esuun SACAAM8NTO MUNICIPAL UTILITY DISTRICT C 6201 S Street. P.O. Box 16830 Secremento CA 95862 1830.1916) 452 3211 AN ELECTRIC SYSTEM SERVING THE HEART OF CALIFORNIA AGM/NUC 90-086 March 8, 1990 U. S. Nuclear Regulatory Commission Attn:
J. B. Martin, Regional Administrator Region V d
6 u
e f
Docket No. 50-312 Rancho % Nuclear Generating Station License No. DPR-54 SPECIAL REPORT 90-05:
FIRE BARRIERS BREACHED MORE THAN 7 DAYS
Dear Mr. Martin:
Twenty-nine fire barrier penetrations were breached during February and not restored to operable status within the 7 days required by the Rancho Seco Technical Specifications.
The Sacramento Municipal Utility District hereby submits Special Report 90-05 in accordance with Technical Specification 3.14.6.2.
Nineteen fire barrier penetrations have been returned to operable status.
Compensatory measures will remain in place for the remaining fire barrier penetrations until they are returned to operable status as required by l
Technical Specification 3.14.6.2.
l Members of'your staff with questions requiring additional information or I
clarification may contact Ed Bennett at (209) 333-2935, extension 4648.
Sincerely, L
Dan R. Keuter i
Assistant General Manager j
Nuclear 1
cc w/atch:
A. D'Angelo NRC, Rancho Seco i
l Document Control Desk, Washington DC f.
2 g
RANCHO SECO NUCLEAR GENERATING STATloN O 1444o Twin Cities Road Herald, CA 95638 9799;(209) 333 2935
~
ATTACHMENT SPECIAL REPORT NUMBER 90-05
- ~
Fire Barriers Breached More Than 7 Days i
Date of Occurrence See Tables 1 and 2.
Plant Condittons at Time of Occurrence The plant is in a defueled condition.
Identification of Occurrence The fire barrier penetrations in the Auxiliary Building listed in Tables 1 and 2 were not restored to operable status within the 7 days required by Rancho Seco Technical Specification 3.14.6.2.
i Description of Occurrence The penetrations listed in Table 1 failed. surveillance test SP.0714. Refueling Interval Fire Barrier Penetrations (Auxiliary Building and Turbine Building, Turbine Deck Level) due to seal degradation.
The penetrations listed in Table 2 failed surveillance test SP.0712, Refueling Interval Fire Barrier Penetrations (Auxiliary Building, Ground Floor Level and Turbine Building-O'-0" Elev) due to seal degradation.
Corrective Action Taken i
Operability of fire detectors was verified on at least one side of the breached barriers and hourly fire watches established in accordance with Technical Specification 3.14.6.2.
Nineteen penetrations have been returned to operable status as noted in Tables 1 and 2.
Hourly fire watches will continue as required until the remaining penetrations are returned to operable status.
4 a
L P
e
i P
TABLE 1
)
Fire Barriers In The Auxiliary Building That Failed SP.0714 I
5 Date Returned Date of Penetration Operable Occurrence Penetration
_ Elevation E11]gg Statut 2/8/90 1-17Al 40'-0" 2/1/90 2/13/90 2/9/90 1-17BZ 40'-0 2/2/90 2/13/90 l
2/9/90 1-17A0 40'-0 2/2/90 2/13/90 i
2/9/90 1-17AR 40'-0 2/2/90 2/13/90 2/9/90 1-17AS 40'-0 2/2/90 2/13/90 2/9/90 1-17BC 40'-0 2/2/90 2/13/90 2/9/90 1-17AH 40'-0 2/2/90 2/9/90 1-17BX 40'-0 2/2/90 2/13/90 2/9/90 1-17CA 40'-0 2/2/90 2/13/90 2/13/90 1-17AM 40'-0 2/6/90 2/13/90 2/13/90 1-17AI 40'-0 2/6/90 2/13/90 2/13/90 No ID 2/6/90 2/16/90 2-14AC 12' 2/9/90 2/16/90 No ID 2/9/90 2/16/90 No ID 2/9/90 TABLE 2 Fire Barriers In The Auxiliary Building That Failed SP.0712 Returned Date of Penetration Operable Occurrence Penetration Elevation Failed Status 2/19/90 18-31AH O'-0" 2/12/90 2/23/90 2/19/90 18-31AG O'-0" 2/12/90 2/23/90 2/20/90 32-33AA 13'-6" 2/13/90 2/28/90 2/20/90 33-36AB 13'-6" 2/13/90 2/26/90 2/20/90 34-36AA 13'-6" 2/13/90 2/23/90 2/21/90 32-36AA 17'-0" 2/14/90 2/26/90
~
2/21/90 34-36AF 17'-6" 2/14/90 2/23/90 2/21/90 34-36AB 16'-0" 2/14/90 2/23/90 2/21/90 34-36AD 17'-3" 2/14/90 2/22/90 34-36AH 6'-9" 2/15/90 2/22/90 32-36AI 6'-9" 2/15/90 2/22/90 34-36AK 6'-9" 2/15/90 2/22/90 36-71/1AA 20'-0" 2/15/90 2/23/90 2/22/90 3082 10'-9" 2/15/90
.