APPENDIX __A_
NOTICE OF VIOLATION Duquesne Light Company Docket No. 50-334 Beaver Valley Unit 1 License No. DPR-66 As a result of the inspection conducted on April 5 - May 2,1983, and in accordance with the NRC Enforcement Policy (10 CFR 2, Appendix C) published in the Federal Register on March 9, 1982 (47 FR 9987), the following violation was identified:
Technical Specification Surveillance Requirement 4.5.2.b, Emergency Core Cool-ing Systems, requires that each testable power operated valve in the flow path be fully cycled at least once per 31 days to demonstrate operability.
Contrary to the above, as of April 22,1983,MOV-SI862AandB(thelowhead safety injection pump suction valves from the Refueling Water Storage Tank),
which are testable power operated valves in an Emergency Core Cooling System flow path, were not being cycled on a 31 day frequency to demonstrate opera-bility.
This is a Severity Level IV Violation (Supplement I).
Pursuant to the provisions of 10 CFR 2.201, Duquesne Light Company is hereby re-quired to submit to this office within 30 days of the date of the letter transmit-ting this Notice, a written statement or explanation in reply, including for each violation:
(1) the corrective steps which have been taken and the results achieved; (2) the corrective steps which will be taken to avoid further violations; and (3) the date when full compliance will be achieved. Where good cause is shown, consi-deration will be given to extending the response time.
1 8306060204 830523 PDR ADOCK 05000334 G
= >I d.........
DATE) nac ronu ais go80(NRCM O240 OFFICIAL RECORD COPY