a ATTACHMENT 1 VIRGINIA ET ECTRIC AND POWER COMPANY NORTH ANNA NUCTEAR-POWER STATION-

-i UNIT 1 I

i s

1989 ANNUAL STEAM GENERATOR INSERVICE INSPECTION REPORT I

'l

'1 I

k J

D 9003070365 900226 m

PDR ADOCK 05000338

[3]

o-Pnr:

Au-

T I'.

6 i

1

.1-ATTACHMENT 1 Page 1 of 24 VIRGINIA ELECTRIC AND POWER COMPANY NORTH ANNA POWER STATION UNIT 1-

~

1989 ANNUAL STEAM GENERATOR INSERVICE INSPECTION REPORT EDDY CURRENT EXAMINATION During 1989 the steam generator tubes were examined once.

This examination occurred during the May refueling outage.

Tubes in "A",

"B",

and "C"

steam generators were examined during the outage.-

The material that follows presents the results of the examinations.

These results include the number and extent of the tubes examiaed, the location and percent of wall-thickness penetration for each indication ofJ an imperfection, and the identification of the tubes that were plugged. is a~ Glossary of Terms, f

P

.[

t

_s l

I'.

(t, f

ATTACHMENT 1 Page 2 of 24

/

REFUELING OUTAGE - MAY 1989 UNIT 1 STEAM GENERATOR "A"

I" EXAMINATION

SUMMARY

I

'In "A"

Steam Generator there were 3074 tube examinations from the-inlet side.

This'is approximately 100 percent of the available-tubes.

These tubes were examined full length (tubesheet-to-tubesheet). = Supplemental examinations were also ' performed using Rotating Pancake,

8x1, and Profilometry probes where - additional confirmatory or other data was t

. desired.

The tubes examined were found to have no indications that are less'than 20% through wall, fifteen indications that are between 20% and 40%-through wall, and.six indications-greater than 40% through wall.

. Thirty-nine tubes were plugged.

Refer to the table below for details.

L

%TWD Location Row-Column Remarks I

SAI' 1H R05C01 PLUGGED SAI 1H R13C04 PLUGGED SAI 3H R03C09 PLUGGED SAI 4H R06C12 PLUGGED MAI 2H R07C18 PLUGGED MAI 3H R07C18 PLUGGED SAI 1H R07C18 PLUGGED' SAI 2H R07C18 PLUGGED SAI 3H R07C18 PLUGGED SAI 1H R07C19 PLUGGED 79 2H R15C21 PLUGGED MAI 2H R15C21 PLUGGED MAI 2H R15C21 PLUGGED 21 AV3 R22C22 20 AV3 R24C22 21 AV3 R25C22 22 AV3 R30C22 SAI 2H R04C23 PLUGGED 52 2H R19C23 PLUGGED MAI 2H R19C23 PLUGGED COI TSH R18C25 PLUGGED 87 2H R05C26 PLUGGED MAI 2H R05C26 PLUGGED SAI 2H R05C26 PLUGGED SAI 2H R07C26 PLUGGED 20 AV3 R38C26 20 AV1 R41C26 COI TSH R16C27 PLUGGED g-30 AV3 R36C27 31 AV2 R37C27 L

20 AV1 R41C27 TSH R17C28 PLUGGED COI 20 AV2 R19C29 31 AV3 R42C29 SAI 2H R16C36 PLUGGED SAI 1H R05C39 PLUGGED SAI 1H R04C40 PLUGGED

([

~

^

f 'i t

V-ATTACHMENT 1 b

Pace 3 of 24

%TWD Location Bow-Column Remarks

+

ct SAI 1H R03C41 PLUGGED COIs TSH R21C42 PLUGGED SAI 7H R10C48 PLUGGED COI TSH R20C51

-PLUGGED COI' TSH R23C52 PLUGGED COI-TSH R23C53 PLUGGED 1

COI TSH R26C54 PLUGGED SAI 4H R30C54 PLUGGED hmI 2H R20C55 PLUGGED

~SAI 5H R02C58 PLUGGED COI TSH R29C59 PLUGGED

)

SAI IH R02C60 PLUGGED'

'COI TSH R27C61 PLUGGED 55 2H R40C63 PLUGGED SAI

'1H R40C63 PLUGGED COI TSH R12C65 PLUGGED 20 AV2 R38C65 23-

'AV2 R39C66 23 AV3 R39C66 29 AV3 R40C66 SAI 5H R04C68 PLUGGED.

SAI 1H R06C68 PliUGGED 70 4H R09C75 PLUGGED SAI 4H R09C75 PLUGGED SAI 1H R18C78 PLUGGED-SAI 1H-R18C78

' PLUGGED.

' 4 7.

4H R11C84 PLUGGED SAI 4H R11C84 PLUGGED i

SAI 3H R25C87 PLUGGED

.SAI.

2H R17C90 PLUGGED s

h

U

\\

ATTACHMENT 1 Page 4 of 24 REFUELING OUTAGE - MAY 1989 UNIT 1 STEAM GENEPATOR "B" EXAMINATION

SUMMARY

In "B"

Steam Generator there-were 3171 tube examinations'from the inlet side.

This is approximately 100 percent of the available tubes.

These tubes were examined full length (tubesheet-to-t ubesheet).

Supplemental examinations were also performed using Rotating Pancake, 8 x 1, and Profilometry probes where additional confirmatory or other data was desired.

The tubes examined were found to have a total of two indications that are less than 20% through wall, 663 indications that are between 20% and 40% through wall, and thirteen. indications greater than 40% through wall.

Fifty-two tubes were plugged.

Refer to the table below for details.

