Y NIAGARA NUMOHAWK NMP-6777 NIAGARA MOHAWK POWER CORPORATION /300 ERIE BOULEVARD WEST. SYRACUSE. N Y.13202/ TELEPHONE (315) 474-1511 June 14, 1983 Richard C. DeYoung, Director United States Naciear Regulatory Commission Region 1 631 Park Avenue King of Prussia, Pennsylvania 19406 RE: Docket Nc. 50-220 TE Buttetin No. 83-03 Dear Mt. DeVoung inspection and Enforcement Bulletin No. 83-03 concerns check value failures in raw attter cooling systems of diesel generators. At Nine Mile Point Un<i.t M1 there are two emergency diesel generators, #102 and W103 each having two Chapman-Crane 4 inch stcing check valves, no. 72-69,,

67 and 72-68, 6S respectively. Check values 72-69 and 68 are downstream of each pump. Check valves 72-67 and 66 are downstream of the diesel generators. Check valves 12-68 and 69 were dhassembled, inspeeted, then reassembled after finding both valves, including internals, in satisfactory physical and operating condition. The integrity of the valves 72-66 and 67 tais proven during a fomoard and reverse flow test. These values teilt be tested fortatrd and reverse on a quarterly basis during surveillance tests. Dbassembly and inspection of valves 72-68 and 69 taitt be performed once cach refueting outage.

The IST ptogram and procedures tcitt be revhed by November 1983 to incorporate the testing and dhassembly as pteviously stated.

There is no history af partial or total disassembty of valve internah and no history of fallure.

Very truly yours, Lc*m M n,.

Thomas E. Lempges Vice President Nuclear Generation jm hSO DO OO O

Efl

l UNITED STATES OF AMERICA NUCLEAR REGULATORY COMMISSION In the Matter of

)

)

Niagara Mohawk Power Corporation

)

Docket No. 50-220

)

(Nine Mile Point Unit #1)

)

AFFIDAVIT T.

E.

Lempges, being duly sworn, states that he is Vice President of Niagara Mohawk Power Corporation; that he is authorized on the part of said Corporation to sign and file with the Nuclear Regulatory Commission the documents attached hereto; and that all such documents are true and correct to the best of his knowledge, information and belief.

4nn a2 i,,ys -:2

/

//

Subscribed and sworn to before me, a N tmry Puplic in and for the State of New Yoqk and County of C am/<ru this

&_ Ilt day of

( /,p, :, f 1983.

g' 9

'a

'$? /l 44 Notafy Public in and for 4tm_ /su County, New York My Commission expires:

. /2 :l f Vl5 Mo. /97f