Proposed Tech Specs Adding Word Specified & Replacing Pages 3-0a to 900124 Application for Amend
ML20012F145
Person / Time
Site: Fort Calhoun 
Issue date: 03/29/1990
From:
OMAHA PUBLIC POWER DISTRICT
To:
Shared Package
ML20012F140 List:
References
NUDOCS 9004100214
Download: ML20012F145 (2)


Text

4 k

i s

1 i.

i l

ATTACHMENT A j

i l

1 I

I l

l r

i 9004100214 900329ADOCV 05000285 FAR PDC P

O 3.0 SURVEILLANCE RE0VIREMENTS 3.0.1.

[ach surveillance requirement shall be performed within the specified surveillance interval with a maximum allowable extension not to exceed 25 percent of the specified surveillance interval.

3.0.2 The surveillance intervals are defined as follows:

Notation lillt f_ttagtEy S

Shift At least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> D

Daily At least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> W

Weekly At least once per 7 days BW Biwtekly At least once per 14 days M

Monthly At least once per 31 days 0

Quarter 1/

At least once per 92 days SA Semiannual At least once per 184 days A

Annually At lear once per 366 days R

Refueling At lea n v,1ce per plant operating cycle P

Startup Prior to Reactor Startup, if not completed in the previous week.

Exception to these intervals are stated in the individual Specifications.

3.0.3 The provisions of Specifications 3.0.1 and 3.0.2 are applicable to all codes and standards referenced within the Technical Specifications.

The requirements of the Technical Specifications shall have precedence over the requirements of the codes and standards referenced within the Technical Specifications.

3.0.4 Failure to perform a Surveillance Requirement within the allowed surveillance interval, defin.;.t by Specifications 3.0.1 and 3.0.2. shall constitute noncompliance witi, the OPERABILITY requirements for the corresponding Limiting Condition for Operation.

The time limits of the i

ACTION requirements are applicable at the time it is identified that a l

Surveillance Requirement has not been performed.

The ACTION requirements may be delayed for up to 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> to permit the completion i

of the surveillance when the allowable outage time limits of the ACTION requirements are less than 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

Surveillance Requirements do not have to be performed on inoperable equipment.

i l

l 3 0a Arrendment No. JJJ