%TWD Location Row-column Remarks 63 3H R02C05 PLUGGED SAI 3H R02C05 PLUGGED MAI 1H R02C06 PLUGGED MAI 1H R02C07 PLUGGED 20 AV1 R23C08 20 AV2 R23C08 27 AV2 R24C08 20 AV2 R23C09 25 AV1 R23C09 INR AV3 R23C09 22 AV1 R24C09 20 AV1 R25C09 R26C09 20 AV1 24 AV2 R23C10 20 AV2 R24C10 30 AV2 R25C10 32 AV1 R26C10 SAI 1H R03C11 PLUGGED 20 AV3 R16C11 23 AV4 R24C11 25 AV2 R24C11 28 AV1 R24C11 21 AV2 R25C11 22 AV3 R27C11 24 AV1 R23C12 29 AV2 R23C12 20 AV2 R24C12 b

23 AV1 R25C12 26 AV2 R25C12 31 AV2 R25C12 31 AV3 R25C12 20 AV2 R30C12 20 AV2 R30C12 21 AV3 R30C12 20 AV3 R24C13 27 AV1 R24C13 24 AV4 R25C13

qb

'c

' ATTACHMENT 1-

fhf, l

Page 5 of 24 1THQ Location Row-Column Remarks 26 AV1 R25C13

'27 AV3-R25C13 l

23 AV4 R26C13 2C AV1 R26C13

~24 AVs R26C13

'27-AV2 R26C13 22 AV2 R27C13-24 AV1 R27C13 4

26 AV4 R27C13 l

30 AV3 R27C13 20 AV3 R29C13 23 AV4 R29C13 26 AV2 R29C13 27 AV1 R29C13 22 AV2 R30C13

'28 AV1 R30C13 24 AV2 R15C14 21 AV3 R17C14 25 AV4 R17C14 22 AV4 R20C14 l

20 AV3 R21C14 21 AV4 R21C14.

20 AV4 R23C14 24 AV2 R23C14 20 AV1 R24C14 20 AV4 R24C14 25 AV2 R24C14 21 AV4 R25C14 22 AV2 R25C14 20 AV1 R26C14-L 25 AV2 R26C14 25 AV4 R26C14 20 AV3 R27C14 l

l 23 AV1 R27C14-

29 AV2 R27C14 1'

21-AV2 R28C14 23 AV4 R29C14 24 AV1 R29C14 26 AV2 R29C14 20-AV3 R13C15 20 AV1 R17C15 24 AV3-R17C15 20 AV3 R19C15 20 AV3 R22C15 25 AV2 R23C15 27 AV1 R23C15 23 AV1 R24C15 26 AV2 R24C15 20 AV1 R25C15 22 AV2 R25C15 20 AV2 R26C15 24 AV2 R27C15 20 AV4 R28C15 4

1k.

e

e t

ATTACHMENT 1 4

Page 6 of 24 11MQ Location Row-column Renarks 20 AV4 R29C15 23 AV3 R29C15 6

26 AV1 R29C15 28 AV2 R29C15 20 AV3 R31C15 22 AV1 R16C16 21 AV3 R17C16 22 AV4 R18C16 23 AV2 R23C16 27 AV1 R23C16 IHR AV3 R23C16 INR AV4 R23C16 23 AVE R24C16 25 AV2-R24C16 20 AV4 R25C16 25 AV2 R25C16 26 AV1 R25C16 20 AV3 R26C16 24 AV4 R26C16 25 AV1 R26C16 29 AV2 R26C16 20 AV2 R27C16 21 AV4 R27C16 24 AV1 R27C16 21 AV3 R29C16 23 AV4 R29C16 26 AV1 R29C16 31 AV2 R29C16 20 AV4 R32C16 23 AV1 R32C16 27 AV2 R32C16 23 AV2 R33C16 27 AV1 R33C16 3

23 AV2 R15CFF 24 AV2 R25C10 24 AV3 R25C17 21 AV3 R27C17 22 AV4 R27C17 26 AV1 R27C17 27 AV2 R27C17 22 AV2 R30C17 24 AV1 R32C17 25-AV2 R32C17 I

21 AV3 R20C18 23 AV3 R21C18 22 AV3 R22C18 21 AV2 R23C18 22 AV3 R23C18 21 AV3 R24C18 1

22 AV1 R24C18 22 AV2 R24C18 24 AV2 R25C18 24 AV1 R27C1B l

L o

t ATTAPHMENT 1 Page 7 of 24 iT]gn Location Row-Column Egggrig 24 AV2 R27018 26 AV4 R29C18 29 AV2 R29C18 22 AV1 R32C18 22 AV2 R32C18 23 AV3 R33C1B 24 AV1 R33C18 24 AV2 R33C18 89 1H R34C18 PLUGGED SAI 1H R34C18 PLUGGED 21 AV4 R35C18 SAI 3H R07C19 PLUGGED 21 AV3 R16C19 INR AV4 R16C19 23 AV3 R17C19 21 AV1 R21C19 21 AV3 R21C19 23 AV2 R21C19 23 AV3 R22C19 26 AVI R23C19 26 AV2 R23C19 22 AV4 R24C19 23 AV3 R24C19 28 AV2 R24C19 34 AV1 R24C19 25 AV1 R25C19 27 AV2 R25C19 23 AV4 R26C19 24 AV1 R26C19 24 AV2 R26C19 24 AV3 R26C19 21 AV3 R27C19 21 AV4 R27C19 INR AVI R27C19 21 AV3 R28C19 21 AV2 R29C19 20 AV3 R30C19 1

21 AV3 R31C19 23 AV2 R32C19 24 AV1 R32C19 21 AV2 R33C19 23 AV1 R33C19 L

21 AV3 R35C19

?

24 AV3 R15C20 23 AV3 R17C20 24 AV3 R18C20 23 AV3 R21C20 21 AV3 R23C20 22 AV1 R24C20 23 AV2 R24C20 24 AV3 R24C20 21 AV2 R25C20 21 AV3 R25C20

6

.1; ATTACHMENT 1 Page B of 24 11EQ Location Row-column Remarks 23 AV1 R25C20 24 AV4 R25C20 23 AV4 R26C20 24 AV3 R26C20 1

27 AV1 R26C20 21 AV3 R28C20 21 AV4 R28C20 21 AV3 R29C20 22 AV2 R29C20 29 AV1 R29C20 29 AV4 R29C20 23 AV2 R30C20 23 AV3 R30C20 25 AV4 R30C20 28 AV1 R30C20 21 AV4 R32C20 23 Avi R32C20 24 AV2 R32C20 24 AV3 R32C20 24 AV2 R33C20 20 AV4 R34C20 21 AV2 R34C20 MAI 2H R02C21 PLUGGED j

21 AV1 R15C21 25 AV1 R16C21 27 AV3 R19C21 24 AV2 R20C21 24 AV4 R20C21 25 AV3 R20C21 21 AV4 R22C21 24 AV3 R22C21 21 AV4 R23C21 23 AV1 R23C21 25 AV3 R23C21 26 AV2 R23C21 21 AV3 R24C21 21 AV4 R24C21 23 AV1 R24C21 25 AV2 R24C21 21 AV3 R25C21 21 AV4 R25C21 23 AV1

