Ro:On 811007,during Preparation for Disassembly of Check Valve on Normal Charging Line,Bonnet Studs Were Discovered Severely Eroded from Boric Acid.Caused by Leak at Gasketed Flange.Detailed Rept Will Be Provided within 14 Days
ML20011A640
Person / Time
Site: Cook 
Issue date: 10/08/1981
From: Townley E
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
NUDOCS 8110290220
Download: ML20011A640 (1)


Text

'

'+

t IPAf,STAh[~

MR S&Is I' 7/D

- i FAO O

D ff.0 L**",,

INDIANA & MICHIGAN ELECTRIC COMPANY 2M'I DONALD C. COOK NUCLEAR PLANT qgp P.0, Box 458, Bridgman. Liichigan 49106 (616) 465 5901 pg October 8,1981 h

2 /,

2 fkS{b!{l) y ISO 2 %

Mr. J.G. Keppler, Regional Director y

Office of Inspection and Enforement 21 m@gWcu United States Nuclear Regulatory Commission Q

,,y Region III h

799 Roosevelt Road y g y.\\

Glen Ellyn, IL 60137 Operating License DPR-74 Docke t No. 50-316 l

Dear Mr. Keppler:

This is to confirm my verbal report made to your NRC Region III Inspec-tor, Mr. E.R. Swanson, at 1635 hours0.0189 days <br />0.454 hours <br />0.0027 weeks <br />6.221175e-4 months <br /> on October 7, 1981, at which time I informed him of the following event identified at Unit 2 of the Dor.ald C. Cook Nuclear Plant.

In preparation for disassembly of a check valve on our normal charging line, it was discovered that the bonnet studs were severely eroded from boric acid due to a leak at the gasketed flange (3 of the 12 studs were cut completely in half). Material for these studs is carbon steel ASTM A-193-B7.

A special report detailing the complete circumstances surrounding uis event will be submitted to your office within 14 days of this letter.

Sincerely, l

l l

E.L. Townley Acting Plant Manager l

i

/bab cc:

J.E. Dolan INPO R.S. Hunter PNSRC R.W. Jurgensen J.F. Stietzel R.F. Kroeger D.V. Shaller K.J. Vehstedt Dir., IE (40 copies)

E.R. Swanson/N.E. DuBry RO:III Dir., MIPC (4 copies) f L

R.C. Callen G. Charnoff, Esq.

l-J.M. Hennigan W. Lavallee, EPRI 8110290220 011000 gDRADOCKosooog OCT 1 3 1981 gM

-