Informs of Status of NUREG-0737,Item II.F.1.3 Re Containment high-range Radiation Monitors.Qualified in-containment Electrical Terminations Will Be Made Per IE Bulletin 79-01B & NUREG-0588 Schedule
ML20023D114
Person / Time
Site: North Anna 
Issue date: 05/12/1983
From: Stewart W
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To: Clark R, Harold Denton
Office of Nuclear Reactor Regulation
References
RTR-NUREG-0588, RTR-NUREG-0737, TASK-2.F.1, TASK-TM 145A, IEB-79-01B, NUDOCS 8305190253
Download: ML20023D114 (1)


Text

VInOINIA ELECTRIC AND PowEn COMPANY RIcnwoxn, VIRGINIA 20261 W.L.SvawAar Vice Pamesomwr wecs.... oramano,.

May 12, 1983 Mr. Harold R. Denton, Director Serial No. 145A Office of Nuclear Reactor Regulation N0/JHL:acm Attn:

Mr. Robert A. Clark, Chief Docket No. 50-339 Operating Reactors Branch No. 3 License No. NPF-7

. Division of Licensing U. S. Nuclear Regulatory Commission Washington, D. C. 20555 Gentlemen:

VIRGINIA ELECTRIC AND POWER COMPANY-NORTH ANNA POWER STATION UNIT NO. 2 STATUS OF THE CONTAINMENT HIGH RANGE RADIATION MONITORS This letter is to inform your Staff of the status of the North Anna Unit 2 Containment High Range Radiation Monitors.

The Containment High Range Radiation Monitors have been' installed and tested. On May 6, 1983, Victoreen, the vendor of the system, calibrated the North Anna Unit 2 Containment High Range Radiation Monitors using their prototype calibration source.

These monitors were in-situ calibrated by electronic signal substitution for all rance decades above 10 R/hr.

In-situ calibration by means of a calibrated radiation source was performed - at 10 R/hr.

The results of the in-situ calibration were satisfactory.

The in-containment electrical terminations for the Containment High Range Radiation Monitors are not qualified.

The current in-containment electrical terminations have been made using a temporary termination procedure.

. Qualified terminations will be made in accordance with the schedule of IEB 79-01B and NUREG-0588 as indicated in Revision 3 to Vepco's NUREG-0737 response.

Vepco has satisfied North Anna Unit 2 License Condition 2.C(21)(1)(iv) and NUREG-0737, Item II.F.1.3, except for the environmental qualification portion of the system.

Very truly yours, W. L St wa cc:

Mr. James P. O'Reilly

[

Regional Administrator Region II Mr. M. B. Shymlock NRC Resident Inspector l

North Anna Power Station i