.R25C21 26 AV2 R25C21 22 AV1 R27C21 i'

23 AV3 R27C21 22 AV2 R28C21 22 AV3 d28C21 23 AV1 R29C21 25 AV4 R29C21 26 AV2 R29C21 26 AV3 R29C21 25 AV2 R30C21 27 AV3 R30C21

k i-ATTACMMENT 1 c

Pace 9 of 24 iTHQ Location Row-Column Remarks 20 AV3 R33C21 21 AV2 R33C21 22 AV2 R36C21 21 AV3 R37C21 22 AV3 R38C21 SAI 1H R07C22 PLUGGED i

22 AV3 R16C22 23 AV2 R20C22 21 AV2 R27C22 24 AV1 R27C22 23 AV3 R28C22 23 AV1 R33C22 25 AV2 R33C22 25 AV4 R37C22 23 AV3 R18C23 22 AV4 R24C23 PLUGGED 24 AV1 R24C23 PLUGGED-24 AV3 R24C23 PLUGGED 34 AV2 R24C23 PLUGGED 22 AV2 R26C23 25 AV3 R26C23 22 AV3 E27C23 30 AV3 R29C23 22 AV3 R30023 24 AV2 R32C23 25 AV3 R32C23 26 AV1 R32C23 22 AV1 R33C23 22 AV2 R33C23 25 AV3 R33C23 21 AV1 R17C24 21 AV3 R24C24 24 AV2 R24C24 22 AV2 R25C24 21 AV2 R26C24 24 AV2 R26C24 22 AV1 R29024 23 AV4 R29C24 25 AV2 R29C24 25 AV3 R29C24 24 AV2 R32C24 24 AV4 R32C24 28 AV3 R32C24 I

33 AV1 R32C24 25 AV4 R38C24 21 AV3 R40C24 MAI 1H R03C25 PLUGGED INR' AV3 R17C25 22 AV3 R18C25 INR 4H R24C25 31 AV2 R25C25 21 AV2 R26C25 23 AV2 R27C25

e 4

ATTACHMENT 1 Page 10 of 24 1THQ Location Row-column Remarks t

22 AV2 R29C25 INR AV4 R31025 20 AV2 R24C26 INR AV1 R24C26 INR AV3 R24C26 22 AV1 R25C26 I

23 AV2 R25C26 22 AV1 R26C26 22 AV3 R26C26 73 AV2 R26C26 INR AV1 R29C26 20 AV4 R32C26 22 AV2 R33C26 21 AV3 R34C26 INR AV1 R38C26 23 LV3-R24C27 y

24 AV1 R24C27 26 AV2 R24C27 22 AV2 R25C27 26 AV2 R26C27 SAI 7C R02C23 PLUGGED SAI 7C R02C28 PLUGGED SAI 1H R07C28 PLUGGED INR AV3 R18C28 28 AV3 R23C28 31 AVI R23C28 INR AV2 R23C28 27 AV3 R24C28 28 AV3 R24C28

+

31 AV2 R24C28 INR AV1 R25C28 INR AV2 R25C28 INR AV3 R25C28 22 AV2 R26C28 INR AV1 R26C28 INR AV3 R26C28 INR AV4 R26C2C 21 AV2 R32C28 23 AV3 R32C28 25 AV3 R36C28 21 AV3 R39C28 26 AV2 R19C29 30 AV1 R19C29 k

30 AV3 R19C29 INR AV4 R19C29 22 AV3 R24C29 24 AV2 R24C29 INR AV1 R24C29 22 AV3 R25C29 27 AV1 R25C29 28-AV2 R25C29 23 AV1 R26C29 25 AV2 R26C29

F t

9 ATTACHMENT 1 Page 11 of 24 j

llHQ Location Row-column Remarks 26 AV3 R26C29 22 AV3 R27C29 25 AV2 R29C29 INR AV1 R29C29 INR AV3 R29C29 INR AV4 R29C29 23 AV3 R34C29 33 AV2 R21C30 23 AV2 R24C30 21 AV2 R25C30 25 AV3 R26C30 21 AV3 R27C30 30 AV1 R41C30

-21 AV1 R23C31 INR AV3 R24C31 INR AV4 R24C31 21 AV1 R25C31 29 AV2 R25C31 INR AV3 R25C31 24 AV4 R27C31 29 AV3 R27C31 22 AV1 R29C31 24 AV2 R29C31 26 AV3 R29C31 INR AV1 R33C31 22 AV3 R34C31

_INR AV2 R35C31 14 AV2 R37C31 21 AV3 R38C31 22 AV3 R13C32 27 AV3 R24C32 29 AV1 R24C32 22 AV1 R25C32 23 AV3 R26C32 INR AV4 R26C32 27 AV1 R27C32 21 AV2 R30C32 22 AVI R32C32 i

INR AV1 R35C32 INR AV3 R36C32 l

23 AV2 R23C33 i

24 AV1 R23C33 24 AV2 R25C33 l

h 24 AV3 R25C33 I

27 AV1 R25C33 27 AV2 R26C33 29 AV3 R26C33 26 AV3 R27C33 INR AV1 R29C33 INR AV2 R29C33 l

26 AV3 R30C33 i

28 AV2 R30C33 28 AV3 R36C33 li

.j

w, i

F ATTACHMENT 1 y

Page 12 of 24 i

11ED Location Row-Column Remarks 4

~

21 AV3 R37C33 23 AV1 R39C33 PLUGGED 34 AV2 R39C33 PLUGGED 24 AV2 R18C34 23 AV1 R23C34 27 AV2 A24C34 28 AV1 R27C34 21 AV2 R29C34 23 AV1 R29C34 l

23 AV1 R32C34 INR AV1 R21C35 i

INR AV4 R21C35 22 AV2 R23C35 L

COI TSH R24C35 PLUGGED 22 AV2 R25C35 22 AV3 R28C35 26 AV2 R28C35

-INR AV2 R31C35 26 AV1 R33C35 27 AV2 R33C35 20 AV1 R36C35 26 AV2 R36C35 INR AV1 R20C36 22 AV1 R34C36 25 AV2 R34C36 21 Avi R35C36 l

