KANSAS GAS AND ELECTRIC COMPANY TW ELECTE COMPANY GLENN L MOESTER vect passects?. NucLaan August 1, 1983 Mr. W.C. Seidle, Chief Reactor Projects Branch 2 S
u ear Regulatory Commission h
611 Ryan Plaza Drive, Suite 1000 I
I h "l
M - 3l983
/ff/
Arlington, Texas 760
,,!j KMLNRC 83-101 Re:
Docket No. STN 50-482
~~~
J Ref: 1) Interim Report KMLNRC 82-221 dated 7/14/82 from GLKoester, KG&E, to WCSeidle, NRC
- 2) Interim Report KMLNRC 82-248 dated 10/25/82 from GLKoester, KG&E, to WCSeidle, NRC
- 3) Interim Report KMLNRC 83-014 dated 2/4/83 from GLKoester, KG&E, to WCSeidle, NRC
- 4) Interim Report KMLNRC 83-067 dated 6/6/83 fro:n GLKoester, KG&E, to WCSeidle, NRC Subj: Withdrawal of Potential 10CFR50.55(e) Report -
Diesel Generator Bolt Torque t
Dear Mr. Seidle:
This letter withdraws the potential 10CFR50.55(e) item concerning loose l
stud / nut combinations in the diesel generators at Wolf Creek Generating S ta tion. This matter was initially reported by Kansas Gas and Electric Company (KG&E) on June 14, 1982, and additional information was provided in References 1), 2), 3) and 4).
As stated in Reference 4), some of the stud-nut combinations in question were found to be slightly under torqued and have subsequently been reworked to meet the manufacturers specified torque values. The "as found" condition was documented during the rework and sent to the manufacturer for evaluation of safety implications. The manufacturer has completed his evaluation and has determined that the stud / nut combinations were sufficiently tight and would not have come loose during operation.
KG&E has concluded that the safety of operations would not have been adversely affected had the stud / nut combinations not been reworked and that this matter is not reportable pursuant to 10CFR50.55(e).
If you have any questions concerning this subject, please contact me or 8308090007 g30801
~
DR ADOCK 05000482 1 E O~/ j g
PDR s
201 N. Market -Wichita, Kansas - Mail Address: PO. Box 208 I Wichita, Kansas 67201 - Telephone: Area Code (316) 261-6451
5 Mr. W.C. Seidle
- KMLNRC 83-101-- August 1, 1983 1
- Mr. Otto Maynard of my staff.
Yours very truly, GLENN L. KOESTER Vice President - Nuclear i