I; I

APPENDIX A NOTICE OF VIOLATION l

Mr. William F. Boeruue License No. SOP-2076-1 Docket No.

55-3438 File with Docket No. 50-263

' Based on the results of an NRC inspection conducted on February 25 and March 17 and 18,1977, it appears that one of your activities was not conducted in full compliance with conditions of your Senior Operator's License as indicated below:

This is an infrac-tion.

l I

Senior Operator License No. SOP-2076-1 states in part that, "In directing the licensed activities of licensed operators and in manipulating the controls of the.

facility.

the licensee i

should observe the operating proced' ires and other conditions specified in the f acility lisence or authorization which authorizes operation of the facility.

." Appendix A to Provisional Operating l

License No. DPR-22, Technical Specification Section 6.5. A.1 requires l

that system procedures fcr startup, operation, and shutdown of the reactor be followed.

Operating Procedure C.1, Startup, in Part B, I

Step 3, and referenced Part A, Section 2. Step 4.c, requires that you "ohserve the period meter and govern control rod withdrawal to i

f L

avoid a reactor period shorter than 30 seconds."

L r

l-Contrary to the above, on February 23, 1977, following the receipt l

of a thort reactor period, you directed and supervised withdrawal i.

of the same control 20d that resulted in the short period over the same notch positions.

After again receiving an indicated fast period, you again directed and supervised withdrawal of a symmetric c ontrol rod, knowing that the reactor response should be similar.

This action resulted in another f ast period and subsequent reactor scram.

i

/

l HOCK 05000263 549 770616 0