21 AV2 R35C36 22 AV1 R36C36 32 AV2 R36C36 23 AV2 R37C36 23 AV2 R38C36 20 AV1 R40C36 21 AV2 R42C36 INR AV1 R44C36 INR AV2 R44C36 INR AV3 R44C36 SAI 1H R06C37 PLUGGED 23 AV2 R28C37 L

24 AV1 R33C37 22 AV1 R34C37 23 Avi R35C37 25 AV2 R35C37 INR AV1 R41C37

~

INR AV1 R42C37 21 AV1 R43C37 21 AV2 R43C37 INR AV1 R44C37 24 AV3 R29C38 23 AV3 R32C38 21 AV2 R34C38 25 AV1 R34C38 95 1H R14C39 PLUGGED COI TSH R14C39 PLUGGED E

[

e -

4 ATTArHMPMT 1

[

Page 13 of 24 iTHQ Location Row-Column Remarks j

SA1 1H R14C39 PLUGGED COI TSH R28C39 PLUGGED 21 AV2 R29C39 22 AV2 R35C39 24 AV1 R35C39

}

INR AV1 R40C39 MAI 1H R03C40 PLUGGED I

21 AV2-R32C40 21 AV2 R34C40 INR AV2 R44C40 l

SAI IH R07C41 PLUGGED COI TSH R24C41 PLUGGED INR AV1 R39C41 L

INR AV2 R39C41 INR AV3 R39C41 14 TSH R17C42 23 AV3 R20C42 22 AV4 R21C42 MAI 1H R25C42 PLUGGED 23 AV3 R27C42 21 AV4 R32C42 INR AV4 R41C42 76 1H R11C43 PLUGGED SAI 1H R11C43 PLUGGED 22 AV4 R13C43 SAI 1H R34C43 PLUGGED 23 AV1 R16C44 PLUGGED 23 AV4 R16C44 PLUGGED SAI 1H R16C44 PLUGGED l

t COI TSH R18C44 PLUGGED 21 AV4 R20C44 MAI-3H R11C45 PLUGGED i

22 AV4 R12C46 SAI 2H R16C46 PLUGGED 70 1H R14C47 PLUGGED 96 1H R14C47 PLUGGED MAI 1H R14C47 PLUGGED SAI TSH R18C47 PLUGGED 94 1H R11C48 PLUGGED MAI IH R11C48 PLUGGED 96 1H R12C48 PLUGGED MAI 1H R12C48 PLUGGED 21 AV4 R21C48 h

22 AV2 R34C48 22 AV1 R41C48

INR, AV1 R19C49 22 AV4 R20C49 21 AV1 R33C49 21 AV1 R35C49 22 AV1 R39C49 INR AV1 R40C49 I

21 AV1 R42C49 INR AV2 R42C49

e

[

ATTANIMENT 1 Pace 14 of 24 lIMD Location Row-column Remarks 24 AV1 R43C49 22 AV1 R10C50 22 AVI R28C50 21 AV1 R29C50 23 AV1 R31C50 21 AV3 R32C50 25 AV1 R35C50 21 AV1 R37C50 22 AV1 R40050 L

23 AV1 R41C50 21 AV1 R42C50 22 AV1 R43C50 22 AV3 R18C51 24 AV2 R25C51 MAI 1H R28C51 PLUGGED 22 AV2 R36C52 24 AVI R36C52 L

31 AV3 R36CS2 22 AV3 R37C52 29 AV3 R39C52 22 AV3 R41C52 23 AV1 R41C52 22 AV3 R44C52 SAI 2H R05C53 PLUGGED SAI IH R15C53 PLUGGED COI TSH R16C53 PLUGGED 22 AV3 R27C53 MAI 3H R30C53 PLUGGED 23 AV3 R39C53 22 AV3 R40C53 MAI 1H R13C54 PLUGGED 26 AV2 R16CSA PLUGGED SAI 1H R16C3C PLUGGED 23 AV1 R22C54 I

COI TSH R26C54 PLUGGED 24 AV3 R36C54 21 AV3 R39C54 INR AV2 R39054 23 AV2 R41C54 INR AV3

-R41C54 23 AV3 R43C54 25 AV2 R43C54 23 AV3 R44C54 h

26 AV2 R44C54 23 AV3 R19C55 23 AV2 R43C55 96 3H R04C56 PLUGGED MAI 3H R04C56 PLUGGED 29 AV4 R12C56 1

27 AV4 R14C56 INR AV2 R20C56 21 AV3 R21C56 23 AV4 R21C56 4

I '..

-e ATTAFHMFNT 1 j)-

Page 15 of 24

[

1TWQ Location Egy-Column Remarks INR AV1 R21C56 27 AV4 R23C56 25 AV2 R35C56 28 AV2 R36056 22 AV3 R41C56 22 AV2 R45C56 25 AV3 R20C57 23 AV1 R29C57 24 AV2 R36C57 22 AV2 R42C57 25 AV2 R43C57 26 AV2 R44C57 27 AV4 R18C58 24 AV3 R22C58 26 AV3 R25C58 27 AV2 R28C56 27 AV3 R28C58 24 AV3 R37C58 21 AV3 R40C58 23 AV3 R41C58 25 AV3 R44C50 26 AV2 R44C58 21 AV3 R45C58 26 AV2 R45C58 26 AV3 R16C59 24 AV3 RTTC59 25 AV2 R32C59 27 AV2 R44C59 24 AV2 R45C59 66 1H R11C60 PLUGGED MAI 1H R11C60 PLUGGED 24 AV2 R15C60 24 AV3 R15C60 23 AV3 R22C60 26 AV2 R27C60 27 AV3 R27C60 29 Avi R28C60 29 AV1 R30060 27 AV2 R31C60 24 AV1 R32C60 28 AV2 R32C60 26 AV3 R33C60 27 AV1 R33C60 25 AV3 R13C61 24 AV3 R16C61 25 AV2 R11C62 22 AV2 R28C62 23 AV3 R32C62 24 AV2 R34C62 23 AV1 R29C63 26 Avi R31C63 23 AV1 R35C63 22 AV1 R37C63 6

