Text

r Y

.m.,

lt.-]

Gpu 2903

Y

/

B ADCOCK & WILCOX Powlt GENER ATION DivtSIO N NUCLEAR Powls GENER ATIOw DtPaafatNT 1

SPECIFICitiiON

(

4=.a /mvo cs_,_2O

$tt! AL/JOS/0 Af t FOR ELECIRICALLY ACiUATED RELIEF VALVES FOR REACTC3 COOL,LT SYSTEl4 SERVICE CONTRACT !!0.

690 0006 CUSTOMER msn enL men & LIGnT CO.

PLAlli T:51EE !?ILE ISTida STATICN - UNI? NO. 2 i

8307080152 700107 PDR ADOCK 05000289 A

HOL PREPACED BY 27 N.a?

DATE

/- /' -7< '

ft

~

\\

REVIEr!ED CY

/3 r - '~'Si':*U'A l'

D ATE _l,/.1.4/75_

A t

-T APP 00VID BY

'z' DATE./A.J_Zo B2'857 n

/

,/;

~_,e~c.

i/,.,<

D/.TO

- Armovi.11 Irt -

.;.~

j TABLE OF CC;TE"rS Sectien fio.

Title Page

1. 0 Scope of the Specification 1
2. 0 Reference Documents 1

3.0 Oeneral Regaire=ents 1

4.0 Material Reg 2irc~ents 1

5. 0 Inspection Require =ents 2
6. 0 Testing Requirc=ents 2
7. 0 Asse=bly, Cleaning, Packaging, and Shipping 2

Requirements 8.0 Proposal Data Required 3

9.0 Contract Data Required 3

Appendix A 4

Appendix B 5

B2J858 f

l 153CC Dr.TE: 1-7-70 PAGE i SERIAL CS-3-79/I*S0-6 P. o.h e o c': *

"':!-n-

l TECM*ICAL OFECIFIN"ICUS PCR ELECI'RICALLY ACTUATO RELIEF VAL'.?3 1.0 SCOPE OF T!!E SPECITICATIC'!

This specificatien delincates the requirc=cnts of electrically actuated Pilot Operated relief valves and covers the Parniching and delivel/ of such valves that are described in detail en the Equipment Specification Shect:.

l I

2. O RESEICE DCC'J'CITS 2.1 The valves are to be designed, fabricated, in=pceted and tested in accordance with the applicabic secticn of the codes and standard listed in Appendin A, as well as with the special requirement: Otated 3

in succeedinC sections of this specification.

5i

[

3.0 C'2!ERAL RE? METS 31 All valvec shall be r.anufacturer's standard, or better, for service condition: stated en the attached data sheet.

I

3. 2 De:ica of valves and their appurten:nces shall include the sciamic forces in accordenec nith Clan: I requirement: of CS-5-107.

3.3 The valves shall be flanced and the flange :pecificaticn: deceribed in the code (USAS 316.5) shall be folloucd. FlanCc facing will be specified in the centract stace.

3.4 The valves shan Le furnidhed with the necessary accescories required for catisfactcry operation in respon o to a remote electrical signal.

3.5 Discharce of calve: to have drain previsions to avoid concetien or condensate.

3.6 The valve shall not act on ic of electrical pcuer and chall fail closed on 1000 of air, f

t.

4. O !nTE?.TAL REC'JIEE'C-"S I

Y

4.1 Stainles

stec1, au:tenitic trpe 304 or 316 or equivalent chall bc l

used for the vetted surfaces of the valve:. thtcrial: chall. meet appropriate ASTM specifications or other recognized indu. trial standard:.

4. 2 The Vendor chall propose trin material: (stem, no: le, neat, and dich) meeting the requirc.ent: of the service and which vill be free non Calling, corrc icn, and frec:ing.

B2,Ms59 l

5' E DATE
1-7 *iO PAGE 1 SE!!!Al. CO-3-79/I:na-6 l,

J I

e n b c - a. e m....

m-_-

--n.--

_-u.

-.~.----- ---

e>

'o i

5.0 E SPECTION REQUntE C.*.'S The appended valve data chects give a classification for each item.

5.1 The inspection require =ents for each cla :ificatien are as follous:

Cla:s I Each item classified as Cla:s I sha1 =eet the requirements of Section A of AS'S Code for Pu.:ps and Valves for nuclear i

Power.

Class II Each item classified as Class II shall meet the require =ents of Section 3 of AS E Code for Pu=ps & Valves for Uuclear Power.

I Class III Each iten classified as Class III shall meet the require =ents of Section C of ASIE Code for Pu=p: &' Valves for Nuclear Power.

(

o 6.0 TESTI:G RECUIRE'CCS 6.1 All valves chall be given hydrostatic shell pressure tests as required in the latest edition of the ccde' (USAS D16.5). Valves shan shou no icakage or per=anent deformation at ar./ point.

6. 2 D-%cralized water chall be used as the hydrotest media. The chloride content of this water : hall not exceed 1 ppm.

