yours very truly, Yeh4>

LJ achter, Vice President Power Production and System Operation LJ/l/br ces R 0 Duncanson C E Larson DEC 2119A 9102110295 720117 DR p

ADOCK 05000263 PDR

.