I

,6 ATTAFHMENT 1 i

Page 16 of 24

[

LIED Location Row-Column Rema rk s 1

l 23 AV2 R37C63 22 AV3 R41C63 22 AVI R23C64 INR AV4 R08C65 21 AV1 R27C65 28 AVI R29C65 26 AV2 R31C65 26 AV1 R33C65 INR AV1 R39C65 25 AV2 R40C65 INR AV1 R41C65 25 AV2 R28C66 f

22 AV3 R29C66 29 AV2 R29C66 INR AV2 R38C66 SAI 1H R12C67 PLUGGED 24 AV3 R21C67 26 AV2 R22C67 l

29 AV4 R22C67 31 AV3 R22C67 23 AV2 R30C67 26 AV1 R30C67 22 AV4 R32C67 23 AV3 R32C67 26 AV1 R32C67 27 AV2 R32C67 26 AV2 R37C67 30 AV2 R39C67 30 AV1 R42C67 32 AV2 R42C67 24 AV4 R19C68 23 AV2 R20C68 25 AV1 R30C68 25 AV2 R30C68 24 AV2 R33C68 98 1H R35C68 PLUGGED MAI 1H R35C68 PLUGGED 26 AV2 R40C68 INR AV2 R22C69 25 AV2 R24C69 23 AV2 R32C69 23 AV2 R41C69 INR AV1 R41C69 INR AV3 R41C69 INR AV1 R09C70 INR AV4 R09C70 26 AV3 R23C70 25 AV4 R24C70 28 AV3 R24C70 25 AV3 R27C70 24 AV2 R28C70 23 AV2 R31C70 24 AV2 R33C70

ATTACHMENT 1 Page 17 of 24 11MD Location Row-column Remarks i

21 AV3 R35C70 22 AV1 R35C70 22 AV2 R35C70 26 AV3 R36C70 27 AV2 R36C70 24 AV3 R39C70 22 AV3 R40C70 28 AV1 R12C71 28 AV4 R12C71 25 AV2 R16C71 27 AV2 R17C71 22 AV3 R21C71 27 AV2 R23C71 23 AV3 R24C71 25 AV4 R24C71 25 AV2 R25C71 26 AV2 R26C71 21 AV3 R31C71 26 AV2 R31C71 INR AVI R31C71 23 AV3 R32C71 27 AV2 R32C71 22 AV3 R33C71 24 AV1 R33C71 25 AV2 R33C71 27 AV2 R35C71 26 AV2 R39C71 INR AV4 R12C72 27 AV2 R15C72 INR AV2 R16C72 26 AV2 R24C72 27 AV1 R24C72 25 AV2 R27C72 26 AV1 R27C72 25 AV1 P'BC72 26 AV2 R30C72 29 AV2 R31C72 24 AV2 R32C72 COI TSH R10C73 PLUGGED 26 AV2 R15C73 26 AV3 R17C73 30 AV2 R17C73 26 AV1 R19C73 k

MAI 1H R24C73 PLUGGED i

26 AV3 R33C73 25 AV3 R34C73 26 AV4 R12C74 INR AV1 R12C74 26 AV4 R13C74 INR AV3 R15C74 25 AV2 R21C74 INR AV1 R27C74 30 AV2 R32C74

.i O

O ATTACHMENT 1 Page la of 24 s

lIEQ location Row-column Remarks 25 AV2 R33C74 MAI 2H R34C74 PLUGGED INR AV2 R38C74 INR AV1 R11C75 INR AV4 R11C75 28 AV2 R24C75 23 AV1 R27C75 25 AV2 R27C75 84 1H R34C75 PLUGGED SAI 1H R34C75 PLUGGED 22 AV4 R37C75 23 AV3 R37C75 INR AV4 R12C77 25 AV3 R14C77 25 AV4 R14C77 26 AV1 R14C77 28 AV2 R14C77 21 AV1 R16C77 22 AV4 R16C77 24 AV3 R16C77 26 AV3 R23C77 25 AV2 R33C77 21 AV3 R17C78 22 AV1 R17C78 23 AV2 R17C78 23 AV3 R24C78 25 Avi R24C78 25 AV2 R24C78 26 AV4 R24C78 21 AV4 R26C78 23 AV1 R29C78 i

21 AV1 R30C78 23 AV2 R31C78 22 AV2 R32C78 25 AV2 R33C78 24 AV1 R17C79 27 AV1 R21C79 22 AV2 R16C80 29 AV2 R17C80 23 AV2 R21C80 24 AV3 R21C80 25 AV4 R21080 29 AV2 R22C90 h

INR AV1 R22C80 93 1H R14C83 PLUGGED SAI 1H R14C83 PLUGGED 25 AV4 R21C83 26 AV2 R21C83 28 AV3 R21C83 27 AV2 R26C83 23 AV1 R30C83 27 AV2 R16C85 22 AV2 R17C85

p I

L '6 -

ATTAPHMENT 1 p

Page 19 of 24 i1 -

%TWD Location Row-column Remarks 23 AV4 R17C85 25 AV2 R18C85

)

23 AV4 R18C85 23 AV3 R22C85 26 AV1 R22C85 L

22 AV2 R24C85 22 AV4 R24C85 21 AV2 R25C85 25 AV3 R17C86 24 AV1 R25C86 24 AV2 R25C86 22 AV3 R26C86 30 AV1 R11C87 27 AV4 R17C87 26 AV2 R18C87 26 AV4 R18C87 24 AV4 R22C87 MAI 3H R25C87 PLUGGED SAI 2H R25CG7 PLUGGED 28 AV2 R12C88 26 AV2 R17C88 24 AV2 R22C88 27 AV1 R22C88 27 AV3 R22C88 26 AV3 R21C89 28 AV1 R11C90 INR AV3 R18C90 21 AV3 R17C91 SAI 7H R02C92 PLUGGED INR AV1 R13C92 l

l

[L c

ATTACHMENT 1 Page 20 of 24 REFUELING OUTAGE - MAY 1989 UNIT 1 STEAM GENERATOR "C"

E)tAMINATION

SUMMARY

In "C" Steam Generator there were 3008 tube examinations from the inlet side.

This is approximately 100 percent of the available tubes.

These tubes were examined full length (tubesheet-to-tubesheet).

Supplemental examinationa were also performed using Rotating Pancake,

0x1, and Profilometry probes where additional confirmatory or other data was desired.

The tubes examined were found to have a total of six indications that are less than 20% through wall, 153 indications that are between 20% and 40% through wall and four indications greetar than 40%

through wall.