6.3 All valve: chall be given cet pressure test:. Eac~t valve shall lift three successive ti=ce within ! 1% of the set pressure. The valve shall exhibit blewdorn within 2% of the nxi=um set pre: ure at cach lift. The valve shall be permitted to cool at least five minute:

between cach lift. The v.lve shall resent after each lift and l

leahace sball not exceed 2 cc of saturated tea = per hour per inch of seat dia acter mea:ured at not les than 907, of set pressure. The valves shall be dried and ccaled following this test.

i

6. l+

Disassembly of the valves after the seal test and/or relief pres:ure l

setting chall be cause for retest.

t 7.0 ASSEM?LY, CLTJREC. PACTAGE G, AUD SHIPPE!G RIT.UICECS 7.1 Markinc of valves sh"11 be in accordance with etandards require =ents of ISS SP-25,

7. 2 Cleanlince: Requirements of the valves chall be in accordance with reference =pecification 1.1, Appendix A.

B23860

[

i-PAGE 2 SERIAL CC-3-79/UCS-6

SUE GUE
1-7 7o i

Bobcock & V/ilcox

- ~ -

. _... - -.. - ~ ~.

-..... ~.....

.r

=.

e i

8.0 PROPCGAL Df.TA REOUIRED 8.1 Vendor shall speciD/ the trim natorials as stipulated in Paragraph 4.2 above.

8. 2 Vendor shall describe the valve test stand and testing procedure to be used to accc=plish testing described in Section 6.0 above.

8.3 Vendor shall describe the flange to be supplied and shall reco=end suitpble caskets for the service.

9. 0 CCUTRAC:' DATA REOUIRED 9.1 Prior to release of the Vendor for ship =cnt, the Vendor shall notiff BE in adequate time of dates of the testing required by Section 6.

In addition, certified test results shall be submitted for approval.

I f

h B20861 UE DATE: 1-7-70 PAGE 3 SEP.lAI. cS-3-79/ICS-6 Gabcock t. Wilcox

.r B ABCOCK & ill L CO X power GENERXTION DivtSICN t

NUCLEAR POWER GENERATION DEPARTMENT APP ENDI X A

SPECIFiCATIO!! HO. m ' w h'ts r, C ON T R A C T N O. 620.c006 scRineissi.c natt i

i REFERCICE D00U:0 TS FOR ELECTRIC /J.TX ACTUATED.RELIE7 VALVES 1.0 REFERE'CE B7..' SPECIFICATICI'S ISSUE D/CE 1.1 BW Specification no. CS-5-95,' " General Specificatica i

for Cleanlines: of Nuclear Reacter Systc== and l

Cc=ponents" 5/29/69 j

1. 2 BMI Specification No. CS-5-95/USS-6 2/W/69 s'

1.3 BW Specification No. CS-3-106/rSS-6, " General l

Technical Specificatica for All Cc=ponents Used in

~

Auxiliary Fluid Systc=="

12/17/69

  • 1.14 l

BW Specification No.1132/0369, "nucicar quality 3/19/69 Program Requirements Specification" 1.5 BSI Specification no. CS-5-107, " Standard Specifica-l tion for Seismic Design Basis for Auxiliary Equipment" 6/14/68 l

1.6 B W Specification 70 CS-5-107/nSS-6 2/n/69

2. 0 RETERE!CE II'DUSTRY STidID.'iRDS 2.1 ASIE Code for Pu=ps and Valves for Nuclear Ibwer Nov. 1968--
2. 2 USA Stand.a.trd, B16.5, " Steel Pipe Flanges and Flanced 1961 Fittings" i

1 2.3 M2nufacturer's Standardization Society of the Valves 1964 and Fittin;; Inductry, Standard Practice SP-25 Itrking

(

of Valves

{

t I.

I i

P 1

i B20862

?

Of.TE ' 7 vn P3EP'O GY #'

' ' " S-W[

APPV'O DY l

Page L of e INDICAILS 8t C V I S 10fa f ROM PREVIOUS IS5uc

's A INDe C Af f $ Dil.ffs0N f if 0M PRLVIOUS IS$ut n.

~.

=

.~

.P

.a BABC0CX & WILC0X

~

1 POWER GENERATION DIVISION NUCLEAR POWER GENERATION DEPARTMENT l

APP ENDI X n

l S P E C I F 1 C A T I O!! NO.cn 1 vohinS /5 CONTRACT NO. 620-ON6 stoiau issuc part l

VATNE T/3JTATICII SHEET Iten:

Electromatic Relief Valve Mark 17o.:

Quantity:

Design Conditions:

2500 PSIG 670 F

Si::c:

2 1/2" x 4" Inlet Flance 2 1/2" 2500 lb.

Out'let Flant e h" 600 lb.

i ASA R.F.

ASA R.F.

}

Service Conditions:

a)

Fluid Saturated Steam

+ 10%

b)

Capacity 115,000 lbs/hr - O $

c)

Sct Pressure 2300 lbs.

d)

Variable Eack Pre::sure 700 lbs.

e)

Constant Back Pressure 700 lbs.

1#

f)

Set Pressure Tolcrance Applicable Code: AS!E Pu:o & Valve Code Class I Cleanline::s Class 3

per Flid Spec. CS-5-95 dtd. 5-29-69 Scismic Class I

per BTR Spec. CS-5-lO7 dtd. 6-14-68 Control Signal: 125 V.D. C.

Supplementary Infor: atica Essentiality Level I

per1132/0369 B20863

.l

'w ' !'-

- [ M' '

APPV'O DY D A T E ~ 3 73 PREP'D CY

/

, smotCAff$ R(vlS40N FRou Pulvt0US ISSUE 3CI b = 0!

4 I

A sNnicatts onartins rnou Purvicus issur

,c

,