Gilbert / Commonwealth engineers and consuitants GILBERT ASSOCIATES, INC., P. O. Box 1498, Reading. PA 19603/Tel 215-775-2600/ Cable Gilasoc/ Telex 836-431 July 27, 1983 W.F. SAILER General Manager Quality Assurance Division.
United States Nuclear Regulatory Commission Office of Inspection and Enforcement Washington, DC 20555 Attention:
Mr. R. C. DeYoung Re: Reportable Event Diesel Generator Exhaust Piping
Dear Mr. DeYoung:
This documents my telephone report under the provisions of 10CFR21 to Mr. R. Baer on July 27, 1983, at approximately 2:00 p.m.
Individual Who Reported Mr. William F. Sailer, General Manager, Quality Assurance Division - Gilbert Associates.
Facility Involved Perry Nuclear Power Plant Units 1 and 2 under construction by the Cleveland Electric Illuminating Company.
Activity / Component Involved' Design of the Standby and HPCS Diesel Generators.
Nature of the Defect The exhaust piping, as designed, would create back pressure in excess of the manufacturers maximum allowable.
If the emergency diesel generators are loaded beyond 75 percent of the 7,000 KW rating, diesel exhaust pressure will exceed 12 inches W.G.
This back pressure will cause rapid decrease in engine performance, to the point where the engine will stall at 16 inches W.G.
This could prevent the diesels from performing their safety function.
f'308030208 830727 '
{DRADOCK 05000440 g[/p PDR
- Pnncee, 525 Lancaster Avenue. Readmg. PA/ Morgantown Road. Green Hdts. Readmg. PA 215 M2600 209 East washmgton Avenue. Jackson. MI 517 753000/0ne Exchange Place, suite 1003. Jersey City, NJ 201451-5220
Mr. R. C. DeYoung Page 2 July 27, 1983 Date Information Obtained The.QAD General Manager was informed on July 25, 1983, of the reportability of this item.
Corrective Action Gilbert / Commonwealth is currently investigating several alternative remedics to. resolve this problem. We have determined that the problem is' limited to the Perry Plant.
The corrective action will be completed prior to final testing of the system.
If you require any further information, please contact me at (215)775-2600, Extension 7543.
Very truly yours,
.f W. F. Sailer General Manager Quality Assurance Division WFS:kb' cc:
H. Lorenz T. M. Demers