Sixty-five tubes were plugged.

Refer to the table below for details.

ATWD Location Row-Column Remarks INR AV3 R17C05 SAI 3H R03C08 PLUGGED INR AV1 R14C08 MAI TSH R24C08 PLUGGED MAI 2H R03C09 PLUGGED MAI 2H R06C09 PLUGGED 23 AV3 R16C09 INR AV3 R17C09 21 AV3 R20C09 23 AV2 R20C09 INR AV4 R20C09 21 AV2 R24C09 22 AV4 R24C09 23 AV3 R24C09 26 AV3 R24C09 26 AV3 R24C09 26 AV4 R24C09 21 AV3 R19C10 22 AV2 R19C10 21 AV3 R20C10 24 AV2 R20C10 21 AV2 R26C10 MAI 3H R02C11 PLUGGED INR AV2 R12C11 23 AV1 R20C11 21 AV3 R22C11 21 AV1 R23C11 26 AV3 R23C11 SAI 3H R11C12 PLUGGED INR AV3 R21C12 20 AV3 R22C12 20 AVI R24C12 21 AV2 R26C12 21 AV4 R28C12 23 AV4 R29C12 INR AV2 R30C12 22 AV3 R18C14

r~

z

+-

ATTAEMMENT 1 y,

Pace 21 of 24 s

11MQ Location Row-column Remarig 24 AV2 R24C14 27 AV3 R24C14 24 AV1 R26C14 28 AV2 R26C14 21 AV3 R27C14 SAI 1H R29C15 PLUGGED MAI 2H R12C16 PLUGGED 22 AV2 R16C16 20 AV3 R20C16 22 AV3 R31C16 SAI 2H R12C19 PLUGGED i

SAI 3H R12C19 PLUGGED INR AV3 R28C19 30 AV3 R34C19 20 AV4 R36C19 20 AV2 R24C20 21 AV3 R24C20 23 AV3 R29C21 22 AVI R14C22 21 AV4 R17C22 21 AV3 R25C22 INR AV3 R35C22 21 AV3 R18C23 21 AV4 R18C23 INR 1C R19C23 20 AV3 R22C23 INR AV2 R28C23 21 AV2 R31C23 20 AV2 R32C23 21 AV3 R39C23 SAI 1H R04C24 PLUGGED 21 AV4 R14C24 INR AV2 R26C24 INR 6C R26C24 INR 2C R34C24 23 AV1 R37C24 29 AV2 R37C24 21 AV2 R39C26 21 AV3 R35C27 21 AV2 R38C27 23 AV3 R38C27 MAI 2H R05C28 PLUGGED 15 2C R31C28 I

23 AV2 R32C28 22 AV4 R18C29 22 AV3 R23C29 23 AV3 R24C29 20 AV4 R29C29 23 AV3 R32C29 SAI 2H R02C30 PLUGGED 22 AV3 R25C30 21 AV2 R31C30 23 AV2 R37C30

I h

~

ATTAFHMENT 1 Pnge 22 of 24 11MD Location Row-Column Remarks 21 AV1 R40C30 21 AV2 R40C30 21 AV3 R38C31 21 AV3 R39C31 23 AV2 R40C31 24 AV3 R40C31 24 AV3 R41C31 20 AV3 R19C32 20 AV1 R23C32 COI TSH R19C33 PLUGGED COI TSH R20C33 PLUGGED 22 AV4 R21C33 12 9 AV3 R25C33 1

20 AV3 R37C33 22 AV1 R37C33 20 AV3 R40C33 86 1H R21C35 PLUGGED SAI 1H R21C35 PLUGGED 22 AV2 R25C35 SAI 1H R06C36 PLUGGED MAI TSH R27C36 PLUGGED 20 AV2 R45C36 92 1H R16C37 PLUGGED SAI 1H R16C37 PLUGGED 20 AV3 R22C38 22 AV2 R22C38 MAI TSH R26C38 PLUGGED 20 AV3 R27C38 23 AV2 R28C38 23 AV3 R28C38 18 AV3 R30C38 21 AV3 R31C38 21 AV3 R32C38 21 AV1 R33C38 21 AV2 R33C38 20 Av3 R28C39 21 AV3 R30C39 INR AV1 R27C40 22 TSH R28C40 SAI 2H R11C41 PLUGGED SAI 2H R11C41 PLUGGED MAI 1H R45C43 PLUGGED 22 AV2 R45C44 h

27 TSH R12C45 35 TSH R12C45 24 AV4 R17C45 22 AV4 R19C45 INR AV2 R19C45 23 Avi R39C45 INR 1C R42C46 MAI 3H R02C47 PLUGGED 37 4H R09C48 PLUGGED SAI 4H R09C48 PLUGGED

c ATTAPHMENT 1 Page 23 of 24 1TWD Location Row-column Remarks COI TSH R21C48 PLUGGED COI TSH R26C48 PLUGGED i

COI TSH R26C48 PLUGGED 20 AV3 R28C48

)

INR AV4 R29C48 31 TSH R32C48 COI TSH R25C49 PLUGGED COI TSH R25049 PLUGGED i

SAI 1H R34C49 PLUGGED 20 AV2 R44C49 MAI 2H R13C50 PLUGGED SAI 1H R14C50 PLUGGED 21 AV3

.R38C50 tiAI IH R13C51 PLUGGED SAI 1H R15C51 PLUGGED 26 Avi R20C51 24 AV3 R27C51 24 AV3 R28C51 24 AV3 R29C51 22 AV3 R32C51 27 AV4 R34C51 PLUGGED l

28 AV2 R34C51 PLUGGED 32 AV2 R34C51 PLUGGED i

32 AV4 R34C51 PLUGGED 43 AV3 R34C51 PLUGGED 21 AV3 R30C52 24 AV2 R34C52 21 AV2 R37C52 23 AV3 R39C52 1

SAI 1H R14C53 PLUGGED MAI 1H R13C54 PLUGGED MAI' 2H R14C54 PLUGGED COI 2H R15C54 PLUGGED 98 3H R33C54 PLUGGED SAI 1H R33C54 PLUGGED SAI 3H R33C54 PLUGGED l

l COI TSH R13C55 PLUGGED SAI 2H R24C57 PLUGGED INR AV3 R12C58 21 AV4 R14C58 24 AV1 R43C58 SAI IH R03C60 PLUGGED MAI 1H R06C60 PLUGGED MAI 1H R06C61 PLUGGED 22 AV2 R24C62 SAI 2H R30C62 PLUGGED SAI 2H R25C64 PLUGGED INR AV2 R30C65 SAI 2H R10C66 PLUGGED 23 AV1 R20066 23 AV4 R20C66 COI TSH R23C67 PLUGGED INR AV3 R25C67

4 ATTAPHMPNT 1 Pace 24 of 24

[

IIEQ Location Row-column Remarks 22 AV2 R29C67 22 AV2 R24C70 26 AV1 R24C70 25 AV3 R32C70 22 AV1 R33C70 24 AV3 R33C70 22 AV3 R37C70 20 AV3 R38C70 MAI IH R03C71 PLUGGED COI TSH R06C71 PLUGGED COI TSH R15C71 PLUGGED SAI 2H R18C71 PLUGGED 24

'AV2 R24C71 SAI 2H R31071 PLUGGED 33 AV2 R35C71 22 AV3 R37C71 24 AV4 R24C72 33 AV3 R24C72 29 AV2 R24C73 30 AV3 R24C73 30 AV2 R25C73 20 AV3 R29C73 28 AV3 R34C73 20 AV3 R37C74 20 AV3 R19C75 26 AV3 R21C75 20 AV3 R22C75 20 AV3 R23C75 24 AV3 R25C75 20 AV3 R30C75 24 AV3 R32C75 22 AV3 R34C75 18 AV3 R19C76 28 AV3 R20C76 22 AV3 R22C76 21 AV3 R26C76 INR AV3 R27C76 24 AV3 R28076 21 AV3 R29C76 18 AV3 R30C76 19 AV3 R31C76 18 AV3 R33C76 21 AV2 R37C76 y

SAI 2H R14C77 PLUGGED MAI 1H R07C81 PLUGGED SAI 2H R20C81 PLUGGED SAI 1H R24C81 PLUGGED SAI 2H R25C81 PLUGGED 32 AV4 R14C86 MAI 1H R03C91 PLUGGED SAI 2H R06C92 PLUGGED

p.

O-' 7 l.

i I

AT1ACMMENT 2 VIRGINIA ELECTRIC AND POWER COMPANY i

1 NORTH ANNA NUCf. EAR POWER STATION UNIT 2

]

)

1989 ANNUAL STEAM GENERATOR

]

INSERVICE INSPECTION REPORT i

o I

L a -'

/

ATTAEMMENT 2 e

Page 1 of 6 VIRGINIA ELECTRIC AND POWER COMPANY NORTH ANNA POWER STATION UNIT 2 1989 ANNUAL STEAM GENERATOR INSERVICE INSPECTION REPORT EDDY CURRENT EXAMINATION During 1989 the steam generator tubes were examined once.

This examination occurred during the February refueling outage.

Tubes in "A",

"B",

and "C"

steam generators were examined during the outage.

The material that follows presents the results of the examinations.

These results include the number and extent of the tubes examined, the location and percent of wall-thickness penetration for each indication of an imperfection, and the identification of the tubes that were plugged.

Refer to Attachment 3 for Glossary of terms used, s

C ATTACHMENT 2 Page 2 of 6 REFUELING OUTAGE - FEBRUARY 1989 UNIT 2 STEAM GENERATOR "A"

EXAMINATION SUl&_ARY In "A"

Steam Generator there were 3237 tube examinations from the inlet side.

This is approximately 100 percent of the available tubes.

These tubes were examined full length (tubesheet-to-tubesheet).

Supplemental examinations were also performed using Rotating Pancake, 8 x 1, and Profilometry probes where additional confirmatory or other data was desired.

The tubes examined were found to have a total of three indications that are less than 20% through wall, and forty indications that are between 20% and 40% through wall.

No tubes were found to have indications greater than 40% through wall.

Four tubes were plugged.

Refer to the table below for details.

%TWD Location Row-Column Remarks

<20 IC R18C06 26 2C R42C31

<20 1H R44C35 COI TSH R15C37 PLUGGED 24 AV2 R33C39 PLUGGED l

35 AV3 R33C39 PLUGGED l

23 AV3 R37C41 21 AV1 R33C42 20 AV2 R22C44 20 AV3 R23C44 i

20 AV4 R23C44 20 AV1 R25C44 23 AV2 R25C44 23 AV4 R25C44 20 AV1 R22C45 26 AV4 R22C45 27 AV3 R22C45 30 AV2 R22C45 19 AV1 R24C45 PLUGGED 24 AV3 R24C45 PLUGGED 36 AV2 R24C45 PLUGGED 25 AV3 R34C45 24 AV2 R35C45 33 AV1 R35C45 i

COI TSH R12C46 PLUGGED 22 AV2 R36C46 INR AV2 R35C47 INR AV4 R35C47 21 AV1 R36C48 21 AV3 R36C48 25 AV2 R36C48 l

25 AV3 R35C49 l

21 AV4 R35C50 L

25 AV2 R35C50 26 AV1 R35C50 28 AV3 R35C50

I

'a O

e ATTAPHMENT 2 e

e Page 3 of 6 I

%TWD Location Row-column Remarks 31 AV2 R29C51 21 AV2 R36C52 l'

21 AV4 R36C52 22 AV3 R36C52 23 AV3 R36C53 34 AV2 R36C53 31 AV2 R29C57 23 TSH R43C57

)

23 AV3 R36C68 27 AV3 R37C68 36 2C R31C81 3

l 1

e

}

p o

ATTArHMENT 2

[.

Page 4 of 6 REFUELING OUTAGE - FEBRUARY 1989 UNIT 2 STEAM GENERATOR "B"

EXAMINATION

SUMMARY

In "B" Steam Generator there were 3258 tube examinations from the inlet side.

This is approximately 100 percent of the available tubes.

These tubes were examined full length (tubesheet-to-tubesheet).

Supplemental examinations were also performed using Rotating Pancake,

8x1, and Profilometry probes where additional confirmatory or other data was desired.

The tubes examined were found to have no indications that are less than 20% through wall, and eighteen indications that are between 20%

and 40% through wall.

No tubes were found to have indications greater than 40% through wall.

Ten tubes were plugged.

Refer to the table below for details.

i

%TWD Location Row-Column Remarks INR 1C R26C10 INR 1C R27C10 SAI TEH R17C12 PLUGGED SAI TEH R27C16 PLUGGED 27 AV4 R35C21 28 AV1 R25C28 31 AV2 R17C29 21 AV1 R26C32 21 AV4 R26C32 26 AV3 R32C44 37 AV3 R39C45 PLUGGED COI TSH R13C48 PLUGGED INR IC R44C48 26 AV1 R39C49 PLUGGED 36 AV2 R39C49 PLUGGED 30 AV3 R39C49 PLUGGED SAI 7H R02C51 PLUGGED SAI 7H R02C51 PLUGGED SAI TSH R15C51 PLUGGED 24 AV2 R39C52 SAI 7H R02C53 PLUGGED SAI.

7H R02C53 PLUGGED 28 AV2 R32C53 22 AV3 R36C53

(

SAI 7H R02C57 PLUGGED SAI 7H R02C57 PLUGGED 23 AV3 R29C58 25 AV4 R29C58 SAI 7H R02C59 PLUGGED SAI 7H R02C59 PLUGGED 28 AV4 R21C63 21 AV1 R09C72 23 TSC R15C77

i o a s ATTAEMMENT 2 Page 5 of 6 t

REFUELING OUTAGE - FEBRUARY 1989 UNIT 2 STEAM GENERATOR "C"

EXAMINATION SUMMAftY In "C"

Steam Generator there were 3220 tube examinations from the inlet-side.

This is approximately 100 percent of the available tubes.

These tubes were examined full length (tubesheet-to-tubesheet).

Supplemental examinations were also performed using Rotating Pancake,

8x1, and Profilometry probes where additional confirmatory or other data was desired.

The tubes examined were found to have a total of four indications that are less than 20% through wall, twenty-four indications that are between 20% and 40% through wall, and seven indications greater than 40% through wall.

Fifteen tubes were plugged.

Refer to the table below for details.

%TWD Location Row-Column Remarks INR 1C R06C01 INR 3C R08CO2 29 2C R09CO2 INR 1C R06C03 35 1H R24C13 PLUGGED MAI 7H R02C19 15 2C R37C21

<20 1H R27C23 SAI TSH R21C24 PLUGGED 62 1H R26C24 PLUGGED 35 1H R08C25 PLUGGED 33 1H R32C29 PLUGGED 33 AV2 R39C31 32 AV3 R39C31 32 1H R29C32 PLUGGED 20 2C R43C33 54 1H R33C35 PLUGGED SAI 1H R05C38 PLUGGED 24 AV2 R24C39 27 AV3 R23C41 45 1H R40C42 PLUGGED 45 1H R35C43 PLUGGED 25 1C R45C43 COI TSH R17C44 PLUGGED 98 7C R02C45 PLUGGED MAI 7C R02C45 PLUGGED h

l l

l

O o

e ATTAEMl4ENT 2

,a Page 6 ot_5 iTWD Location Row-column Remarks 36 AV2 R29C48 PLUGGED 24 AV3 R29C48 PLUGGED 22 AV4 R29C48 PLUGGED 27 IH R18C50 27 AV4 R27C51 27 AV3 R17C53 33 AV4 R37C53 26 1C R44C56 41 AV3 R37C58 PLUGGED 40 AV4 R37C58 PLUGGED 28 AV2 R39C60 MAI 7H R02Cf1 PLUGGED MAI 7H R02C61 PLUGGED SAI 7H R02C62 23 AV2 R23C62 27 AV3 R29C62 MAI 7H R02C64 33 AV1 R34C69 25 AV2 R34C69 COI 7H R02C70 16 1C R21C88

<20 1C R06C93 I

I l

d Q.

o

.c o e ATTACMMENT 3 i

VIRGINIA ELECTRIC AND POWER COMPANY NORTH ANNA NUCf.FAR POWER STATION UNITS 1 AND 2 1999 ANNUAL STEAM GENERATOR I

INSERVICE INSPECTION REPORTS t

[

GLOSSARY OF TERM 3 h..

t.

ATTACHMENT 3 Pace 1 of 2 VIRGINIA ELECTRIC AND POWER COMPANY 3

NORTH ANNA POWER STATION 1

UNITS 1 AND.2 l

1989 ANNUAL STEAM GENERATOR L

. INSERVICE INSPECTION REPORT GLOSSARY OF TERMS Circumferential1y Oriented Indication describes a

1)

CD.I.

circumferential1y oriented indication signal from Rotating Pancake probe data - either single or multiple signals - SCI or MCI will be used if it is possible to clearly detect the number of signals present.

2)

D.1 - Distorted Indication - a possible tube wall loss condition that is unquantifiable with a numeric percent call due to the existing signal characteristics.

3)

IHH - Indication Not Reportable - indicates that a very small tube wall loss condition exists in the data being analyzed that is below the reportable criteria threshold for this specific inspection can be used to address indications called in previous inspections that are still detectable but fall below current criteria.

describes multiple axially Multiple Axial Indication l

4)

MAI.

l oriented indication signals from Rotating Pancake probe data.

5)

MCI - Multiple Circumferentially oriented Indication describes multiple circumferentially oriented indication signals from Rotating Pancake probe data - COI is used if it is impossible to clearly detect the number of signals present.

6)

SAI - Single Axial Indication - describes a single axially oriented l

signal from Rotating Pancake probe data.

~/ )

SC.1 - Single Circumferentially oriented Indication - describes a single circumferentially oriented indication signal from Rotating-Pancake probe data - COI is used if it is impossible to clearly i

detect the number of signals present.

8)

Ifdl - Tube End Hot leg.

9)

TEC - Tube End Cold leg.

10)

ISH - Top of TubeSheet Hot leg.

E 11)

ISC - Top of TubeSheet Col 6 leg.

-J f y '$l - 9 6

ATTACHMENT 3-d to,

Page-2 of 2

..' +.

- 12 ) '

l.C, 13 -- ( # = '.numbe r) of. Support Plate Hot or Cold leg.

e.g.,

3H, 6H, 7C.

13) - AE, AE, AD,; AM - Anti-Vibration Bars 1 thru 4.

4.~.

i l

w 4

i '[

I j,

1 t

\\

w I

5 I

a 1

.j